BERWYN, IL ·
OSHA Inspection: VHS OF ILLINOIS
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of VHS OF ILLINOIS in 3249 SOUTH OAK PARK AVENUE, BERWYN, IL 60402 (NAICS 622110). OSHA activity number 339495061.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- VHS OF ILLINOIS
- Site address
- 3249 SOUTH OAK PARK AVENUE
- City
- BERWYN
- State
- IL
- ZIP
- 60402
- Mailing
- 3249 SOUTH OAK PARK AVENUE, BERWYN, IL 60402
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 622110
- Employees
- 2000
- Ownership type
- Private (A)
Citations
7 citations on file for this inspection.
1910.147 C01
- Issued
- Mar 20, 2014
- Abate by
- Oct 6, 2014
- Penalty
- Initial $7,000 · Current $3,000 Reduced
General-duty citation text
29 CFR 1910.147(c)(1): The employer did not establish a program consisting of an energy control procedure, employee training and periodic inspections to ensure that before any employee performed any servicing or maintenance on a machine or equipment where the unexpected energing, startup or release of stored energy could occur and cause injury, the machine or equipment shall be isolated from the energy source and rendered inoperative: a. Entire facility - On or about November 15, 2013, the employer had not implemented an adequate energy control program for employees who perform servicing and maintenance on such equipment including but not limited to, air handlers, boilers, fans washer/dryer machines. Employees were thereby exposed to the hazards associated with the unexpected energization of equipment.
Recent events (2)
- · I (S) $3000
- · Z (S) $7000
1910.305 D
- Issued
- Mar 20, 2014
- Penalty
- Initial $7,000 · Current $1,000 Reduced
General-duty citation text
29 CFR 1910.305(d): Panelboards were not mounted in cabinets, cutout boxes, or enclosures approved for the purpose and were not dead front: a. South building basement - On or about November 15, 2013, the electrical panelboard in the telecom room was not dead front, thereby exposing employees to live electrical parts.
Recent events (2)
- · I (O) $1000
- · Z (S) $7000
1910.332 B01
- Issued
- Mar 20, 2014
- Abate by
- Oct 6, 2014
- Penalty
- Initial $7,000 · Current $3,500 Reduced
General-duty citation text
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments: a. Facility - On or about November 15, 2013, employees required to perform voltage testing (110- 480V) on such equipment but not limited to outlets, ballasts, sump pump motors and air handlers were not provided with training in the safety related work practices emphasized in 29 CFR 1910.331 - 1910.335. The employees were thereby exposed to hazards of electrical shock and arc flash/blasts.
Recent events (2)
- · I (S) $3500
- · Z (S) $7000
1910.333 B02 I
- Issued
- Mar 20, 2014
- Abate by
- May 6, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.333(b)(2)(i): The employer did not make a written copy of the procedures outlined in paragraph (b)(2) of 29 CFR 1910.333 available for inspection by employees and by the Assistant Secretary of Labor and his or her authorized representatives: a. Facility - On or about November 15, 2013, the employer did not maintain written electrical safety-related work practice procedures outlined in 29 CFR 1910.333(b)(2) for employees who are required to perform voltage testing (110- 480V) on such equipment but not limited to outlets, ballasts, sump pump motors and air handlers.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1910.335 A01 I
- Issued
- Mar 20, 2014
- Abate by
- May 6, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not using electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed: a. Facility - On or about November 15, 2013, employees were required to perform voltage testing (110- 480V) on such equipment but not limited to outlets, ballasts, sump pump motors and air handlers. The employees were not provided with electrical protective equipment including but not limited to fire retardant clothing, hard hat, face shield, and adequate voltage rated gloves. The employees were thereby exposed to hazards of electrical shock and arc flash/blasts.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1910.335 A02 I
- Issued
- Mar 20, 2014
- Abate by
- May 6, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.335(a)(2)(i): When working near exposed energized conductors or circuit parts, each employee did not use insulated tools or handling equipment when the tools or handling equipment might have made contact with such conductors or parts: a. Facility - On or about November 15, 2013, employees were required to perform voltage testing (110- 480V) on such equipment but not limited to outlets, ballasts, sump pump motors and air handlers. The employees were not provided with insulated tools and were thereby exposed to the hazards of electrical shock and arc flash/blasts.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1910.303 G01 II
- Issued
- Mar 20, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage: a. Basement Pump Area - On or about November 15, 2013, the south pump electrical panel box was blocked by stored materials which could interfere with ready access to the electric equipment in the case of an emergency.
Recent events (2)
- · I (O) $0
- · Z (O) $0
More inspections at VHS of Illinois
View VHS of Illinois's full OSHA safety record →
More inspections in this industry (NAICS 622110)
More inspections in IL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 339495061.