WHITEWATER, WI ·
OSHA Inspection: GENERAC POWER SYSTEMS, INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of GENERAC POWER SYSTEMS, INC. in 757 N NEWCOMB ST, WHITEWATER, WI 53190 (NAICS 335312). OSHA activity number 339409989.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- GENERAC POWER SYSTEMS, INC.
- Site address
- 757 N NEWCOMB ST
- City
- WHITEWATER
- State
- WI
- ZIP
- 53190
- Mailing
- S45 W29290 HWY. 59, WAUKESHA, WI 53189
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 335312
- Employees
- 400
- Ownership type
- Private (A)
Citations
5 citations on file for this inspection.
1910.137 B02 II
- Issued
- Dec 19, 2013
- Abate by
- Dec 30, 2013
- Penalty
- Initial $7,000 · Current $3,500 Reduced
General-duty citation text
29 CFR 1910.137(b)(2)(ii): Insulating equipment were not inspected for damage before each day's use and immediately following any incident that can reasonably be suspected of having caused damage. Insulating gloves shall be given an air test, along with the inspection. On or about July 16, 2013 employees were wearing insulated electrical gloves that had not been inspected for damage prior to each use.
Recent events (2)
- · I (S) $3500
- · Z (S) $7000
1910.137 B02 VIII
- Issued
- Dec 19, 2013
- Abate by
- Dec 30, 2013
- Penalty
- Initial $7,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.137(b)(2)(viii): Electrical protective equipment were not subjected to periodic electrical tests. Test voltages and the maximum intervals between tests shall be in accordance with Table I-5 and Table I-6. On or about October 16, 2013 insulated electrical gloves used by employees had not received an electrical test every six months.
Recent events (2)
- · I (S) $0
- · Z (S) $7000
1910.147 C07 I B
- Issued
- Dec 19, 2013
- Abate by
- Dec 30, 2013
- Penalty
- Initial $7,000 · Current $3,000 Reduced
General-duty citation text
29 CFR 1910.147(c)(7)(i)(B): Each affected employee was not instructed in the purpose and use of the energy control procedure. On or about October 16, 2013 employees operating the varnisher machine had not received affected employee energy control training.
Recent events (2)
- · I (S) $3000
- · Z (S) $7000
1910.212 A01
- Issued
- Dec 19, 2013
- Abate by
- Dec 30, 2013
- Penalty
- Initial $7,000 · Current $3,500 Reduced
General-duty citation text
29 CFR 1910.212(a)(1): Types of guarding. One or more methods of machine guarding wer not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks. Examples of guarding methods are-barrier guards, two-hand tripping devices,electronic safety devices, etc. a) on or about August 12, 2013, employees were exposed to pinch point hazards on the automated powerhead machine due to lack of effective machine guarding." b) On or about October 16, 2013, employees were exposed to pinch point hazards on the varnisher machine due to the lack of effective machine guarding."
Recent events (2)
- · I (S) $3500
- · Z (S) $7000
1910.147 D04 I
- Issued
- Dec 19, 2013
- Abate by
- Dec 30, 2013
- Penalty
- Initial $7,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.147(d)(4)(i): Lockout or tagout devices shall be affixed to each energy isolating device by authorized employees. On or about October 16, 2013 employees did not apply lock out devices while entering the varnisher to perform maintenance duties.
Recent events (2)
- · I (S) $0
- · Z (S) $7000
More inspections at Generac Power Systems, INC.