OSHA Inspection: PURE POWER TECHNOLOGIES, LLC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of PURE POWER TECHNOLOGIES, LLC in 1401 PERKINS AVENUE, WAUKESHA, WI 53186 (NAICS 331511). OSHA activity number 339245854.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Pure Power Technologies, LLC — free Get an email when a new federal OSHA severe-injury report for Pure Power Technologies, LLC is published. One employer, no account, unsubscribe in one click.
Site address
1401 PERKINS AVENUE
City
WAUKESHA
State
WI
ZIP
53186
Mailing
1401 PERKINS AVENUE, WAUKESHA, WI 53186
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
331511
Employees
200
Ownership type
A

8 citations on file for this inspection.

1910.137 B02 II

Serious Gravity 10 2 instances 1 exposed
Issued
Dec 18, 2013
Abate by
Feb 6, 2014
Penalty
Initial $7,000 · Current $5,750 Reduced
29 CFR 1910.137(b)(2)(ii): Insulating gloves were not given an air test prior to each days usage:    (a) Electricians used Salisbury rubber insulating gloves, Class 00, Type I gloves rated to 500 volts AC when working on energized circuits without performing an air test on gloves before each use. This exposed electricians to an electrical shock hazard.    (b) Electricians used Salisbury rubber insulating gloves, Class 0, Type I gloves rated to 1000 volts AC when working on energized circuits without performing an air test on gloves before each use. This exposed electricians to an electrical shock hazard.
Recent events (3)
  • — F (S) $5750
  • — C (S) $7000
  • — Z (S) $7000

1910.137 B02 VIII

Serious Gravity 10 1 instance 11 exposed
Issued
Dec 18, 2013
Abate by
Feb 6, 2014
Penalty
Initial $7,000 · Current $0 Reduced
29 CFR 1910.137(b)(2)(viii): Electrical protective equipment was not subjected to periodic electrical tests in accordance with Tables I-5 and I-6:    (a) Salisbury rubber insulating gloves, Class 00, Type I gloves rated to 500 volts AC and Salisbury rubber insulating gloves, Class 0, Type I gloves rated to 1000 volts AC were not electrically tested every six (6) months.
Recent events (3)
  • — F (S) $0
  • — C (S) $7000
  • — Z (S) $7000

1910.147 C06 I

Deleted Serious Gravity 10 1 instance 1 exposed
Issued
Dec 18, 2013
Abate by
Feb 6, 2014
Penalty
Initial $7,000 · Current $0 Reduced
29 CFR 1910.147(c)(6)(i): The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirement of this standard were being followed:  (a) An annual/periodic inspection of the energy control procedures has not been conducted for, but not limited to I3 Auto Pour and H1 Molding Mahcine to ensure that procedures and requirements of the standard are being followed and that employees who implement energy control procedures understand their application.
Recent events (3)
  • — F (S) $0
  • — C (S) $7000
  • — Z (S) $7000

1910.332 B01

Serious Gravity 10 2 instances 5 exposed
Issued
Dec 18, 2013
Abate by
Feb 6, 2014
Penalty
Initial $7,000 · Current $5,750 Reduced
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments:     Employee(s) worked on electrical equipment without taking special precautions, to reduce exposure to electrical hazards. Employees who perform electrical work and testing on energized electrical equipment and systems were not effectively trained in implementing electrical Safety-Related Work Practices, such as determining flash hazard boundary, determining arc flash and shock hazard associated with the high current 480V circuit breaker equipment in "Substation 5" a switch gear room containing switch gear cubicles, and establishing a protective value for required arc rated protective clothing to be worn.     (a) On or about June 25, 2013, employee(s) performing resetting of circuit breakers on "Substation 5" a switch gear room containing switch gear cubicles, were not trained to assess the arc flash and shock hazard level of the electrical equipment being worked on.      (b) On or about June 25, 2013 employee(s) were not instructed on the inspection methods for rubber insulating gloves. Employees were not familiar with the air test requirement for rubber insulating gloves prior to use and the six month requirement for electrical testing of all rubber insulating gloves.
Recent events (3)
  • — F (S) $5750
  • — C (S) $7000
  • — Z (S) $7000

1910.333 A02

Serious Gravity 10 1 instance 2 exposed
Issued
Dec 18, 2013
Abate by
Feb 6, 2014
Penalty
Initial $7,000 · Current $5,750 Reduced
29 CFR 1910.333(a)(2): Safety-related work practices shall be employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts, when work is performed near or on equipment or circuits which are or may be energized. The specific safety-related work practices shall be consistent with the nature and extent of the associated electrical hazards:    (a) Employees did not employ electrical safety-related work practices while attempting to reset the main circuit breaker and circuit breakers fed by the main circuit breaker in "Substation 5" a switch gear room containing switch gear cubicles.
Recent events (3)
  • — F (S) $5750
  • — C (S) $7000
  • — Z (S) $7000

1910.334 B02

Serious Gravity 10 1 instance 2 exposed
Issued
Dec 18, 2013
Abate by
Feb 6, 2014
Penalty
Initial $7,000 · Current $5,750 Reduced
29 CFR 1910.334(b)(2): Reclosing circuits after protective device operation. After a circuit is deenergized by a circuit protective device, the circuit may not be manually reenergized until it has been determined that the equipment and circuit can be safely energized.     (a) On or about June 25, 2013,  an employee(s) attempted to manually reenergize a 480 volt AC circuit "Substation 5 circuit breaker 5T5CB3 - 800 Amp Rating " that had been deenergized by a circuit protective device. The circuit and equipment had not been evaluated to ensure that the circuit could be reenergized safely, exposing employees to arc flash and electrical shock hazards.
Recent events (3)
  • — F (S) $5750
  • — C (S) $7000
  • — Z (S) $7000

1910.335 A02 II

Deleted Serious Gravity 10 1 instance 2 exposed
Issued
Dec 18, 2013
Abate by
Feb 6, 2014
Penalty
Initial $7,000 · Current $0 Reduced
29 CFR 1910.335(a)(2)(ii): Protective shields, protective barriers, or insulating materials shall be used to protect each employee from shock, burns, or other electrically related injuries while that employee is working near exposed energized parts which might be accidentally contacted or where dangerous electric heating or arcing might occur. When normally enclosed live parts are exposed for maintenance or repair, they shall be guarded to protect unqualified persons from contact with the live parts.  (a) On or about June 25, 2013, the employeer had no insulating protective equipment in use at "Substation 5", such as barriers or shielding in place to protect employees from arcing faults, and covers that were normally in place had been removed to operate the circuit breakers.
Recent events (3)
  • — F (S) $0
  • — C (S) $7000
  • — Z (S) $7000

1910.335 A01 I

Repeat Gravity 10 1 instance 2 exposed
Issued
Dec 18, 2013
Abate by
Feb 6, 2014
Penalty
Initial $70,000 · Current $70,000
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not using electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed:    (a) On or about June 25, 2013, employee(s) working on energized 480 volt AC circuit breakers within "Substation 5" did not use personal protective equipment, such as, but not limited to arc rated apparel, faceshield, and voltage-rated gloves to protect against arc flash hazards and electrical shock hazards.
Recent events (3)
  • — F (R) $70000
  • — C (W) $70000
  • — Z (W) $70000

View Pure Power Technologies, LLC's full OSHA safety record →