Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,197,549Inspections Most recent open 2026-08-27 Last loaded 2026-08-31

OSHA Inspection: VHS OF ILLINOIS

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of VHS OF ILLINOIS in 3249 SOUTH OAK PARK AVENUE, BERWYN, IL 60402 (NAICS 622110). OSHA activity number 339495061.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch VHS of Illinois for free Get an email when a new federal OSHA severe-injury report for VHS of Illinois is published. One employer, no account, unsubscribe in one click.
Establishment
VHS OF ILLINOIS
Site address
3249 SOUTH OAK PARK AVENUE
City
BERWYN
State
IL
ZIP
60402
Mailing
3249 SOUTH OAK PARK AVENUE, BERWYN, IL 60402
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
622110
Employees
2000
Ownership type
Private (A)

7 citations on file for this inspection.

1910.147 C01

Serious Gravity 10 1 instance 5 exposed
Issued
Mar 20, 2014
Abate by
Oct 6, 2014
Penalty
Initial $7,000 · Current $3,000 Reduced
29 CFR 1910.147(c)(1): The employer did not establish a program consisting of an energy control procedure, employee training and periodic inspections to ensure that before any employee performed any servicing or maintenance on a machine or equipment where the unexpected energing, startup or release of stored energy could occur and cause injury, the machine or equipment shall be isolated from the energy source and rendered inoperative:    a. Entire facility - On or about November 15, 2013, the employer had not implemented an adequate energy control program for employees who perform servicing and maintenance on such equipment including but not limited to, air handlers, boilers, fans washer/dryer machines.  Employees were thereby exposed to the hazards associated with the unexpected energization of equipment.
Recent events (2)
  • · I (S) $3000
  • · Z (S) $7000

1910.305 D

Other-than-serious 1 instance 5 exposed
Issued
Mar 20, 2014
Penalty
Initial $7,000 · Current $1,000 Reduced
29 CFR 1910.305(d): Panelboards were not mounted in cabinets, cutout boxes, or enclosures approved for the purpose and were not dead front:      a. South building basement -  On or about November 15, 2013, the electrical panelboard in the telecom room was not dead front, thereby exposing employees to live electrical parts.
Recent events (2)
  • · I (O) $1000
  • · Z (S) $7000

1910.332 B01

Serious Gravity 10 1 instance 3 exposed
Issued
Mar 20, 2014
Abate by
Oct 6, 2014
Penalty
Initial $7,000 · Current $3,500 Reduced
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments:     a. Facility - On or about November 15, 2013, employees required to perform voltage testing (110- 480V) on such equipment but not limited to outlets, ballasts, sump pump motors and air handlers were not provided with training in the safety related work practices emphasized in 29 CFR 1910.331 - 1910.335.  The employees were thereby exposed to hazards of electrical shock and arc flash/blasts.
Recent events (2)
  • · I (S) $3500
  • · Z (S) $7000

1910.333 B02 I

Serious Gravity 10 1 instance 5 exposed
Issued
Mar 20, 2014
Abate by
May 6, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.333(b)(2)(i): The employer did not make a written copy of the procedures outlined in paragraph (b)(2) of 29 CFR 1910.333 available for inspection by employees and by the Assistant Secretary of Labor and his or her authorized representatives:  a. Facility - On or about November 15, 2013, the employer did not maintain written electrical safety-related work practice procedures outlined in 29 CFR 1910.333(b)(2) for employees who are required to perform voltage testing (110- 480V) on such equipment but not limited to outlets, ballasts, sump pump motors and air handlers.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.335 A01 I

Serious Gravity 10 1 instance 5 exposed
Issued
Mar 20, 2014
Abate by
May 6, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not using electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed:  a. Facility - On or about November 15, 2013, employees were required to perform voltage testing (110- 480V) on such equipment but not limited to outlets, ballasts, sump pump motors and air handlers. The employees were not provided with electrical protective equipment including but not limited to fire retardant clothing, hard hat, face shield, and adequate voltage rated gloves.  The employees were thereby exposed to hazards of electrical shock and arc flash/blasts.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.335 A02 I

Serious Gravity 10 1 instance 5 exposed
Issued
Mar 20, 2014
Abate by
May 6, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.335(a)(2)(i): When working near exposed energized conductors or circuit parts, each employee did not use insulated tools or handling equipment when the tools or handling equipment might have made contact with such conductors or parts:  a. Facility - On or about November 15, 2013, employees were required to perform voltage testing (110- 480V) on such equipment but not limited to outlets, ballasts, sump pump motors and air handlers.  The employees were not provided with insulated tools and were thereby exposed to the hazards of electrical shock and arc flash/blasts.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.303 G01 II

Other-than-serious 1 instance 5 exposed
Issued
Mar 20, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:  a. Basement Pump Area - On or about November 15, 2013, the south pump electrical panel box was blocked by stored materials which could interfere with ready access to the electric equipment in the case of an emergency.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

View VHS of Illinois's full OSHA safety record →