CHICAGO, IL —
OSHA Inspection: MRC POLYMERS, INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of MRC POLYMERS, INC. in 3535 W. 31ST STREET, CHICAGO, IL 60623 (NAICS 325211). OSHA activity number 339154270.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- MRC POLYMERS, INC.
- Site address
- 3535 W. 31ST STREET
- City
- CHICAGO
- State
- IL
- ZIP
- 60623
- Mailing
- 3535 W. 31ST STREET, CHICAGO, IL 60623
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 325211
- Employees
- 60
- Ownership type
- A
Citations
7 citations on file for this inspection.
1910.147 C04 I
- Issued
- Dec 23, 2013
- Abate by
- Feb 11, 2014
- Penalty
- Initial $3,500 · Current $1,750 Reduced
General-duty citation text
29 CFR 1910.147(c)(4)(i): Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section. a. Facility - On or about June 28, 2013, the written energy control program did not include specific step by step procedures to control and lockout all energy sources for employees who performed maintenance on such equipment but not limited to conveyors, dumpers, grinders and wash lines. Employees were thereby exposed to the hazards associated with the unexpected energization of equipment.
Recent events (2)
- — I (S) $1750
- — Z (S) $3500
1910.178 L01 I
- Issued
- Dec 23, 2013
- Abate by
- Feb 11, 2014
- Penalty
- Initial $4,900 · Current $2,450 Reduced
General-duty citation text
29 CFR 1910.178(l)(1)(i): The employer did not ensure that each powered industrial truck operator is competent to operate a powered industrial truck safely, as demonstrated by the successful completion of the training and evaluation specified in this paragraph (l): a. Entire Facility - On or about June 28, 2013, employees were required to operate powered industrial vehicles. The employees were not provided training on the safe operation of powered industrial vehicles and were thereby exposed to crushing and struck by hazards.
Recent events (2)
- — I (S) $2450
- — Z (S) $4900
1910.332 B01
- Issued
- Dec 23, 2013
- Abate by
- Feb 11, 2014
- Penalty
- Initial $4,900 · Current $2,450 Reduced
General-duty citation text
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments: a. Facility - On or about June 28, 2013, employees required to perform voltage testing on 480V motor pump drives, were not provided with training in the safety related work practices emphasized in 29 CFR 1910.331 - 1910.335. The employees were thereby exposed to hazards of electrical shock and arc flash/blasts.
Recent events (2)
- — I (S) $2450
- — Z (S) $4900
1910.333 B02 I
- Issued
- Dec 23, 2013
- Abate by
- Feb 11, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.333(b)(2)(i): The employer did not make a written copy of the procedures outlined in paragraph (b)(2) of 29 CFR 1910.333 available for inspection by employees and by the Assistant Secretary of Labor and his or her authorized representatives: a. Facility - On or about June 28, 2013, the employer did not maintain written electrical safety-related work practice procedures outlined in 29 CFR 1910.333(b)(2) for employees who are required to perform voltage testing on 480V motor pump drives.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.335 A01 I
- Issued
- Dec 23, 2013
- Abate by
- Jan 21, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not using electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed: a. Facility - On or about June 28, 2013, employees were required to perform voltage testing on 480V motor pump drives. The employees were not provided with electrical protective equipment including but not limited to fire retardant clothing, hard hat, face shield, and voltage rated gloves. The employees were thereby exposed to hazards of electrical shock and arc flash/blasts.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.335 A02 I
- Issued
- Dec 23, 2013
- Abate by
- Feb 11, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.335(a)(2)(i): When working near exposed energized conductors or circuit parts, each employee did not use insulated tools or handling equipment when the tools or handling equipment might have made contact with such conductors or parts: a. Facility - On or about June 28, 2013, employees were required to perform voltage testing on 480V motor pump drives. The employees were not provided with insulated tools and were thereby exposed to the hazards of electrical shock and arc flash/blasts.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.147 C06 II
- Issued
- Dec 23, 2013
- Abate by
- Feb 11, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(c)(6)(ii): The employer did not certify that periodic inspections of the energy control procedures had been performed: a. Facility - On or about June 28, 2013, the employer had not adequately certified periodic inspections of the established energy control procedures in place for employees who perform servicing and maintenance of equipment. Employees were thereby exposed to the hazards associated with the unexpected energization of equipment.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at MRC Polymers, INC.
View MRC Polymers, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 325211)
More inspections in IL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339154270.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.