RENO, NV —
OSHA Inspection: USDA, ANIMAL AND PLANT HEALTH INSPECTION SERVICE/ PLANT PROTECTION QUARANTINE
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of USDA, ANIMAL AND PLANT HEALTH INSPECTION SERVICE/ PLANT PROTECTION QUARANTINE in 8775 TECHNOLOGY WAY, RENO, NV 89521 (NAICS 813312). OSHA activity number 339298713.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Site address
- 8775 TECHNOLOGY WAY
- City
- RENO
- State
- NV
- ZIP
- 89521
- Mailing
- 8775 TECHNOLOGY WAY, RENO, NV 89521
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 813312
- Employees
- 100
- Ownership type
- D
Citations
9 citations on file for this inspection.
1910.36 G02
- Issued
- Sep 23, 2013
- Abate by
- Oct 17, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.36(g)(2): Exit access(es) were not at least 28 inches (71.1 cm) wide at all points. (a) On or about August 5, 2013, in the staff and wildlife biologists' office spaces, exit/egress were 19 and 25 inches obstructed by boxes, desk, file cabinet and furniture.
Recent events (1)
- — Z (S) $0
1910.157 C01
- Issued
- Sep 23, 2013
- Abate by
- Oct 17, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries. (a) On or about August 5, 2013, in the Archive and Break room, portable fire extinguishers were free standing on tables and floor.
Recent events (1)
- — Z (S) $0
1910.253 B04 III
- Issued
- Sep 23, 2013
- Abate by
- Oct 17, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.253(b)(4)(iii): Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one-half hour. (a) On or about August 5, 2013, in the warehouse, oxygen and acetylene gas cylinders were stored together.
Recent events (1)
- — Z (S) $0
1910.303 B02
- Issued
- Sep 23, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling. (a) On or about August 5, 2013, in the PPQ Lab, two re-locatable power taps were daisy chained together.
Recent events (1)
- — Z (S) $0
1910.303 F02
- Issued
- Sep 23, 2013
- Abate by
- Oct 17, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident. (a) On or about August 5, 2013, in the electrical room, the P2 power panel circuit breakers were not labled.
Recent events (1)
- — Z (S) $0
1910.305 G01 IV A
- Issued
- Sep 23, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure. (a) On or about August 5, 2013, in the PPQ area, a white extension cord was used to extend power to the Holmes oscillating pedestal fan and a surge protector for more than 90 days.
Recent events (1)
- — Z (S) $0
1910.1200 E01 I
- Issued
- Sep 23, 2013
- Abate by
- Oct 17, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.1200(e)(1)(i): The employer did not comply a list of the hazardous chemicals known to be present using a product identifier that was referenced on the appropriate safety data sheet. (a) On or about August 5, 2013, in the mini shop area, the employer did not have a complete inventory sheet for all the chemicals present in the work place such as great value bleach, staticide spray nine, grease lightning, etc,.
Recent events (1)
- — Z (S) $0
1910.1200 G01
- Issued
- Sep 23, 2013
- Abate by
- Oct 17, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.1200(g)(1): The employer did not have a material safety data sheet for each hazardous chemical in use: (a) On or about 3/28/13, in the mini shop area, material safety data sheets were not available for chemicals present in the workplace such as great value bleach, staticide spray nine, grease lightning, etc.,.
Recent events (1)
- — Z (S) $0
1910.304 F01 IV
- Issued
- Sep 23, 2013
- Abate by
- Oct 17, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(f)(1)(iv): Overcurrent devices for circuits rated 600 volts, nominal, or less, were not readily accessible to each employee or authorized building management personnel. (a) On or about August 5, 2013, the power panels in the electrical room area were obstructed by chair, plant materials, boxes, etc.,.
Recent events (1)
- — Z (O) $0
More inspections at Usda, Animal and Plant Health Inspection Service/ Plant Protection Quarantine
More inspections in this industry (NAICS 813312)
More inspections in NV
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339298713.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.