Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: OUTRIGGER HOTELS HAWAII

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of OUTRIGGER HOTELS HAWAII in 150 KAIULANI AVE., HONOLULU, HI 96815 (NAICS 721110). OSHA activity number 339512097.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Outrigger Hotels Hawaii — free Get an email when a new federal OSHA severe-injury report for Outrigger Hotels Hawaii is published. One employer, no account, unsubscribe in one click.
Site address
150 KAIULANI AVE.
City
HONOLULU
State
HI
ZIP
96815
Mailing
150 KAIULANI AVE., HONOLULU, HI 96815
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
721110
Employees
82
Ownership type
A

3 citations on file for this inspection.

1910.304 B03 I

Deleted Serious Gravity 5 2 instances 12 exposed
Issued
Dec 31, 2013
Penalty
Initial $3,613 · Current $0 Reduced

Hazardous substances 8870

29 CFR 1910.304(b)(3)(i): All 125-volt, single-phase, 15- and 20-ampere receptacles installed in wet locations were not equipped with ground-fault circuit-interrupter protection for personnel.  a) LAUNDRY ROOM AREA: On or about December 5, 2013 the employer did not ensure that receptacle(s) were equipped with a GFCI where the potential of a water leak was feasible.  These conditions exposed the employees to the hazards associated with electrical shock.
Recent events (2)
  • — I (S) $0
  • — Z (S) $3613

1910.305 B02

Serious Gravity 5 2 instances 6 exposed
Issued
Dec 31, 2013
Penalty
Initial $3,613 · Current $2,710 Reduced

Hazardous substances 8870

29 CFR 1910.305(b)(2): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy:    a) SWIMMING POOL EQUIPMENT AREA: On or about December 5, 2013 the employer did not ensure that a junction box was equipped with a cover.     b) BOILER ROOM AREA: On or about December 5, 2013 the employer did not ensure that a breaker panel was completely enclosed. The top section of the panel was missing a cover.     These conditions exposed the employees to the hazards associated with electrical shock.
Recent events (2)
  • — I (S) $2709.75
  • — Z (S) $3613

1910.305 J04 V

Deleted Serious Gravity 5 2 instances 6 exposed
Issued
Dec 31, 2013
Penalty
Initial $2,890 · Current $0 Reduced

Hazardous substances 8870

29 CFR 1910.305(j)(4)(v): The disconnect of a motor was not readily accessible.    LAUNDRY ROOM AREA:  On or about December 5, 2013 the employer did not ensure that disconnect electrical box(s) were accessible in the event of an emergency.  Laundry carts and/or other items were stacked in front of the electrical box(s) impeding the location and/or accessibility, thus exposing employees to electrical and/or other hazards associated with not having immediate access to the disconnect lever.
Recent events (2)
  • — I (S) $0
  • — Z (S) $2890

View Outrigger Hotels Hawaii's full OSHA safety record →