Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,196,991Inspections Most recent open 2026-08-24 Last loaded 2026-08-27

OSHA Inspection: VA BROOKINGS CLINIC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of VA BROOKINGS CLINIC in 555 5TH STREET, BROOKINGS, OR 97415 (NAICS 621111). OSHA activity number 339121717.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch VA Brookings Clinic for free Get an email when a new federal OSHA severe-injury report for VA Brookings Clinic is published. One employer, no account, unsubscribe in one click.
Establishment
VA BROOKINGS CLINIC
Site address
555 5TH STREET
City
BROOKINGS
State
OR
ZIP
97415
Mailing
555 5TH STREET, BROOKINGS, OR 97415
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Union (A)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
621111
Employees
12
Ownership type
Federal government (D)

2 citations on file for this inspection.

1910.305 J02 IV

Serious Gravity 1 3 instances 7 exposed
Issued
Sep 18, 2013
Abate by
Oct 15, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.305(j)(2)(iv): A receptacle installed in a wet or damp location was not suitable for the location:  a)  In the laboratory three receptacle outlets, located within 51 to 65 inches from the sink, were not equipped with groundfault circuit interrupters.
Recent events (1)
  • · Z (S) $0

1910.37 B06

Other-than-serious 1 instance 10 exposed
Issued
Sep 18, 2013
Abate by
Oct 15, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(6): Each exit sign was not illuminated to a surface value of at least five foot-candles (54 lux) by a reliable light source and be distinctive in color:   a.)  On or about June 11, 2013, and at times prior thereto, the light inside the exit sign, at the emergency exit door from the storage room, was not functional.
Recent events (1)
  • · Z (O) $0

View VA Brookings Clinic's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 339121717.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.