Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,198,892Inspections Most recent open 2026-09-03 Last loaded 2026-09-07

OSHA Inspection: NOR-RAL, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of NOR-RAL, INC. in 164 HICKORY SPRINGS INDUSTRIAL DRIVE, CANTON, GA 30115 (NAICS 332710). OSHA activity number 339152134.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Nor-Ral, INC. for free Get an email when a new federal OSHA severe-injury report for Nor-Ral, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
NOR-RAL, INC.
Site address
164 HICKORY SPRINGS INDUSTRIAL DRIVE
City
CANTON
State
GA
ZIP
30115
Mailing
164 HICKORY SPRINGS INDUSTRIAL DRIVE, CANTON, GA 30115
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332710
Employees
47
Ownership type
Private (A)

10 citations on file for this inspection.

1910.37 A03

Serious Gravity 1 1 instance 2 exposed
Issued
Oct 24, 2013
Penalty
Initial $1,785 · Current $1,630 Reduced
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed:   On or about 06/25/2013 at 164 Hickory Springs Drive, Canton, GA:  In Building#3, crates blocked the access to the emergency exit. Employees working in Building #3, were exposed to a smoke and fire hazard.
Recent events (2)
  • · I (S) $1630
  • · Z (S) $1785

1910.37 B02

Serious Gravity 1 1 instance 2 exposed
Issued
Oct 24, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit":   On or about 06/25/2013 at 164 Hickory Springs Drive, Canton, GA: In Building #3, the emergency exit sign was damaged, the red illuminated faceplate was missing. Employees are exposed to a smoke and fire hazard.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.37 A04

Serious Gravity 1 1 instance 3 exposed
Issued
Oct 24, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.37(a)(4): Safeguard(s) designed to protect employees during an emergency (e.g., sprinkler systems, alarm systems, fire doors, exit lighting), were not in proper working order at all times:   On or about 06/25/2013 at 164 Hickory Springs Drive, Canton, GA: In Paint/Parts the emergency exit light did not operate. The employees working in the area were exposed to a smoke and fire hazard.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.110 F02 II

Serious Gravity 5 1 instance 2 exposed
Issued
Oct 24, 2013
Abate by
Nov 5, 2013
Penalty
Initial $2,800 · Current $2,280 Reduced
29 CFR 1910.110(f)(2)(ii): Liquefied petroleum gas container(s) stored inside were located near exits, stairways, or in areas normally used or intended for the safe exit of people:  On or about 06/25/2013 at 164 Hickory Springs Drive, Canton, GA: In Building #3, three empty liquefied petroleum gas containers used as motor fuel for the forklift were stored near the exit. Employees were exposed to an explosion hazard.
Recent events (2)
  • · I (S) $2280
  • · Z (S) $2800

1910.253 B04 III

Serious Gravity 5 1 instance 6 exposed
Issued
Oct 24, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.253(b)(4)(iii): Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one half hour.  On or about 06/25/2013 at 164 Hickory Springs Drive, Canton, GA: In the welding area in Building #3 oxygen and acetylene cylinders were stored in the same rack. The employees working in Building #3, were exposed to an explosion hazard.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.147 C04 I

Deleted Serious Gravity 5 5 instances 3 exposed
Issued
Oct 24, 2013
Abate by
Dec 12, 2013
Penalty
Initial $3,500 · Current $0 Reduced
29 CFR 1910.147(c)(4)(i): Procedures were not developed, documented, and utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section.  On or about 06/25/2013 at 164 Hickory Springs Industrial Drive, Canton, GA: The employer failed to develop written procedures for the CNC machines when cleaning, servicing, and making adjustments. Employees are exposed to struck-by hazards.
Recent events (2)
  • · I (S) $0
  • · Z (S) $3500

1910.215 A04

Serious Gravity 5 1 instance 1 exposed
Issued
Oct 24, 2013
Abate by
Nov 5, 2013
Penalty
Initial $2,380 · Current $2,080 Reduced
29 CFR 1910.215(a)(4): Grinding machinery was not used with work rest(s) to support offhand grinding work.   On or about 06/25/2013 at 164 Hickory Springs Drive, Canton, GA:  In Building #2, the tool rest was missing on the bench grinder. Employees were exposed to a struck-by hazard.
Recent events (2)
  • · I (S) $2080
  • · Z (S) $2380

1910.215 B09

Serious Gravity 5 1 instance 1 exposed
Issued
Oct 24, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.215(b)(9): Guard for abrasive wheel machine where the operator stands in front of the machine was not constructed so that the peripheral protecting member could be adjusted to the constantly decreasing diameter of the wheel.   On or about 06/25/2013 at 164 Hickory Springs Drive, Canton, GA: In Building #2, the tongue guard was not installed properly on the bench grinder. Employees working at the bench grinder were exposed to a struck by hazard.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.242 B

Serious Gravity 5 1 instance 2 exposed
Issued
Oct 24, 2013
Abate by
Nov 5, 2013
Penalty
Initial $2,380 · Current $1,530 Reduced
29 CFR 1910.242(b): Compressed air used for cleaning purposes was not reduced to less than 30 p.s.i.  On or about 06/25/2013 at 164 Hickory Springs Drive, Canton, GA: An employee using compressed air to dust off his clothing was exposed to a potential embolism.  The pistol style air gun registered the air pressure between 45 and 60 p.s.i.
Recent events (2)
  • · I (S) $1530
  • · Z (S) $2380

1910.303 G01 I A

Serious Gravity 1 1 instance 2 exposed
Issued
Oct 24, 2013
Abate by
Nov 5, 2013
Penalty
Initial $1,785 · Current $1,480 Reduced
29 CFR 1910.303(g)(1)(i)(A): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the depth of the working space in the direction of access to live parts (as measured from the live parts where they were exposed or from the enclosure front or opening where they were enclosed) was less than indicated in Table S-1 of Subpart S of Part 1910:(a).   On or about 06/25/2013 at 164 Hickory Springs Drive, Canton, GA: In Building #3, two 55-gallon barrels of resin and a crate were placed in front of the electrical panel. Sufficient space for ready and safe access to the electrical panel was not maintained. Employees were exposed to fire and smoke hazards.
Recent events (2)
  • · I (S) $1480
  • · Z (S) $1785

View Nor-Ral, INC.'s full OSHA safety record →