Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: QUALITY PACKAGING SPECIALISTS INTERNATIONAL

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of QUALITY PACKAGING SPECIALISTS INTERNATIONAL in 5 COOPER STREET, BURLINGTON, NJ 08016 (NAICS 561910). OSHA activity number 339273088.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Quality Packaging Specialists International — free Get an email when a new federal OSHA severe-injury report for Quality Packaging Specialists International is published. One employer, no account, unsubscribe in one click.
Site address
5 COOPER STREET
City
BURLINGTON
State
NJ
ZIP
08016
Mailing
5 COOPER STREET, BURLINGTON, NJ 08016
Inspection type
Complaint (B)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
561910
Employees
200
Ownership type
A

5 citations on file for this inspection.

1910.178 G02

Serious Gravity 1 1 instance 2 exposed
Issued
Nov 26, 2013
Abate by
Dec 23, 2013
Penalty
Initial $3,000 · Current $2,250 Reduced
29 CFR 1910.178(g)(2):  Battery charging apparatus for industrial trucks located in battery changing and charging installation was not protected from damage by trucks:  a)  QPSI warehouse area, forklift charging area:  Facilities were not provided to protect battery charging apparatuses from damage.  The charging cables on a battery charger had damaged cords with exposed copper conduit, observed on or about August 1, 2013.
Recent events (2)
  • — I (S) $2250
  • — Z (S) $3000

1910.303 B02

Serious Gravity 1 1 instance 39 exposed
Issued
Nov 26, 2013
Abate by
Dec 23, 2013
Penalty
Initial $3,000 · Current $2,250 Reduced
29 CFR 1910.303(b)(2):   Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  a)  QPSI, Production area:  Employer used multiple 4x4 metallic knockout boxes in room #1, areas 6, 7, 8 and room #2, which are not approved to be used as pendant drop outlets to connect sections of machinery including but not limited to; ISHIDA machine, BILT RITE conveyor, KBMD machine, label conveyor, etc., located throughout the facility,  observed on or about 08/01/2013.
Recent events (2)
  • — I (S) $2250
  • — Z (S) $3000

1910.305 B01 I

Serious Gravity 1 3 instances 39 exposed
Issued
Nov 26, 2013
Abate by
Dec 23, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1)(i): Openings through which conductors entered cutout boxes, cabinets, or fittings were not effectively closed:   a)  QPSI, production area Room # 1:  Machine Model #402 located inside room#1 had missing knockouts exposing machine wires, observed on or about 08/01/2013.   b)  QPSI, Production area Room #2:  Conveyor #44 had missing knockouts in various areas exposing the machine wires, observed on or about 08/01/2013.   c)  QPSI, Maintenance area: An outlet powering an overhead lamp had missing knockout exposing the wires inside the box, observed on or about 08/01/2013.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G01 IV A

Serious Gravity 1 1 instance 39 exposed
Issued
Nov 26, 2013
Abate by
Dec 23, 2013
Penalty
Initial $3,000 · Current $2,250 Reduced
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:   a)  QPSI, Warehouse, loading area near door #10:  An extension cord was used for prolonged periods of time to power a wrapping machine located near the dock door #10  in the loading/unloading area of the warehouse, observed on or about 08/01/2013.
Recent events (2)
  • — I (S) $2250
  • — Z (S) $3000

1910.305 G02 III

Serious Gravity 1 1 instance 20 exposed
Issued
Nov 26, 2013
Abate by
Dec 23, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(iii):   Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws:  a)  QPSI, Production area, Room#1:  The Conveyor machine had a flexible cable with damaged strain relief, observed on or about 08/01/2013.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View Quality Packaging Specialists International's full OSHA safety record →