Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,196,249Inspections Most recent open 2026-08-20 Last loaded 2026-08-24

OSHA Inspection: USDA FOREST SERVICE - SAN BERNARDINO NF

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of USDA FOREST SERVICE - SAN BERNARDINO NF in 41374 NORTH SHORE DRIVE BIG BEAR RANGER STATION, FAWNSKIN, CA 92333 (NAICS 924120). OSHA activity number 339119109.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Usda Forest Service - SAN Bernardino NF for free Get an email when a new federal OSHA severe-injury report for Usda Forest Service - SAN Bernardino NF is published. One employer, no account, unsubscribe in one click.
Site address
41374 NORTH SHORE DRIVE BIG BEAR RANGER STATION
City
FAWNSKIN
State
CA
ZIP
92333
Mailing
602 S. TIPPECANOE AVE, SAN BERNARDINO, CA 92408
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Union (A)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
924120
Employees
55
Ownership type
Federal government (D)

8 citations on file for this inspection.

1910.37 B02

Serious Gravity 5 1 instance 15 exposed
Issued
Jul 10, 2013
Abate by
Aug 5, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit":   Hallway Outside Ranger's Office: On or about 05JUN13, an exit door leading outside was not labeled with a sign reading "Exit".
Recent events (1)
  • · Z (S) $0

1910.37 B05

Serious Gravity 5 1 instance 15 exposed
Issued
Jul 10, 2013
Abate by
Aug 5, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(5): Each doorway or passage along an exit access that could be mistaken for an exit must be marked "Not an Exit" or similar designation, or be identified by a sign indicating its actual use (e.g., closet).  Hallway Outside Ranger's Office: On or about 05JUN13, a door leading to the ranger's office was not marked "not an exit".
Recent events (1)
  • · Z (S) $0

1910.157 C04

Serious Gravity 1 1 instance 5 exposed
Issued
Jul 10, 2013
Abate by
Aug 5, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.157(c)(4): Portable fire extinguishers were not kept in their designated places when not being used:   Copy Room: On or about 05JUN13, a fire extinguisher was on the floor and not mounted in its designated location, exposing employees to delay in locating the fire extinguisher in the event of fire.
Recent events (1)
  • · Z (S) $0

1910.303 B02

Serious Gravity 5 3 instances 15 exposed
Issued
Jul 10, 2013
Abate by
Aug 5, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:   (a) Permit Administration Office: On or about 05JUN13, two power strips were connected in series to provide 120VAC electrical service to office equipment.   (b) Botanist Office: On or about 05JUN13, two power strips were connected in series to provide 120VAC electrical service to office equipment.   (c) Break Room: On or about 05JUN13, a relocatable power tap was used to provide 120VAC electrical service to a microwave oven and coffee pot.
Recent events (1)
  • · Z (S) $0

1910.303 B07 I

Serious Gravity 5 1 instance 5 exposed
Issued
Jul 10, 2013
Abate by
Aug 5, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment:   Break Area: On or about 05JUN13, 120VAC live conductors were exposed to inadvertent employee contact where an opening on an electrical box was left uncovered.
Recent events (1)
  • · Z (S) $0

1910.303 G01

Serious Gravity 1 1 instance 5 exposed
Issued
Jul 10, 2013
Abate by
Aug 5, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment:    Restoration Office: On or about 05JUN13; access to an electrical panel was obstructed by the accumulated containers, backpacks, and paperwork.
Recent events (1)
  • · Z (S) $0

1910.304 B03 I

Serious Gravity 1 1 instance 15 exposed
Issued
Jul 10, 2013
Abate by
Aug 5, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.304(b)(3)(i): All 125-volt, single-phase, 15- and 20-ampere receptacles installed in bathrooms or on rooftops did not have ground-fault circuit-interrupter protection for personnel:   Men's Bathroom: On or about 05JUN13, a GFCI protected receptacle outlet was not operational, failing to activate when the grounding path was interrupted.
Recent events (1)
  • · Z (S) $0

1910.305 D01

Serious Gravity 5 1 instance 5 exposed
Issued
Jul 10, 2013
Abate by
Aug 5, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.305(d)(1): Switchboards with exposed live parts. Switchboards that have any exposed live parts shall be located in permanently dry locations and shall be accessible only to qualified persons.   Break Room: On or about 05JUN13, openings in a circuit breaker panel were not covered exposing unqualified employees to inadvertent contact with live 120VAC service conductors.
Recent events (1)
  • · Z (S) $0