HONOLULU, HI —
OSHA Inspection: OUTRIGGER HOTELS HAWAII
Planned inspection · Health discipline
At a glance
On , OSHA opened a planned health inspection of OUTRIGGER HOTELS HAWAII in WYNDHAM WAIKIKI BEACH WALK 227 LEWERS STREET, HONOLULU, HI 96815 (NAICS 721110). OSHA activity number 339514267.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- OUTRIGGER HOTELS HAWAII
- Site address
- WYNDHAM WAIKIKI BEACH WALK 227 LEWERS STREET
- City
- HONOLULU
- State
- HI
- ZIP
- 96815
- Mailing
- WYNDHAM WAIKIKI BEACH WALK 227 LEWERS STREET, HONOLULU, HI 96815
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 721110
- Employees
- 65
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.304 G05
- Issued
- Dec 31, 2013
- Penalty
- Initial $3,400 · Current $2,550 Reduced
General-duty citation text
29 CFR 1910.304(g)(5): Grounding path. The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective. This violation was discovered on December 9, 2013; where employees worked with and around the following equipment which was not properly grounded: a) One Festool, CT 33, Dust Extractor. b) One Stinger 2.5 gallon Wet/Dry vacuum.
Recent events (2)
- — I (S) $2550
- — Z (S) $3400
1910.305 G02 II
- Issued
- Dec 31, 2013
- Penalty
- Initial $3,400 · Current $2,550 Reduced
General-duty citation text
29 CFR 1910.305(g)(2)(ii): Flexible cords may be used only in continuous lengths without splice or tap. Hard-service cord and junior hard-service cord No. 14 and larger may be repaired if spliced so that the splice retains the insulation, outer sheath properties, and usage characteristics of the cord being spliced. This violation was discovered on December 9, 2013; where maintenance employees worked with and around a damaged 120 volt Hitachi cutoff saw. The flexible cord to the motor was spliced with uncovered plastic wire nuts. The plastic wire nuts were subjected to strain imposed by a dust collection bag that rubbed on them. Employees that worked with and around the cutoff saw were thereby exposed to an electrical hazard.
Recent events (2)
- — I (S) $2550
- — Z (S) $3400
1910.132 D02
- Issued
- Dec 31, 2013
- Abate by
- Jan 15, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.132(d)(2): The employer did not verify that the required workplace hazard assessment had been performed through a written certification that identifies the workplace evaluated; the person certifying that the evaluation has been performed; the date(s) of the hazard assessment; and, which identifies the document as a certification of hazard assessment: This violation was discovered on December 9, 2013; where employees were required to work with hazardous chemicals such as EcoLab Solar Brite, and EcoLab Fast Form Degreaser. The employee's skin and eye were exposed to the hazards and necessitated the uses of personal protective equipment. The employer did not verify, through a written certification, that the required workplace hazard assessment had been performed.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.333 B02 I
- Issued
- Dec 31, 2013
- Abate by
- Jan 27, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.333(b)(2)(i): The employer did not maintain a copy of the written procedures outlined in 29 CFR 1910.333(b)(2) and did not make it available for inspection by employees: This violation was discovered on December 9, 2013; where maintenance employees were required to work with premises wiring, lighting, machinery and other equipment. The employer did not have in place and/or in writing a safety-related work practices program as required by 29 CFR 1910.333(b)(l).
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Outrigger Hotels Hawaii
View Outrigger Hotels Hawaii's full OSHA safety record →
More inspections in this industry (NAICS 721110)
More inspections in HI
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339514267.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.