MAXWELL, TX —
OSHA Inspection: MAXWELL MANUFACTURING, INC.
Planned inspection · Health discipline
At a glance
On , OSHA opened a planned health inspection of MAXWELL MANUFACTURING, INC. in 55 2ND STREET, MAXWELL, TX 78656 (NAICS 326199). OSHA activity number 339244113.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- MAXWELL MANUFACTURING, INC.
- Site address
- 55 2ND STREET
- City
- MAXWELL
- State
- TX
- ZIP
- 78656
- Mailing
- 55 2ND STREET, MAXWELL, TX 78656
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 326199
- Employees
- 33
- Ownership type
- A
Citations
10 citations on file for this inspection.
1910.213 P03
- Issued
- Sep 13, 2013
- Abate by
- Sep 28, 2013
- Penalty
- Initial $2,800 · Current $1,680 Reduced
General-duty citation text
29 CFR 1910.213(p)(3): Disk sanding machine(s) were not provided with guard(s) or hood(s) so arranged as to enclose the revolving disk, except for that portion of the disk above the table: On or about July 29, 2013, the Enco Belt Sander Grinder in the maintenance shop was missing the nip point guards, exposing employees to the hazard of being caught in rotating parts.
Recent events (2)
- — I (S) $1680
- — Z (S) $2800
1910.215 A04
- Issued
- Sep 13, 2013
- Abate by
- Sep 28, 2013
- Penalty
- Initial $2,800 · Current $1,680 Reduced
General-duty citation text
29 CFR 1910.215(a)(4): Grinding machinery was not used with work rest(s) to support offhand grinding work: On or about July 29, 2013, the Delta, bench-mounted grinder was not equipped with a work rest, exposing employees to the hazard of being caught in rotating parts.
Recent events (2)
- — I (S) $1680
- — Z (S) $2800
1910.215 B09
- Issued
- Sep 13, 2013
- Abate by
- Sep 28, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.215(b)(9): 29 CFR 1910.215(b)(9): The distance between the abrasive wheel periphery(s) and the adjustable tongue or the end of the safety guard peripheral member at the top exceeded one fourth inch. On or about July 29, 2013, the Delta, bench-mounted grinder was not equipped with a tongue guard, exposing employees to the hazard of being caught in rotating parts.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 F02
- Issued
- Sep 13, 2013
- Abate by
- Sep 28, 2013
- Penalty
- Initial $2,100 · Current $1,260 Reduced
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: On or about July 29, 2013, each branch circuit in the breaker panel was not labeled to indicate its purpose, nor located and arranged so the purpose was evident: a: Breaker panel B, 240 volts manufactured by I-Line, located in the facility was not labeled. b: Breaker panel K, 240 volts manufactured by Siemens, located in the break room was not labeled. c: Breaker panel H1, 240 volts manufactured by Siemens, located next to the office entrance was not labeled. d: Breaker panel L, 240 volts manufactured by Siemens, located in the maintenance shop was not labeled.
Recent events (2)
- — I (S) $1260
- — Z (S) $2100
1910.303 G01
- Issued
- Sep 13, 2013
- Abate by
- Sep 28, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: On or about July 29, 2013, breaker panels were blocked and inaccessible at the facility: a: Breaker panel L, 240 volts manufactured by Siemens, located in the maintenance shop was blocked by parts and debris. b: The breaker panel, voltage and manufacturer unknown, in the maintenance storage area was blocked by a storage rack.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 B01 II
- Issued
- Sep 13, 2013
- Abate by
- Sep 28, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: a: Breaker panel B, 240 volts manufactured by I-Line, located in the facility had unused openings. b: Breaker panel K, 240 volts manufactured by Siemens, located in the break room had unused openings. c: Breaker panel H1, 240 volts manufactured by Siemens, located next to the office entrance had unused openings. d: Breaker panel L, 240 volts manufactured by Siemens, located in the maintenance shop had unused openings.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 B02 I
- Issued
- Sep 13, 2013
- Abate by
- Sep 28, 2013
- Penalty
- Initial $2,100 · Current $1,260 Reduced
General-duty citation text
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose: On or about July 29, 2013, A 110 volt junction box in the maintenance area behind the chop saw was missing its cover. Sawdust from the saw was found in and on top of the box, exposing employees to electrical and fire hazards.
Recent events (2)
- — I (S) $1260
- — Z (S) $2100
1910.305 G01 IV A
- Issued
- Sep 13, 2013
- Abate by
- Sep 28, 2013
- Penalty
- Initial $2,100 · Current $1,260 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: On or about July 29, 2013, flexible cords were used as permanent wiring, exposing employees to electrical and burn hazards. a: A wireless router in the maintenance shop was powered permanently by an extension cord. The router was kept on top of the office in the maintenance shop. b: A flexible cord was cut and used to power a receptacle box near the office in the warehouse
Recent events (2)
- — I (S) $1260
- — Z (S) $2100
1910.305 G02 II
- Issued
- Sep 13, 2013
- Abate by
- Sep 28, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(ii): Flexible cords were not used only in continuous lengths without splice or tap: On or about July 29, 2013, the flexible cord powering the Enco Sander Grinder was not used in a continuous length, exposing employees to an electrical hazard. The cord had been repaired with a splice.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G02 III
- Issued
- Sep 13, 2013
- Abate by
- Sep 28, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws: On or about July 29, 2013, the flexible cords in the facility showed signs of strain, exposing employees to an electrical hazard. a: The Miller Syncrowave 250 arc welder had exposed wiring where the flexible cord met the plug. b: The Enco Belt Sander Grinder model 163-4700 had exposed wiring where the flexible cord met the plug.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections at Maxwell Manufacturing, INC.
View Maxwell Manufacturing, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 326199)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339244113.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.