OSHA Inspection: MAGENS POINT RESORT

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of MAGENS POINT RESORT in 6200 MAGENS BAY ROAD, ST THOMAS, VI 00802 (NAICS 721110). OSHA activity number 339272635.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Magens Point Resort for free Get an email when a new federal OSHA severe-injury report for Magens Point Resort is published. One employer, no account, unsubscribe in one click.
Establishment
MAGENS POINT RESORT
Site address
6200 MAGENS BAY ROAD
City
ST THOMAS
State
VI
ZIP
00802
Mailing
6200 MAGENS BAY ROAD, SUITE 307, ST THOMAS, VI 00802
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
721110
Employees
19
Ownership type
Private (A)

8 citations on file for this inspection.

1910.212 A02

Serious Gravity 5 1 instance 2 exposed
Issued
Sep 27, 2013
Abate by
Oct 3, 2013
Penalty
Initial $1,800 · Current $540 Reduced
29 CFR 1910.212(a)(2): Guard(s) on machine(s) were not affixed to the machine or secured elsewhere when attachment to the machine was not possible:    a:    On or about 08/01/2013, Magens Point Resort, 6200 Magens Bay Road, St. Thomas, VI - Waste Water Treatment Plant area:  Employees were working with a waste water pump without a belt and pulley cover guard, which exposed employees to caught by hazards while equipment is in operation.       Note: Certification of abatement is not required for this citation item since it was submitted prior to citation issuance. Please disregard the abatement date.
Recent events (2)
  • · I (S) $540
  • · Z (S) $1800

1910.303 G01 I

Serious Gravity 5 1 instance 3 exposed
Issued
Sep 27, 2013
Abate by
Oct 3, 2013
Penalty
Initial $1,800 · Current $540 Reduced
29 CFR 1910.303(g)(1)(i): Work space was less than 30 inches wide in front of electric equipment operating at 600 volts, nominal, or less:    a:     On or about 08/01/2013, Magens Point Resort,  6200 Megans Bay Road, St. Thomas, VI- electrical panel/ laundry area:  Access to an electrical panel was blocked with laundry materials.     Note:  Certification of abatement is not required for this citation item since it was submitted prior to citation issuance. Please disregard the abatement date.
Recent events (2)
  • · I (S) $540
  • · Z (S) $1800

1910.303 G02 I

Serious Gravity 5 3 instances 3 exposed
Issued
Sep 27, 2013
Abate by
Oct 3, 2013
Penalty
Initial $1,800 · Current $900 Reduced
29 CFR 1910.303(g)(2)(i):  Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by approved cabinets or other forms of approved enclosures, or other means listed under this provision:    Instance #1     On or about 08/01/2013, Magens Point Resort,  6200 Megans Bay Road, St. Thomas, VI- Waste Water Treatment Plant area - electrical panel area:  Employees were using an electrical panel where unused openings were not effectively closed, therefore, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact.      Instance #2     On or about 08/01/2013, Magens Point Resort, 6200 Megans Bay Road, St. Thomas, VI  electrical panel/ laundry area:  Employees were using an electrical panel where unused openings were not effectively closed, therefore, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact. Electrical panel have missing breakers exposing live bus bars. Empty breaker slots were not covered, thus, exposing employees to electrical hazards.    Instance #3     On or about 08/01/2013, Magens Point Resort,  6200 Megans Bay Road, St. Thomas, VI- electrical panel area/ lower level pump room area:   Employees were using an electrical panel where unused openings were not effectively closed, therefore, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact.    Note for instances #1, #2 and #3:  Certification of abatement is not required for this citation item since it was submitted prior to citation issuance. Please disregard the abatement date.
Recent events (2)
  • · I (S) $900
  • · Z (S) $1800

1910.305 A04 II

Serious Gravity 5 1 instance 2 exposed
Issued
Sep 27, 2013
Abate by
Oct 3, 2013
Penalty
Initial $1,800 · Current $540 Reduced
29 CFR 1910.305(a)(4)(ii): Conductors installed as open wiring on insulators were not rigidly supported on noncombustible, nonabsorbent insulating materials     Instance #1     On or about 08/01/2013, Magens Point Resort,  6200 Megans Bay Road, St. Thomas, VI- Waste Water Treatment Plant area - electrical panel area:  Employees were exposed to electrical hazards while using an electrical panel in which its electrical conductors wires were not rigidly supported on noncombustible conduit.       Instance #2     On or about 08/01/2013, Magens Point Resort, 6200 Megans Bay Road, St. Thomas, VI- electrical panel area/ lower level pump room area:  Employees were exposed to electrical hazards while using an electrical panel in which its electrical conductors wires were not rigidly supported on noncombustible conduit.     Note #1 & #2:  Certification of abatement is not required for this citation item since it was submitted prior to citation issuance. Please disregard the abatement date.
Recent events (2)
  • · I (S) $540
  • · Z (S) $1800

1910.305 B01

Serious Gravity 5 1 instance 2 exposed
Issued
Sep 27, 2013
Abate by
Oct 3, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1):  Conductors entering boxes, cabinets, or fittings were not protected from abrasions:   a.     On or about 08/01/2013, Magens Point Resort, 6200 Magens Bay Road, St. Thomas, VI- electrical panel area/ lower level pump room area:  Employees were exposed to electrical hazards while using an electrical panel in which electrical conductors wires were exposed to damage and abrasions when opening and closing the panel door.   Note:  Certification of abatement is not required for this citation item since it was submitted prior to citation issuance. Please disregard the abatement date.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.305 B02 I

Serious Gravity 5 2 instances 3 exposed
Issued
Sep 27, 2013
Abate by
Dec 16, 2013
Penalty
Initial $1,800 · Current $900 Reduced
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose:    Instance #1      On or about 08/01/2013, Magens Point Resort, 6200 Magens Bay Road, St. Thomas, VI- electrical panel area/ lower level pump room area:   Employees have been using electrical pump that its electrical junction box lacked a face plate cover.    Instance #2     On or about 08/01/2013, Magens Point Resort,  6200 Megans Bay Road, St. Thomas, VI- Waste Water Treatment Plant area  electrical outlets area:  Employees have been using electrical tools connected to a metal outlet box. The MT outlet box lacked a face plate cover.    NOTE:   Certification and documentation of abatement must be submitted for this citation item as required by 29 CFR 1903.19(c) and (d), respectively
Recent events (2)
  • · I (S) $900
  • · Z (S) $1800

1910.305 G01 IV A

Serious Gravity 5 1 instance 2 exposed
Issued
Sep 27, 2013
Abate by
Dec 16, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and cables were used as a substitute for the fixed wiring of a structure    a.  On or about 08/01/2013, Magens Point Resort, 6200 Magens Bay Road, St. Thomas, VI - Waste Water Treatment Plant area: Employees were using an a flexible cord (extention cord) attached to jury rigged female cord connector used to power tools.    NOTE:  Documentation of abatement must be submitted for this citation item as required by 29 CFR 1903.19(d).
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.303 F02

Other-than-serious 1 instance 3 exposed
Issued
Sep 27, 2013
Abate by
Oct 3, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.303(f)(2):   Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:  a.    On or about 08/01/2013, Magens Point Resort, 6200 Magens Bay Road, St. Thomas, VI-electrical panel/ laundry area: Employees were using an electrical panel with missing labels.   NOTE:  Certification of abatement is not required for this citation item since it was submitted prior to citation issuance. Please disregard the abatement date.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

View Magens Point Resort's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 339272635.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.