Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,196,249Inspections Most recent open 2026-08-20 Last loaded 2026-08-24

OSHA Inspection: VETERANS ADMINISTRATION

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of VETERANS ADMINISTRATION in 5580 MILL STREET, STE 600, RENO, NV 89502 (NAICS 923140). OSHA activity number 339280646.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Veterans Administration for free Get an email when a new federal OSHA severe-injury report for Veterans Administration is published. One employer, no account, unsubscribe in one click.
Site address
5580 MILL STREET, STE 600
City
RENO
State
NV
ZIP
89502
Mailing
5580 MILL STREET, STE 600, RENO, NV 89502
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
923140
Employees
8
Ownership type
Federal government (D)

6 citations on file for this inspection.

1910.37 B05

Serious Gravity 1 1 instance 8 exposed
Issued
Aug 27, 2013
Abate by
Sep 20, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(5): Each doorway or passage along an exit access that could be mistaken for an exit was not marked "Not an Exit" or similar designation, or be identified by a sign indicating its actual use (e.g. closet):  (a) On or about July 29, 2013, in the file room, the door leading to the server room was not marked "NOT AN EXIT"
Recent events (1)
  • · Z (S) $0

1910.303 B02

Serious Gravity 5 1 instance 8 exposed
Issued
Aug 27, 2013
Abate by
Sep 20, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  (a) On or about July 29, 2013, in the employee staff lounge, a relocatable power tap was used to plug-in first coffee maker and other high powered/amperage appliances.
Recent events (1)
  • · Z (S) $0

1910.303 F02

Serious Gravity 5 4 instances 8 exposed
Issued
Aug 27, 2013
Abate by
Sep 20, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident.  (a) On or about July 9, 2013, electrical power panel was not labeled in the file room.
Recent events (1)
  • · Z (S) $0

1910.304 F01 IV

Serious Gravity 1 1 instance 8 exposed
Issued
Aug 27, 2013
Abate by
Sep 20, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.304(f)(1)(iv): Overcurrent devices for circuits rated 600 volts, nominal, or less, were not readily accessible to each employee or authorized building management personnel.  (a) On or about July 29, 2013, in the file room, the electrical power panel was obstructed by a metal rack.
Recent events (1)
  • · Z (S) $0

1910.305 G01 IV A

Serious Gravity 5 1 instance 1 exposed
Issued
Aug 27, 2013
Abate by
Sep 20, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A):   Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure.  (a) On or about July 29, 2013, a brown 2 wire extension cord was used to extend power to a acharger and lights for more than 90 days.
Recent events (1)
  • · Z (S) $0

1910.305 G02 III

Serious Gravity 5 1 instance 1 exposed
Issued
Aug 27, 2013
Abate by
Sep 20, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws.  (a) On or about July 29, 2013, the power cord of the relocatable power tap used to plug-in the first coffee maker did not have strain relief.