OSHA Inspection: NATIONAL PARK SERVICE-VI BIOSPHERE RESERVE CENTER

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of NATIONAL PARK SERVICE-VI BIOSPHERE RESERVE CENTER in BIOSPHERE CENTER-LIND PT-BLDG.2, ST JOHN, VI 00831 (NAICS 712190). OSHA activity number 339162307.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch National Park Service-Vi Biosphere Reserve Center for free Get an email when a new federal OSHA severe-injury report for National Park Service-Vi Biosphere Reserve Center is published. One employer, no account, unsubscribe in one click.
Site address
BIOSPHERE CENTER-LIND PT-BLDG.2
City
ST JOHN
State
VI
ZIP
00831
Mailing
1300 CRUZ BAY CREEK, ST JOHN, VI 00830
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
712190
Employees
12
Ownership type
Federal government (D)

7 citations on file for this inspection.

1910.303 B02

Serious Gravity 5 5 instances 5 exposed
Issued
Sep 18, 2013
Abate by
Nov 5, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Installation and use. Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling:   a) On or about 06/27/13, at the Biosphere Center, St John, VI, in building #4 area, a relocatable power tap was not directly connected to a permanently installed branch circuit receptacle.   b) On or about 06/27/13, at the Biosphere Center, St John, VI, in building #3 NE corner area, two relocatable power taps were not directly connected to a permanently installed branch circuit receptacle.   c) On or about 06/27/13, at the Biosphere Center, St John, VI, in building #3 SW corner area, an uninterruptible power supply was not connected to a permanently installed branch circuit receptacle.  d) On or about 06/27/13, at the Biosphere Center, St John, VI, in building #3 SW corner area, two relocatable power taps were not directly connected to a permanently installed branch circuit receptacle.   e) On or about 06/27/13, at the Biosphere Center, St John, VI, in building #2 kitchen area, a ground-fault circuit interrupter was not installed in all 125-volt, single phase, 15-and 20-ampere receptacles installed within 6 feet or 1.8 meters of the outside edge of a sink.   PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • · Z (S) $0

1910.303 F02

Serious Gravity 1 1 instance 3 exposed
Issued
Sep 18, 2013
Abate by
Nov 5, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.303(f)(2): Services, feeders, and branch circuits. Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, shall be legibly marked to indicate its purpose, unless located and arranged so the purpose is evident:  On or about 06/27/13, at the Biosphere Center, St John, VI, in building #1, the circuit breakers or fuses in the electrical panel were not identified or labeled to show the locations of the building whose circuits they protect.  PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • · Z (S) $0

1910.303 G01

Serious Gravity 1 1 instance 2 exposed
Issued
Sep 18, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1): Space about electric equipment. Sufficient access and working space shall be provided and maintained about all electric equipment to permit ready and safe operation and maintenance of such equipment:  On or about 06/27/13, at the Biosphere Center, St john, VI, in building #4 area, an electrical service panel was not readily accessible.  PLEASE NOTE: CERTIFICATION OF ABATEMENT IS NOT REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • · Z (S) $0

1910.304 B03 I

Serious Gravity 5 2 instances 12 exposed
Issued
Sep 18, 2013
Abate by
Nov 5, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.304(b)(3)(i): All 125-volt, single-phase, 15- and 20-ampere receptacles installed in bathrooms or on rooftops shall have ground-fault circuit-interrupter protection for personnel:  a) On or about 06/27/13, at the Biosphere Center, St John, VI, in building #2 male bathroom area, electrical receptacles were not equipped with ground-fault circuit-interrupter protection.  b) On or about 06/27/13, at the Biosphere Center, St John, VI, in building #2 female bathroom area, electrical receptacles were not equipped with ground-fault circuit-interrupter protection.  PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • · Z (S) $0

1910.305 B01 II

Serious Gravity 1 1 instance 12 exposed
Issued
Sep 18, 2013
Abate by
Nov 5, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1)(ii): Unused openings in cabinets, boxes, and fittings shall be effectively closed:  On or about 06/27/13, at the Biosphere Center, St John, VI, in building #1 area, openings in the electrical panel board were not closed.  PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • · Z (S) $0

1910.305 B02 I

Serious Gravity 1 1 instance 12 exposed
Issued
Sep 18, 2013
Abate by
Nov 5, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(2)(i): All pull boxes, junction boxes, and fittings shall be provided with covers identified for the purpose. If metal covers are used, they shall be grounded. In completed installations, each outlet box shall have a cover, faceplate, or fixture canopy. Covers of outlet boxes having holes through which flexible cord pendants pass shall be provided with bushings designed for the purpose or shall have smooth, well-rounded surfaces on which the cords may bear:  On or about 06/27/13, at the Biosphere Center, St John, VI, in building #2 kitchen area, an electrical outlet box was not covered.  PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • · Z (S) $0

1910.305 G01 IV A

Serious Gravity 1 2 instances 2 exposed
Issued
Sep 18, 2013
Abate by
Nov 5, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, flexible cords and cables may not be used as a substitute for the fixed wiring of a structure:  a) On or about 06/27/13, at the Biosphere Center, St John, VI, in building #3 NW corner area, a flexible cord was used in lieu of permanent wiring.  b) On or about 06/27/13, at the Biosphere Center, St John, VI, in building #3 SW corner area, a flexible cord was used in lieu of permanent wiring.  PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • · Z (S) $0

View National Park Service-Vi Biosphere Reserve Center's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 339162307.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.