OSHA Inspection: VETERANS ADMINISTRATION MEDICAL CENTER

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of VETERANS ADMINISTRATION MEDICAL CENTER in 17273 STATE ROUTE 104, CHILLICOTHE, OH 45601 (NAICS 622210). OSHA activity number 339427650.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Veterans Administration Medical Center for free Get an email when a new federal OSHA severe-injury report for Veterans Administration Medical Center is published. One employer, no account, unsubscribe in one click.
Site address
17273 STATE ROUTE 104
City
CHILLICOTHE
State
OH
ZIP
45601
Mailing
17273 STATE ROUTE 104, CHILLICOTHE, OH 45601
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Union (A)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
622210
Employees
1452
Ownership type
Federal government (D)

3 citations on file for this inspection.

1910.332 B01

Deleted Serious Gravity 5 1 instance 1 exposed
Issued
Feb 6, 2014
Abate by
Mar 12, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.332(b)(1): Practices addressed in this standard. Employees shall be trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertain to their respective job assignments.  A HVAC Mechanic and Electrician who had performed energized electrical work consisting of voltage testing on voltages up to 480 Volts AC had not received specific electrical safety-related work practice training on when and what personal protective equipment to wear to protect himself against electric shock and arc flash.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.335 A01

Repeat Gravity 5 1 instance 1 exposed
Issued
Feb 6, 2014
Abate by
Mar 31, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.335(a)(1): Employees working in areas where there were potential electrical hazards were not provided with, and did not use, electrical protective equipment that is appropriate for the specific parts of the body to be protected and for the work to be performed:    a.  On or about September 19, 2013, in Building 261, an electrician was exposed to an electric shock and arc flash hazard while voltage testing lighting circuits, 277 Volt AC siingle phase for exit lights without wearing the appropriate personal protective equipment.       b.   On or about November 5, 2013, in Building 35 on a Air Handler Unit, a HVAC mechanic was exposed to an electric shock and arc flash hazard by not wearing the appropriate personal protective equipment when pushing in an energized 240 Volt AC blade that did not engage inside an electrical disconnect switchbox.      Veterans Administration Medical Center, Chillicothe, OH was previously cited for a violation of this occupational safety and health standard or its equivalent standard, which was contained in OSHA inspection number 314652629, citation number 1, item number 18 and was affirmed as a final order on September 14, 2010, with respect to a workplace located at 17273 St. Rt. 104, Chillicothe, OH 45601.
Recent events (2)
  • · I (R) $0
  • · Z (R) $0

1910.146 C02

Other-than-serious 1 instance 5 exposed
Issued
Feb 6, 2014
Abate by
Feb 26, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.146(c)(2): If the workplace contains permit spaces, the employer shall inform exposed employees, by posting danger signs or by any other equally effective means, of the existence and location of and the danger posed by the permit spaces.  NOTE: A sign reading DANGER -- PERMIT-REQUIRED CONFINED SPACE, DO NOT ENTER or using other similar language would satisfy the requirement for a sign.  In Building 261, Power Plant, the two pits, 10 ft. x 50 ft. by 10 ft., containing wood chips for the biomass boiler were not identified as a permit required confined spaces.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

View Veterans Administration Medical Center's full OSHA safety record →