Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: LIBERTY CONTRACTING LLC

Unprogrammed Other inspection · Safety discipline

On , OSHA opened an unprogrammed Other safety inspection of LIBERTY CONTRACTING LLC in 9255 S PADRE ISLAND DR, CORPUS CHRISTI, TX 78411 (NAICS 238210). OSHA activity number 339481962.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Liberty Contracting LLC — free Get an email when a new federal OSHA severe-injury report for Liberty Contracting LLC is published. One employer, no account, unsubscribe in one click.
Site address
9255 S PADRE ISLAND DR
City
CORPUS CHRISTI
State
TX
ZIP
78411
Mailing
2020 SILVER MOUNTAIN, SAN ANTONIO, TX 78264
Inspection type
Unprogrammed Other (I)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
9
Ownership type
A

4 citations on file for this inspection.

1926.403 B01

Serious Gravity 1 3 instances 9 exposed
Issued
Jan 31, 2014
Abate by
Mar 3, 2014
Penalty
Initial $1,200 · Current $1,200
29 CFR 1926.403(b)(1): 29 CFR 1926.403(b)(1): Employer did not ensure that electrical equipment was free from recognized hazards that were likely to cause death or serious physical harm to employees:  At this location: Employees were exposed to shock hazards from contact with electrical equipment that contained the following deficiencies:  a) North end of the workplace, ground level: electrical power panelboard used as a workplace temporary electrical service did not contain a means to disconnect all conductors in the building or other structure from the service entrance conductors in violation of Article 230.70 of the National Electrical Code,  b) Throughout the worksite building under construction: Type MC cable used by employees as extension cords that supplied electrical power to portable electrical equipment used by employees engaged in construction operations were attached to 15 ampere, 120 volt, 3 pole male plugs in violation of Article 300.15 of the National Electrical Code,  c) North end of the workplace, ground level: Employees were exposed to shock-hazards from contact with two Type MC cables used as Aerial Cables and transferred electrical power of 120 volts AC from the  top of the ground level temporary power pole to the building under construction; but were not suspended/supported from an overhead messenger cable as required by Article 330.10(B)(4) of the National Electrical Code.
Recent events (1)
  • — Z (S) $1200

1926.404 B01 II

Serious Gravity 1 4 instances 9 exposed
Issued
Jan 31, 2014
Abate by
Mar 3, 2014
Penalty
Initial $1,200 · Current $1,200
29 CFR 1926.404(b)(1)(ii): On a construction site, where an assured equipment grounding program was not utilized, all 120-volt, single-phase, 15 and 20 ampere receptacle outlets which were not a part of the permanent wiring of the building or structure and which are in use by employees did not have approved ground fault circuit interrupters for personal protection:  At this location: Employees were exposed to shock hazards from contact with portable electrical equipment not protected by ground fault circuit interrupters. The portable electrical equipment used by employees engaged in construction operations and not powered by ground fault circuit interrupters operated at 120 volts AC in the following locations:  a) Ground floor, north end of the worksite, temporary power pole panelboard at a height of 36 inches above the ground,   b) 2nd floor, northeast interior area of the building at a height of 34 inches above the workplace floor, a 15 ampere duplex receptacle.  c) 2nd floor, northeast interior area of the building at a height of 56 inches above the workplace floor, a 15 ampere duplex receptacle, a 15 ampere duplex receptacle.  d) 3rd floor, northeast interior area of the building at a height of 51 inches above the workplace floor, a 15 ampere duplex receptacle.
Recent events (1)
  • — Z (S) $1200

1926.405 A02 II B

Serious Gravity 1 1 instance 9 exposed
Issued
Jan 31, 2014
Abate by
Mar 3, 2014
Penalty
Initial $1,200 · Current $1,200
29 CFR 1926.405(a)(2)(ii)(B): 29 CFR 1926.405(a)(2)(ii)(B): 29 CFR 1926.405(a)(2)(ii)(B): Runs of open conductors were not located where the conductors will not be subject to physical damage. The conductors were not fastened at intervals not exceeding 10 feet (3.05 m); with branch-circuit conductors laid upon the floor.     At this location: Employees were exposed to shock hazards from contact with branch circuit conductors enclosed within type "MC" cable (metal clad) that operated at 120 volts AC, and were laid on the floor in the following locations:  a) 2nd floor of the workplace, the energized MC cable ran in a north/south direction while it was laid upon the floor,  b) 3rd floor of the workplace, the energized MC cable ran in a north/south direction while it was laid upon the floor,  c) 3rd floor of the workplace, the energized MC cable rain in an east/west direction from the 3rd floor building window to      the center of the hallway floor.
Recent events (1)
  • — Z (S) $1200

1926.405 B02

Serious Gravity 1 3 instances 9 exposed
Issued
Jan 31, 2014
Abate by
Mar 3, 2014
Penalty
Initial $1,200 · Current $1,200
29 CFR 1926.405(b)(2): In energized installations, each outlet box did not have a cover, faceplate, or fixture canopy:  At this location: Employees were exposed to shock hazards from contact with exposed, energized terminals of installed duplex receptacles that did not have a cover. The installed duplex receptacles that did not have a cover; operated at 120 volts AC, and were used by employees engaged in construction operations at the following locations:  a) 2nd floor, northeast interior area of the building at a height of 34 inches above the workplace floor,  b) 2nd floor, northeast interior area of the building at a height of 56 inches above the workplace floor,  c) 3rd floor, northeast interior area of the building at a height of 51 inches above the workplace floor.
Recent events (1)
  • — Z (S) $1200

View Liberty Contracting LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339481962.