SAINT MARYS, OH —
OSHA Inspection: AAP ST. MARYS CORP.
Referral inspection · Health discipline
At a glance
On , OSHA opened a referral health inspection of AAP ST. MARYS CORP. in 1100 MCKINLEY RD., SAINT MARYS, OH 45885 (NAICS 336399). OSHA activity number 339210452.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- AAP ST. MARYS CORP.
- Site address
- 1100 MCKINLEY RD.
- City
- SAINT MARYS
- State
- OH
- ZIP
- 45885
- Mailing
- 1100 MCKINLEY ROAD, SAINT MARYS, OH 45885
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 336399
- Employees
- 518
- Ownership type
- A
Citations
1 citation on file for this inspection.
5(a)(1)
- Issued
- Jan 10, 2014
- Penalty
- Initial $7,000 · Current $0 Reduced
L130L131
General-duty citation text
OSH ACT of 1970 Section (5)(a)(1): The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to Legionella bacteria and were at risk of developing Legionnaires' disease. (a) AAP St. Marys, St. Marys, Ohio: On or about July 21, 2013 water samples were collected and later analyzed. The samples indicated significant levels of Legionella pneumophila bacteria in the east cooling tower and the leak test wheel washer. Among other methods, one feasible and acceptable abatement method to correct this hazard is to follow: Cooling Technology Institute, Legionellosis Guideline: Best Practice for Control of Legionella July 2008 and/or ASHRAE Guideline 12-2000 Minimizing the Risk of Legionellosis Associated with Building Water Systems and (1) feed a source of halogen-based disinfectant (chlorine or bromine) continuously and maintain a free residual, (2) install high efficiency nesting type drift eliminators, and (3) locate cooling towers away from building air intakes in such a manner that cooling tower drift or splash-out is not fed into the building air supply system.
Recent events (3)
- — F (S) $0
- — C (S) $7000
- — Z (S) $7000
More inspections at AAP ST. Marys Corp.
View AAP ST. Marys Corp.'s full OSHA safety record →
More inspections in this industry (NAICS 336399)
More inspections in OH
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339210452.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.