AMBRIDGE, PA —
OSHA Inspection: DESIGN DYNAMICS, INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of DESIGN DYNAMICS, INC. in 2920 DUSS AVENUE PO BOX 55, AMBRIDGE, PA 15003 (NAICS 323119). OSHA activity number 339123275.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- DESIGN DYNAMICS, INC.
- Site address
- 2920 DUSS AVENUE PO BOX 55
- City
- AMBRIDGE
- State
- PA
- ZIP
- 15003
- Mailing
- 2920 DUSS AVENUE PO BOX 55, AMBRIDGE, PA 15003
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 323119
- Employees
- 8
- Ownership type
- A
Citations
11 citations on file for this inspection.
1910.36 D01
- Issued
- Oct 24, 2013
- Abate by
- Nov 5, 2013
- Penalty
- Initial $1,600 · Current $0 Reduced
General-duty citation text
29 CFR 1910.36(d)(1): Employee(s) were not able to open an exit route door from the inside at all times without keys, tools, or special knowledge: (a) Facility, Rear: On or before June 17, 2013, two rear exit doors were chained in a closed position.
Recent events (2)
- — I (S) $0
- — Z (S) $1600
1910.37 A03
- Issued
- Oct 24, 2013
- Abate by
- Nov 5, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed: (a) Facility, Rear: On or before June 17, 2013, two exit doors were blocked by sand bags and other materials.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 B02
- Issued
- Oct 24, 2013
- Abate by
- Dec 12, 2013
- Penalty
- Initial $1,600 · Current $0 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: (a) Facility, Digital Printing: On or before June 17, 2013, employees were exposed to electrical shock, arcing parts, and/or fire hazards in that a metal utility box was not mounted. (b) Facility, Miller Weldmaster Cable: On or before June 17, 2013, employees were exposed to tripping hazards in that a cable was lying along the floor. (c) Facility, Office Area: On or before June 17, 2013, employees were exposed to electrical shock, arcing parts, and/or fire hazards in that a metal utility box was not mounted.
Recent events (2)
- — I (S) $0
- — Z (S) $1600
1910.305 G02 III
- Issued
- Oct 24, 2013
- Abate by
- Nov 5, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws: (a) Facility, Digital Printing: On or before June 17, 2013, employees were exposed to electrical shock, arcing parts, and/or fire hazards in that a cord was pulling away from a utility box.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 G02 I
- Issued
- Oct 24, 2013
- Abate by
- Nov 5, 2013
- Penalty
- Initial $2,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i): (a) Facility, Electrical/Compressor Area: On or before June 17, 2013, employees were exposed to electrical shock, arcing parts, and/or fire hazards in that a panel cover was not attached on a 120/208 volts AC three phase 225 amp electrical distribution panel.
Recent events (2)
- — I (S) $0
- — Z (S) $2000
1910.304 G05
- Issued
- Oct 24, 2013
- Abate by
- Nov 5, 2013
- Penalty
- Initial $1,600 · Current $0 Reduced
General-duty citation text
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective: (a) Facility, Electrical/Compressor Area: On or before June 17, 2013, employees were exposed to electrical shock, arcing parts, and/or fire hazards in that a ground wire was not connected to the grounding termination block.
Recent events (2)
- — I (S) $0
- — Z (S) $1600
1910.305 B01 III
- Issued
- Oct 24, 2013
- Abate by
- Nov 5, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(iii): Cable was not secured to the cabinet, cutout box, or meter socket enclosure: (a) Facility, Electrical/Compressor Area: On or before June 17, 2013, employees were exposed to arcing parts and/or fire hazards in that a cable was not connected to the cabinet with an approved cable connector.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 B07
- Issued
- Oct 24, 2013
- Abate by
- Nov 20, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(7): Electric equipment was not installed in a neat and workmanlike manner: (a) Facility, Miller Weld Master 112 Extreme: On or before June 17, 2013, the employer did not properly install an electrical cable in that it was powered with a listed voltage of 208 volts AC single phase and was not routed appropriately.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.305 B02 I
- Issued
- Oct 24, 2013
- Abate by
- Nov 20, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose: (a) Facility, Digital Area: On or before June 17, 2013, the employer did not provide covers for the fluorescent light fixtures exposing electrical terminations.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.305 G01 IV A
- Issued
- Oct 24, 2013
- Abate by
- Dec 12, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: (a) Facility, Ink Mixing Area: On or before June 17, 2013, the employer used a flexible cord extended down through the ceiling to power a fluorescent light fixture. (b) Facility, Office Area: On or before June 17, 2013, the employer used a flexible cord extended down through the ceiling to power office equipment. (c) Facility, Digital Area: On or before June 17, 2013, the employer used a flexible cord extended along the floor to power a printer.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.141 D02 II
- Issued
- Oct 24, 2013
- Abate by
- Dec 12, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.141(d)(2)(ii): Lavatories were not provided with hot and cold, or tepid running water: (a) Facility, Lavatories: On or before June 17, 2013, employees did not have hot or tepid water for use in the lavatories.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Design Dynamics, INC.
View Design Dynamics, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 323119)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339123275.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.