Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,197,124Inspections Most recent open 2026-08-25 Last loaded 2026-08-28

OSHA Inspection: IDSI PRODUCTS OF GEORGIA, INC.

Follow-up inspection · Health discipline

On , OSHA opened a follow-up health inspection of IDSI PRODUCTS OF GEORGIA, INC. in 68 ROSS ROAD, SAVANNAH, GA 31403 (NAICS 424610). OSHA activity number 339079428.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Idsi Products of Georgia, INC. for free Get an email when a new federal OSHA severe-injury report for Idsi Products of Georgia, INC. is published. One employer, no account, unsubscribe in one click.
Site address
68 ROSS ROAD
City
SAVANNAH
State
GA
ZIP
31403
Mailing
68 ROSS ROAD, SAVANNAH, GA 31405
Inspection type
Follow-up (F)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
424610
Employees
32
Ownership type
Private (A)

6 citations on file for this inspection.

1910.106 E02 II B

Serious Gravity 5 1 instance 10 exposed
Issued
Oct 22, 2013
Penalty
Initial $3,570 · Current $2,142 Reduced
29 CFR 1910.106(e)(2)(ii)(b): 29 CFR 1910.106(e)(2)(ii)(b)(3):     The quantity of liquid that was located outside of an inside storage room or storage cabinet exceeded 120 gallons of Class IB, IC, II or III liquids in containers:     a) In the Production Area, on the right side of the spray booth, on or about and at times preceding to May 21, 2013, 5-55 gallon drums of flammable and combustible liquids were stored outside of a flammable storage room.
Recent events (2)
  • · I (S) $2142
  • · Z (S) $3570

1910.106 E02 IV D

Serious Gravity 5 1 instance 10 exposed
Issued
Oct 22, 2013
Abate by
Nov 18, 2013
Penalty
Initial $2,800 · Current $1,680 Reduced
29 CFR 1910.106(e)(2)(iv)(d): Flammable or combustible liquids were not drawn from or transferred into vessels, containers, or portable tanks within a building only through a closed piping system, from safety cans, by means of a device drawing through the top, or from a container or portable tanks by gravity through an approved self-closing valve:    a) In the production area, on or about and at times proceeding to May 21, 2013, a 55 gallon drum of acetone was not dispensed through a self-closing valve, creating a fire hazard.
Recent events (2)
  • · I (S) $1680
  • · Z (S) $2800

1910.305 B01 II

Serious Gravity 1 1 instance 10 exposed
Issued
Oct 22, 2013
Abate by
Nov 18, 2013
Penalty
Initial $2,100 · Current $1,260 Reduced
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:    (a) Production areas, on or about and at times preceding to May 21, 2013, junction boxes up to 240 volts were missing knockouts, exposing operators and employees working in the area to electrical burn hazards.
Recent events (2)
  • · I (S) $1260
  • · Z (S) $2100

1910.305 C04

Serious Gravity 1 1 instance 2 exposed
Issued
Oct 22, 2013
Penalty
Initial $1,785 · Current $1,071 Reduced
29 CFR 1910.305(c)(4): Faceplates for flush-mounted snap switches. Snap switches mounted in boxes shall have faceplates installed so as to completely cover the opening and seat against the finished surface.    (a) Rear Production Ares, SW Rear exit door, on or about, and at times preceding to May 21, 2013, electrical light snap switch was not properly secured and contained exposed live parts, exposing employees to electrical shock hazards.
Recent events (2)
  • · I (S) $1071
  • · Z (S) $1785

1910.37 B06

Other-than-serious 1 instance 10 exposed
Issued
Oct 22, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(6): Each exit sign was not illuminated to a surface value of at least five foot-candles (54 lux) by a reliable light source and be distinctive in color:  a) Production Area, West exit door, on or about and at times preceding to May 21, 2013, exit light was not illuminated, bulbs were burned out.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

1910.134 A02

Other-than-serious 1 instance 1 exposed
Issued
Oct 22, 2013
Abate by
Nov 18, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.134(a)(2): The employer did not establish and maintain a respiratory protection program which included the requirements outlined in 29 CFR 1910.134(c):  (a) Production Area, painting area, on or about and at times preceding to May 21, 2013, 3M one half mask cartridge respirator was used for painting  tubing inside paint booth.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

View Idsi Products of Georgia, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 339079428.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.