FAIRVIEW, PA ·
OSHA Inspection: ELK CREEK FARM ENTERPRISES, LLC
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of ELK CREEK FARM ENTERPRISES, LLC in 6886 STERRETTANIA ROAD, FAIRVIEW, PA 16415 (NAICS 722511). OSHA activity number 339389652.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ELK CREEK FARM ENTERPRISES, LLC
- Site address
- 6886 STERRETTANIA ROAD
- City
- FAIRVIEW
- State
- PA
- ZIP
- 16415
- Mailing
- 6886 STERRETTANIA ROAD, FAIRVIEW, PA 16415
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 722511
- Employees
- 5
- Ownership type
- A
Citations
11 citations on file for this inspection.
1910.37 A04
- Issued
- Nov 6, 2013
- Abate by
- Nov 29, 2013
- Penalty
- Initial $1,200 · Current $1,200
General-duty citation text
29 CFR 1910.37(a)(4): Safeguard(s) designed to protect employees during an emergency (e.g., sprinkler systems, alarm systems, fire doors, exit lighting), were not in proper working order at all times: A.) Elk Creek Farm Enterprises, LLC dba Elk Creek Inn, 6886 Sterrettania Road, Fairview, PA 16415, southeast dining room entrance, on or about September 5, 2013 and times prior thereto: An emergency light unit above the doorway was unplugged and did not illuminate when tested. B.) Elk Creek Farm Enterprises, LLC dba Elk Creek Inn, 6886 Sterrettania Road, Fairview, PA 16415, southeast dining room entrance, on or about September 5, 2013 and times prior thereto: An emergency exit sign above the doorway did not illuminate when tested.
Recent events (1)
- · Z (S) $1200
1910.37 B02
- Issued
- Nov 6, 2013
- Abate by
- Nov 29, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit": A.) Elk Creek Farm Enterprises, LLC dba Elk Creek Inn, 6886 Sterrettania Road, Fairview, PA 16415, kitchen doorway to the outside, on or about September 5, 2013 and times prior thereto: An emergency exit sign was not posted above the doorway.
Recent events (1)
- · Z (S) $0
1910.157 C01
- Issued
- Nov 6, 2013
- Abate by
- Nov 29, 2013
- Penalty
- Initial $1,200 · Current $1,200
General-duty citation text
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries: A.) Elk Creek Farm Enterprises, LLC dba Elk Creek Inn, 6886 Sterrettania Road, Fairview, PA 16415, kitchen, on or about September 5, 2013 and times prior thereto: An Amerex 6 liter stored pressure wet chemical fire extinguisher (M/N: B260, S/N: AA-964807) was sitting on the floor. B.) Elk Creek Farm Enterprises, LLC dba Elk Creek Inn, 6886 Sterrettania Road, Fairview, PA 16415, bar area, on or about September 5, 2013 and times prior thereto: An Amerex 10# multi-purpose dry chemical fire extinguisher (M/N: 456, S/N: HT-731117) was sitting on the floor.
Recent events (1)
- · Z (S) $1200
1910.157 E02
- Issued
- Nov 6, 2013
- Abate by
- Nov 29, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(e)(2): Portable fire extinguishers were not visually inspected at least monthly: A.) Elk Creek Farm Enterprises, LLC dba Elk Creek Inn, 6886 Sterrettania Road, Fairview, PA 16415, kitchen, on or about September 5, 2013 and times prior thereto: Monthly fire extinguisher inspections were not conducted on an Amerex 6 liter stored pressure wet chemical fire extinguisher (M/N: B260, S/N: AA-964807). B.) Elk Creek Farm Enterprises, LLC dba Elk Creek Inn, 6886 Sterrettania Road, Fairview, PA 16415, bar area, on or about September 5, 2013 and times prior thereto: Monthly inspections were not conducted on an Amerex 10# multi-purpose dry chemical fire extinguisher (M/N: 456, S/N: HT-731117).
Recent events (1)
- · Z (S) $0
1910.157 G02
- Issued
- Nov 6, 2013
- Abate by
- Nov 29, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(g)(2): The educational program to familiarize employees with the general principles of fire extinguisher use and the hazards involved with incipient stage fire fighting was not provided to all employees upon initial employment, and at least annually thereafter: A.) Elk Creek Farm Enterprises, LLC dba Elk Creek Inn, 6886 Sterrettania Road, Fairview, PA 16415, on or about September 5, 2013 and times prior thereto: Employees did not have initial employee fire extinguisher training.
Recent events (1)
- · Z (S) $0
1910.305 B02 I
- Issued
- Nov 6, 2013
- Abate by
- Nov 29, 2013
- Penalty
- Initial $1,600 · Current $1,600
General-duty citation text
29 CFR 1910.305(b)(2)(i): All pull boxes, junction boxes, and fittings were not provided with covers identified for the purpose, and in completed installations, each outlet box shall have a cover, faceplate, or fixture canopy. A.) Elk Creek Farm Enterprises, LLC dba Elk Creek Inn, 6886 Sterrettania Road, Fairview, PA 16415, dishwasher area, on or about September 5, 2013 and times prior thereto: An electrical GFCI outlet was not covered with an approved outlet cover plate. B.) Elk Creek Farm Enterprises, LLC dba Elk Creek Inn, 6886 Sterrettania Road, Fairview, PA 16415, kitchen area, on or about September 5, 2013 and times prior thereto: An energized electrical junction box was not equipped with a cover plate.
Recent events (1)
- · Z (S) $1600
1910.303 B06
- Issued
- Nov 6, 2013
- Abate by
- Nov 29, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(6): Conductors or equipment were located in damp or wet locations; where exposed to gases, fumes, vapors, liquids, or other agents that had a deteriorating effect on the conductors or equipment; or where exposed to excessive temperatures: A.) Elk Creek Farm Enterprises, LLC dba Elk Creek Inn, 6886 Sterrettania Road, Fairview, PA 16415, dishwasher area, on or about September 5, 2013 and times prior thereto: An electrical GFCI outlet and its electrical outlet box was exposed to water from the sink / dishwasher, and presented signs of rusting.
Recent events (1)
- · Z (S) $0
1910.303 B07
- Issued
- Nov 6, 2013
- Abate by
- Nov 29, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(7): Electrical equipment was not installed in a neat and workmanlike manner: A.) Elk Creek Farm Enterprises, LLC dba Elk Creek Inn, 6886 Sterrettania Road, Fairview, PA 16415, dishwasher area, on or about September 5, 2013 and times prior thereto: An electrical GFCI was not activating when tested.
Recent events (1)
- · Z (S) $0
1910.305 G01 IV
- Issued
- Nov 6, 2013
- Abate by
- Nov 29, 2013
- Penalty
- Initial $1,600 · Current $1,600
General-duty citation text
29 CFR 1910.305(g)(1)(iv): Flexible cords and/ or cables were used for purposes prohibited by paragraphs (A) through (F) of 29 CFR 1910.305(g)(1)(iv): A.) Elk Creek Farm Enterprises, LLC dba Elk Creek Inn, 6886 Sterrettania Road, Fairview, PA 16415, kitchen area / outside, on or about September 5, 2013 and times prior thereto: A flexible extension cord was running from an outlet in the kitchen behind the refrigerator to a mobile cooler unit outside. The flexible cord was utilized in a prohibited manner in that the flexible cord was running through a closed doorway and used in lieu of the permanent wiring of the structure. B.) Elk Creek Farm Enterprises, LLC dba Elk Creek Inn, 6886 Sterrettania Road, Fairview, PA 16415, kitchen area, on or about September 5, 2013 and times prior thereto: A flexible extension cord was running from an outlet above the hand washing sink to a microwave oven. The flexible cord was utilized in a prohibited manner in that the flexible cord was running along various wall surfaces and used in lieu of the permanent wiring of the structure.
Recent events (1)
- · Z (S) $1600
1910.303 B01
- Issued
- Nov 6, 2013
- Abate by
- Nov 29, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(1): Electrical equipment was not free from recognized hazards that were likely to cause death or serious physical harm to employees: A.) Elk Creek Farm Enterprises, LLC dba Elk Creek Inn, 6886 Sterrettania Road, Fairview, PA 16415, handwashing sink, on or about September 5, 2013 and times prior thereto: The electrical outlet above the handwashing sink was not equipped with GFCI protection.
Recent events (1)
- · Z (S) $0
1910.101 B
- Issued
- Nov 6, 2013
- Abate by
- Nov 29, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.101(b): Section 3.4.4, Compressed Gas Association pamphlet P1-1965, as adopted by 29 CFR 1910.101(b): Cylinders were not properly supported to prevent them from being knocked over: A.) Elk Creek Farm Enterprises, LLC dba Elk Creek Inn, 6886 Sterrettania Road, Fairview, PA 16415, dishwasher area, on or about September 5, 2013 and times prior thereto: Carbon dioxide cylinders used for the beer tap system were not secured from being knocked over.
Recent events (1)
- · Z (O) $0
More inspections at ELK Creek Farm Enterprises, LLC
View ELK Creek Farm Enterprises, LLC's full OSHA safety record →
More inspections in this industry (NAICS 722511)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339389652.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.