Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,193,745Inspections Most recent open 2026-08-06 Last loaded 2026-08-10

OSHA Inspection: ELK CREEK FARM ENTERPRISES, LLC

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of ELK CREEK FARM ENTERPRISES, LLC in 6886 STERRETTANIA ROAD, FAIRVIEW, PA 16415 (NAICS 722511). OSHA activity number 339495475.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch ELK Creek Farm Enterprises, LLC for free Get an email when a new federal OSHA severe-injury report for ELK Creek Farm Enterprises, LLC is published. One employer, no account, unsubscribe in one click.
Site address
6886 STERRETTANIA ROAD
City
FAIRVIEW
State
PA
ZIP
16415
Mailing
6886 STERRETTANIA ROAD, FAIRVIEW, PA 16415
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
722511
Employees
2
Ownership type
A

5 citations on file for this inspection.

1910.36 D01

Serious Gravity 1 1 instance 1 exposed
Issued
Jan 15, 2014
Abate by
Feb 11, 2014
Penalty
Initial $1,200 · Current $1,200
29 CFR 1910.36(d)(1): Employee(s) were not able to open an exit route door from the inside at all times without keys, tools, or special knowledge:  A.)  Elk Creek Farm Enterprises, LLC dba Elk Creek Inn, 6886 Sterrettania Road, Fairview, PA  16415, kitchen exit door, on or about November 7, 2013 and times prior thereto:  An emergency exit door was locked with a dead bolt and an overhead pin latching device.
Recent events (1)
  • · Z (S) $1200

1910.303 B07 I

Serious Gravity 1 1 instance 1 exposed
Issued
Jan 15, 2014
Abate by
Feb 11, 2014
Penalty
Initial $1,200 · Current $1,200
29 CFR 1910.303(b)(7)(i):   Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment:  A.)   Elk Creek Farm Enterprises, LLC dba Elk Creek Inn, 6886 Sterrettania Road, Fairview, PA  16415, kitchen storage area, on or about November 7, 2013 and times prior thereto:  Unused openings on the dead front of the electrical panel  were covered with duct tape.   B.)    Elk Creek Farm Enterprises, LLC dba Elk Creek Inn, 6886 Sterrettania Road, Fairview, PA  16415, kitchen storage area, on or about November 7, 2013 and times prior thereto:  A knockout blank was missing on the left side of the electrical junction box.
Recent events (1)
  • · Z (S) $1200

1910.303 G01 II

Serious Gravity 1 1 instance 1 exposed
Issued
Jan 15, 2014
Abate by
Feb 11, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(ii):   The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:  A.)   Elk Creek Farm Enterprises, LLC dba Elk Creek Inn, 6886 Sterrettania Road, Fairview, PA  16415, kitchen storage area, on or about November 7, 2013 and times prior thereto:  Plastic milk crates, food and a Werner folding ladder were stored in front of an electrical panel box.
Recent events (1)
  • · Z (S) $0

1910.305 B02 I

Serious Gravity 1 2 instances 1 exposed
Issued
Jan 15, 2014
Abate by
Feb 11, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(2)(i):   All pull boxes, junction boxes, and fittings were not provided with covers identified for the purpose, and in completed installations, each outlet box did not have a cover, faceplate, or fixture canopy.  A.)   Elk Creek Farm Enterprises, LLC dba Elk Creek Inn, 6886 Sterrettania Road, Fairview, PA  16415, kitchen storage area, on or about November 7, 2013 and times prior thereto:  A junction box was equipped with a cover that was too small.  B.)    Elk Creek Farm Enterprises, LLC dba Elk Creek Inn, 6886 Sterrettania Road, Fairview, PA  16415, food preparation area, on or about November 7, 2013 and times prior thereto:  An electrical outlet box containing a 240 volt outlet was not equipped with a cover plate.
Recent events (1)
  • · Z (S) $0

1910.101 B

Other-than-serious 2 instances 1 exposed
Issued
Jan 15, 2014
Abate by
Feb 11, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.101(b):   Section 3.3.8 Compressed Gas Association Pamphlet P1-1965, as adopted by 29 CFR 1910.101(b):  Caps were provided for valve protection, and were not kept on the cylinder for storage:  A.)  Elk Creek Farm Enterprises, LLC dba Elk Creek Inn, 6886 Sterrettania Road, Fairview, PA  16415, dishwasher area, on or about November 7, 2013 and times prior thereto:  An inactive carbon dioxide cylinder was stored without the cap affixed to the cylinder for valve protection.
Recent events (1)
  • · Z (O) $0

View ELK Creek Farm Enterprises, LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339495475.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.