Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: CF INDUSTRIES NITROGEN, LLC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of CF INDUSTRIES NITROGEN, LLC in 39018 HWY 3089, DONALDSONVILLE, LA 70346 (NAICS 325311). OSHA activity number 339127284.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch CF Industries Nitrogen, LLC — free Get an email when a new federal OSHA severe-injury report for CF Industries Nitrogen, LLC is published. One employer, no account, unsubscribe in one click.
Site address
39018 HWY 3089
City
DONALDSONVILLE
State
LA
ZIP
70346
Mailing
39018 HWY 3089, DONALDSONVILLE, LA 70346
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
325311
Employees
391
Ownership type
A

1 citation on file for this inspection.

1910.119 J04 IV

Serious Gravity 10 10 instances 81 exposed
Issued
Dec 13, 2013
Abate by
Dec 30, 2013
Penalty
Initial $7,000 · Current $7,000
29 CFR 1910.119(j)(4)(iv):  The documentation of the inspection or test that had been performed on process equipment to maintain its mechanical integrity did not identify the date of the inspection or test, the serial number or other identifier of the equipment on which the inspection or test was performed, a description of the inspection or test, and the results of the inspection or test.  The employer does not ensure results from inspections and tests performed on process equipment are documented.    The violation occurred in the Ammonia #1 and #2 units on or about June 20, 2013 and at times prior thereto where the employer failed to ensure results from inspections and tests performed on identified safeguards were documented. Identified safeguards include but are not limited to:  a.     EFT-102 A/B and associated logic   b.     TI-46/47 and associated logic  c.     PIC-1A and associated logic  d.     EFT-3 A/B and logic  e.     EF3LL EF-102LL and associated logic and controls   f.      ETI-14 and 106DHH logic  g.     EPI-160 A/B/C and LF160HH logic   h.     EPI-181 Alarms and Trips EPT-19 A/B and EF102LL logic   i.      EPT 8 A/B and V-8A logic    This condition exposed employees to fire, explosion, and/or inhalation hazards.    Pursuant to 29 C.F.R. 1903.19, within ten (10) calendar days of the abatement date the employer must submit documentation showing it is in compliance with the standard, including describing the steps it is taking to ensure results from inspections and tests performed on process equipment are documented with the date, serial number or equipment identifier, and a description of the of the inspection or test.
Recent events (1)
  • — Z (S) $7000

View CF Industries Nitrogen, LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339127284.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.