OSHA Inspection: IEC HOLDEN CORPORATION

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of IEC HOLDEN CORPORATION in 51 DISTRIBUTION WAY SUITE102, PLATTSBURGH, NY 12901 (NAICS 335312). OSHA activity number 339366205.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch IEC Holden Corporation — free Get an email when a new federal OSHA severe-injury report for IEC Holden Corporation is published. One employer, no account, unsubscribe in one click.
Site address
51 DISTRIBUTION WAY SUITE102
City
PLATTSBURGH
State
NY
ZIP
12901
Mailing
51 DISTRIBUTION WAY SUITE102, PLATTSBURGH, NY 12901
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
335312
Employees
33
Ownership type
A

12 citations on file for this inspection.

5(a)(1)

Serious Gravity 10 2 instances 33 exposed
Issued
Nov 26, 2013
Abate by
Dec 3, 2013
Penalty
Initial $6,300 · Current $3,500 Reduced
OSH ACT of 1970 Section (5)(a)(1): Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which was free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to fire and explosion hazards due to flammable volatile material heated in an industrial oven that was not designed for use with flammables :    a)  VPI Area - On or about August 28, 2013, an industrial walk in oven (Oven #1, JPW Design & Manufacturing  Model # ST216TULEP460V90KWCH Serial #00847 Classification NFPA 86 Class B) used for a process involving a flammable liquid, including but not limited to Elantas RanVar B7-373 VTC containing Vinyl Toluene (FP 108 degrees F), was not adequately designed to protect employees from fire and explosion hazards with use of flammable chemicals.      b)  VPI Area - On or about August 28, 2013, an industrial walk in oven (Oven #2, JPW Design & Manufacturing  Model # ST216TULEP460V90KWCH Serial #00849 Classification NFPA 86 Class B) used for a process involving a flammable liquid, including but not limited to Elantas RanVar B7-373 VTC containing Vinyl Toluene (FP 108 degrees F), was not adequately designed to protect employees from fire and explosion hazards with use of flammable chemicals.
Recent events (2)
  • — I (S) $3500
  • — Z (S) $6300

1910.106 E02 II B 2

Serious Gravity 5 1 instance 33 exposed
Issued
Nov 26, 2013
Abate by
Dec 23, 2013
Penalty
Initial $4,500 · Current $2,500 Reduced
29 CFR 1910.106(e)(2)(ii)(b)(2): The quantity of Category 2, 3 or 4 flammable liquid located outside of an inside storage room or storage cabinet in a building or in any one fire area of a building exceeded 120 gallons:    a)  VPI Area - On or about August 28, 2013, the quantity of Category 3 Flammable Liquids located outside of a flammable storage cabinet exceeded 120 gallons in a room that did not meet the requirement of a flammable storage room.  There were four 55 gallon drums of Elantas RanVar B7-373 VTC containing Vinyl Toluene and a flashpoint of 108 degrees F next to the Class H Polyester VPI System.
Recent events (2)
  • — I (S) $2500
  • — Z (S) $4500

1910.106 E02 III

Serious Gravity 10 1 instance 33 exposed
Issued
Nov 26, 2013
Abate by
Dec 23, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.106(e)(2)(iii): Drainage or other means to control spills was not provided in areas where flammable or combustible liquids were transferred from one tank or container to another container:  a)  VPI Area - On or about September 10, 2013, a Category 3 Flammable Liquid (Elantas RanVar B7-373 VTC containing Vinyl Toluene and a flashpoint of 108 degrees F) was poured into the Class H Polyester VPI System from 55 gallon steel drums using a hoist without a barrier or spill protection.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.106 E02 IV D

Serious Gravity 10 1 instance 33 exposed
Issued
Nov 26, 2013
Abate by
Dec 23, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.106(e)(2)(iv)(d): Flammable or combustible liquids were not drawn from or transferred into vessels, containers, or portable tanks within a building only through a closed piping system, from safety cans, by means of a device drawing through the top, or from a container or portable tanks by gravity through an approved self-closing valve:  a)  VPI Area - On or about September 10, 2013, a Category 3 Flammable Liquid (Elantas RanVar B7-373 VTC containing Vinyl Toluene and a flashpoint of 108 degrees F) was poured into the Class H Polyester VPI System from 55 gallon steel drums using a hoist.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.137 B02 II

Serious Gravity 5 1 instance 13 exposed
Issued
Nov 26, 2013
Abate by
Dec 3, 2013
Penalty
Initial $4,500 · Current $2,500 Reduced
29 CFR 1910.137(b)(2)(ii): Insulating gloves were not given an air test prior to each days usage:      a)  Stator Assembly Room - On and prior to August 28, 2013, employees do not conduct an air test on the rubber insulating gloves to identify flaws prior to using the Criterion Dielectric Strength Tester Model AV-100VA-180-05 for high potential testing on the stators with approximately 4200V output.
Recent events (2)
  • — I (S) $2500
  • — Z (S) $4500

1910.137 B02 VII

Serious Gravity 5 1 instance 13 exposed
Issued
Nov 26, 2013
Abate by
Dec 3, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.137(b)(2)(vii): Protector gloves were not worn over insulating gloves:   a)  Stator Assembly Room - On and prior to August 28, 2013, employees do not wear protector leather gloves over the rubber insulating gloves while using the Criterion Dielectric Strenth Tester Model AV-100VA-180-05 for high potential testing on the stators with approximately 4200V output.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.147 C01

Serious Gravity 5 1 instance 33 exposed
Issued
Nov 26, 2013
Abate by
Jan 31, 2014
Penalty
Initial $4,500 · Current $2,500 Reduced
29 CFR 1910.147(c)(1): The employer did not establish a program consisting of an energy control procedure, employee training and periodic inspections to ensure that before any employee performed any servicing or maintenance on a machine or equipment where the unexpected energizing, startup or release of stored energy could occur and cause injury, the machine or equipment shall be isolated from the energy source and rendered inoperative:    a)  IEC Holden Corporation - On or about August 28, 2013 for the maintenance employee conducting service of equipment, including but not limited to, the HeatTek vacuum pressure impregnation systems, the JPW Design & Manufacture industrial ovens, and the hoists.
Recent events (2)
  • — I (S) $2500
  • — Z (S) $4500

1910.157 G01

Serious Gravity 5 1 instance 33 exposed
Issued
Nov 26, 2013
Abate by
Dec 23, 2013
Penalty
Initial $3,600 · Current $2,000 Reduced
29 CFR 1910.157(g)(1): An educational program was not provided for all employees to familiarize them with the general principles of fire extinguisher use and the hazards involved with incipient stage fire fighting:      a)  IEC Holden Facility - On or about August 28, 2013, employees were not trained in use of portable fire extinguishers.
Recent events (2)
  • — I (S) $2000
  • — Z (S) $3600

1910.332 B01

Serious Gravity 10 1 instance 13 exposed
Issued
Nov 26, 2013
Abate by
Jan 15, 2014
Penalty
Initial $6,300 · Current $3,500 Reduced
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments:      a)  Stator Assembly Room - On or about August 28, 2013, Stator Assembly Employees were not trained on electrical hazards including but not limited to voltage, grounding, resistance, signs of exposure, impact on the body, glove inspection techniques, use of over protective gloves, proper glove storage.  Stator Assembly Employees use a Criterion Dielectric Strength Tester (Model # AV-100VA-180V-05 Serial # 8669) to conduct high potential testing (hipot) on stators.
Recent events (2)
  • — I (S) $3500
  • — Z (S) $6300

1910.335 A01 I

Serious Gravity 10 1 instance 13 exposed
Issued
Nov 26, 2013
Abate by
Dec 3, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not using electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed:  a)  Stator Assembly Room - Stator Assembly Employees, on and prior to, May 28, 2013, did not wear rubber insolated gloves and outer protective gloves to protect from the electrical hazards while conducting a high potential (hipot) test on a stator with a Criterion Dielectric Strength Tester (Model # AV-100VA-180V-05 Serial # 8669) exposing the employee to an electrical hazard.  b)  Stator Assembly Room - On or about August 28, 2013, Stator Assembly employees wore a Class 1 rubber insulating glove (10 Novax by G.B. Industries) rated for maximum 7500V.  The employees are using a Criterion Dielectric Strength Tester (Model # AV-100VA-180V-05 Serial # 8669) that has the capacity of 10,000V output which requires the use of a Class 2 Rubber insulating glove.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1904.29 A

Other-than-serious 1 instance 33 exposed
Issued
Nov 26, 2013
Abate by
Dec 23, 2013
Penalty
Initial $900 · Current $500 Reduced
29 CFR 1904.29(a): 29 CFR 1904.29(a):  The employer did not use OSHA 300, 300-A, and 301 forms, or equivalent forms, for recordable injuries and illnesses. The OSHA 300 form is called the Log of Work-Related Injuries and Illnesses, the 300-A is the Summary of Work-Related Injuries and Illnesses, and the OSHA 301 form is called the Injury and Illness Incident Report:    a)  IEC Holden Corporation - On or about August 28, 2013, the employer did not record injuries including but not limited to a chest wall strain (occurring on 6/12/13) requiring restricted work on the OSHA Form 300 or the 301
Recent events (2)
  • — I (O) $500
  • — Z (O) $900

1910.132 D02

Other-than-serious 2 instances 13 exposed
Issued
Nov 26, 2013
Abate by
Jan 15, 2014
Penalty
Initial $900 · Current $500 Reduced
29 CFR 1910.132(d)(2): The employer did not verify that the required workplace hazard assessment has been performed through a written certification that identifies the workplace evaluated, the person certifying that the evaluation has been performed, the date(s) of the hazard assessment, and, which identifies the document as a certification of hazard assessment:    a)  Stator Assembly Room - On or about, August 28, 2013, for the Stator Assembly Employees that conduct high potential (hipot) testing on stators with a Criterion Dielectric Strength Tester (Model # AV-100VA-180V-05 Serial # 8669) exposing employees to electrical hazards.    b)  VPI Area - On or about August 28, 2013, for the VPI Operators transferring stators out of the Class H Polyester VPI System exposing employees to Elantas RanVar B7-373 VTC containing Vinyl Toluene.
Recent events (2)
  • — I (O) $500
  • — Z (O) $900

View IEC Holden Corporation's full OSHA safety record →