NEWHALEM, WA —
OSHA Inspection: NATIONAL PARK SERVICE NORTH CASCADES, NEWHALEM VISITOR'S CENTER
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of NATIONAL PARK SERVICE NORTH CASCADES, NEWHALEM VISITOR'S CENTER in STATE ROUTE 20, NEWHALEM, WA 98283 (NAICS 712190). OSHA activity number 339341059.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Site address
- STATE ROUTE 20
- City
- NEWHALEM
- State
- WA
- ZIP
- 98283
- Mailing
- 810 STATE ROUTE 20, SEDRO WOOLLEY, WA 98284
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 712190
- Employees
- 15
- Ownership type
- D
Citations
14 citations on file for this inspection.
1910.36 D01
- Issued
- Sep 24, 2013
- Abate by
- Nov 16, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.36(d)(1): Employee(s) were not able to open an exit route door from the inside at all times without keys, tools, or special knowledge: a) Newhalem VC Tool Shed: The door handle to the exit door was broken, exposing employees to delayed egress hazards.
Recent events (1)
- — Z (S) $0
1910.305 J02 V
- Issued
- Sep 24, 2013
- Abate by
- Nov 16, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(j)(2)(v): A receptacle installed outdoors in a location protected from the weather or in other damp locations did not have an enclosure for the receptacle that was weatherproof when the receptacle was covered (attachment plug cap not inserted and receptacle covers closed): a) Newhalem Campground, Bathroom# 1068; Outdoor outlets did not have a weather proof cover, exposing employees to possible electrical shock hazards.
Recent events (1)
- — Z (S) $0
1910.147 C04
- Issued
- Sep 24, 2013
- Abate by
- Nov 16, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(c)(4): Procedures were not developed, documented, and utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section: a) Goodell Campground Pumphouse; Lockout tagout procedures were not developed and written for the water treatment pump station. The National Park Service was previously cited for a violation of this standard which was contained in OSHA inspection no. 309098275 citation 1, item 2a, issued on September 22, 2010 with respect to a workplace at Stehekin, Washington. The National Park Service was previously cited for a violation of this standard which was contained in OSHA inspection no. 309096139 citation 1, item 1a, issued on September 9, 2009 with respect to a workplace at Newhalem, Washington. The National Park Service was previously cited for a violation of this standard which was contained in OSHA inspection no. 309096162 citation 2, item 3a, issued on September 9, 2009 with respect to a workplace at Marblemount, Washington.
Recent events (1)
- — Z (R) $0
1910.303 B01
- Issued
- Sep 24, 2013
- Abate by
- Nov 16, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(1): Electrical equipment was not free from recognized hazards that were likely to cause death or serious physical harm to employees: a) A Loop Shelter with Kitchen; A florescent light fixture was filled with water, exposing employees to possible electrical shock hazards. The National Park Service was previously cited for a violation of this standard which was contained in OSHA inspection no. 901802 citation 1, item 6, issued on May 30, 2013 with respect to a workplace at Death Valley, California. The National Park Service was previously cited for a violation of this standard which was contained in OSHA inspection no. 559578 citation 1, item 2, issued on September 4, 2012 with respect to a workplace at Denali National Park, Alaska.
Recent events (1)
- — Z (R) $0
1910.37 A03
- Issued
- Sep 24, 2013
- Abate by
- Nov 16, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed: a) Newhalem VC Tool Shed: An exit door was blocked with Mortar Mix, exposing employees to possible delayed egress hazards.
Recent events (1)
- — Z (O) $0
1910.37 B02
- Issued
- Sep 24, 2013
- Abate by
- Nov 16, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit": a) Newhalem VC Tool Shed: The two exit doors did not have exit signs, exposing employees to possible delayed egress hazards.
Recent events (1)
- — Z (O) $0
1910.157 C01
- Issued
- Sep 24, 2013
- Abate by
- Nov 16, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries: a) Goodell Campground, building 10611, Pumphouse: The Badger fire extinguisher was not mounted, exposing employees to struck by hazards.
Recent events (1)
- — Z (O) $0
1910.157 E02
- Issued
- Sep 24, 2013
- Abate by
- Nov 16, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(e)(2): Portable fire extinguishers were not visually inspected at least monthly: a) Newhalem VC Tool Shed: The Ansul Sentry fire extinguisher had not undergone a monthly maintenance check. b) Goodell Campground, Building 10611, Pumphouse; The Badger fire extinguisher had not undergone a monthly maintenance check. c) Newhalem Campground A Loop Shelter with kitchen: The Kiddie fire extinguisher had not undergone a monthly maintenance check. d) Newhalem Campground Bathroom #1068; The fire extinguisher in the janitorial closet had not undergone a monthly maintenance check. e) Newhalem Amphitheater: The fire extinguisher had not undergone a monthly maintenance check. f) Newhalem Campground #1071 Bathroom; The Badger fire extinguisher had not undergone a monthly maintenance check. g) Newhalem Campground #1070; The Badger fire extinguisher had not undergone a monthly maintenance check.
Recent events (1)
- — Z (O) $0
1910.157 E03
- Issued
- Sep 24, 2013
- Abate by
- Nov 16, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(e)(3): Portable fire extinguishers were not subjected to an annual maintenance check: a) Newhalem VC Tool Shed: The Ansul Sentry fire extinguisher had not undergone an annual maintenance check since March 2012. b) Goodell Campground, Building 10611, Pumphouse: The Badger fire extinguisher had not undergone an annual maintenance check since March 2012. c) Newhalem Campground A Loop Shelter with kitchen: The Kiddie fire extinguisher had not undergone an annual maintenance check since March 2012. d) Newhalem Campground Bathroom #1068; The fire extinguisher in the janitorial closet had not undergone an annual maintenance check since March 2012. e) Newhalem Amphitheater: The fire extinguisher had not undergone an annual maintenance check since March 2012. f) Newhalem Campground #1071 Bathroom; The Badger fire extinguisher had not undergone an annual maintenance check since March 2012. g) Newhalem Campground #1070; The Badger fire extinguisher had not undergone an annual maintenance check since March 2012.
Recent events (1)
- — Z (O) $0
1910.176 B
- Issued
- Sep 24, 2013
- Abate by
- Nov 16, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.176(b): Storage of material created a hazard: a) Newhalem VC Tool Shed: Shovels were stores haphazardly in a metal storage cabinet, when the door was opened, employees were exposed to struck by hazards, (equipment falling out of storage cabinet and on to an employee).
Recent events (1)
- — Z (O) $0
1910.303 B02
- Issued
- Sep 24, 2013
- Abate by
- Nov 16, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a) Newhalem Amphitheater: A relocatable power tap was plugged into an extension cord. The UL listing states that relocatable power taps are designed to be plugged into an outlet, and not daisy chained and plugged into other relocatable power taps or extension cords. This exposes employees to possible electrical fire hazards.
Recent events (1)
- — Z (O) $0
1910.303 G02 II
- Issued
- Sep 24, 2013
- Abate by
- Nov 16, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(2)(ii): In locations where electric equipment was likely to be exposed to physical damage, enclosures or guards were not so arranged and of such strength as to prevent such damage: a) Newhalem VC Tool Shed: Two light bulbs located on the ceiling were not guarded and tall metal and fiberglass ladders were stored adjacent to them, exposing employees to potential broken glass. b) Newhalem Amphitheater: East side wood storage closet: An unguarded light bulb was located less than 8 feet from the floor. A shovel was stored in the closet as well. This exposes employees to potential broken glass.
Recent events (1)
- — Z (O) $0
1910.305 G01 I
- Issued
- Sep 24, 2013
- Abate by
- Nov 16, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(i): Flexible cords and cables were not approved or conditions of use and location: a) Newhalem Amphitheater; Extension cords used to power audio visual equipment are used outside in the rain, and the extension cords are not rated for wet and damp locations, exposing employees to possible electrical shock hazards.
Recent events (1)
- — Z (O) $0
1960.25 C
- Issued
- Sep 24, 2013
- Abate by
- Nov 16, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1960.25(c): 29 CFR 1960.25(c): The Agency did not inspect annually, all areas in each workplace, including office operations: a) Newhalem Campground, Newhalem VC Tool Shed, Newhalem Amphitheater, and the Goodell Campground did not undergo an annual health and safety walkthrough and evaluation to correct hazards found in the workplace.
Recent events (1)
- — Z (O) $0
More inspections at National Park Service North Cascades, Newhalem Visitor'S Center
View National Park Service North Cascades, Newhalem Visitor'S Center's full OSHA safety record →
More inspections in this industry (NAICS 712190)
More inspections in WA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339341059.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.