1,224,460Inspections Most recent open 2026-07-13 Last loaded 2026-07-16
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Inspection: STRONG FORGE AND FABRICATION LLC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of STRONG FORGE AND FABRICATION LLC in 20 LIBERTY STREET, BATAVIA, NY 14021 (NAICS 332710). OSHA activity number 339320442.

Watch Strong Forge AND Fabrication LLC — free Get an email when a new federal OSHA severe-injury report for Strong Forge AND Fabrication LLC is published. One employer, no account, unsubscribe in one click.
Site address
20 LIBERTY STREET
City
BATAVIA
State
NY
ZIP
14021
Mailing
20 LIBERTY STREET, BATAVIA, NY 14021
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332710
Employees
42
Ownership type
A

5 citations on file for this inspection.

1910.147 C04 I

Serious Gravity 5 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $2800.00 · Current $1800.00 Reduced
29 CFR 1910.147(c)(4)(i): Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section:     a) On or about 8/23/13 in the Forge area; written procedures titled Setting Up Hammers, did not include instructions for identifying the energy sources, shutting down and applying lockout/tagout devices to the energy isolation devices and testing prior to beginning service and maintenance work such as but not limited to die changing.        b) On or about 8/23/13 in the CNC area; employees are involved in setting up the tracer lathe, with two energy sources ( air and electric ), without the use of a written procedure for locking out this equipment.              Abatement Certification Required
Recent events (2)
  • — I (S) $1800
  • — Z (S) $2800

1910.147 C07 I A

Other-than-serious 1 instance 6 exposed
Issued
Penalty
Initial $2800.00 · Current $0.00 Reduced
29 CFR 1910.147(c)(7)(i)(A): Authorized employee(s) did not receive training in the methods and means necessary for energy isolation:    a) On or about 8/23/13 throughout the shop area; employer's  Training Verification Authorized Employee Lockout/Tagout Program, conducted March 2013, did not include instructions for applying lockout/tagout devices to the energy isolation devices prior to beginning service and maintenance work such as but not limited to, die changing on Forge presses, tracer lathe set up.      No Abatement Certification Required
Recent events (2)
  • — I (O) $0
  • — Z (S) $2800

1910.151 C

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $2800.00 · Current $1800.00 Reduced
29 CFR 1910.151(c): Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use:     a) On or about 8/23/13 in the Welding area; employees are being exposed to contact with a corrosive liquid, without the availability of a suitable facility for quick drenching of the eyes in the immediate area, while adding Excel to the parts washer.         Abatement Certification Required
Recent events (2)
  • — I (S) $1800
  • — Z (S) $2800

1910.218 F01 I

Serious Gravity 5 2 instances 5 exposed
Issued
Penalty
Initial $2800.00 · Current $1800.00 Reduced
29 CFR 1910.218(f)(1)(i): The power to mechanical forging press(es) was not locked out when the die(s) were being changed on the press(es):     a) On or about 8/23/13 in the Forge area; the local control circuits are shut off and the air is turn off when dies are being changed on the on the 2500# board forging presses without locks being applied to these energy isolation devices.          b) On or about 8/19/13 in the Forge area; the electrical disconnect in the breaker (motor control) room is shut off and the door to this room locked when the dies are being changed on the 2,000# board forging hammer.       No Abatement Certification Required
Recent events (2)
  • — I (S) $1800
  • — Z (S) $2800

1910.304 F01 IV

Other-than-serious 1 instance 5 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.304(f)(1)(iv): Overcurrent devices for circuits rated 600 volts, nominal, or less, were not readily accessible to each employee or authorized building management personnel:   a) On or about 8/19/13 in the Forge area; during servicing of the Forge presses, a lock is attached to a latch on the side of the door to the motor control room, which contains the electrical panels for the five lathes and five trim shears in this work area, effectively preventing access to the circuit breakers for the equipment located in the Forge area exposing employees to potential for caught between hazards.     No Abatement Certification
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View STRONG FORGE AND FABRICATION LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339320442.