CLACKAMAS, OR —
OSHA Inspection: OREGON ARMY NATIONAL GUARD, CSMS
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of OREGON ARMY NATIONAL GUARD, CSMS in 15300 INDUSTRIAL WAY, CLACKAMAS, OR 97015 (NAICS 928110). OSHA activity number 339514804.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- OREGON ARMY NATIONAL GUARD, CSMS
- Site address
- 15300 INDUSTRIAL WAY
- City
- CLACKAMAS
- State
- OR
- ZIP
- 97015
- Mailing
- 15300 SE MINUTEMAN WAY BUILDING 6488, CLACKAMAS, OR 97015
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 928110
- Employees
- 89
- Ownership type
- D
Citations
8 citations on file for this inspection.
1910.219 D01
- Issued
- Jan 6, 2014
- Abate by
- Mar 15, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.219(d)(1): Pulley(s) with part(s) seven feet or less from the floor or work platform were not guarded in accordance with the requirements specified in 29 CFR 1910.219(m) and (o): (a) On or about December 11, 2013 the inspection revealed a pulley on the Adler sewing machine serial number 0353000116, property number 3530-00-392-4652 that was not guarded. The sewing machine was located in in the textile room at Camp Withycombe in Clackamas, Oregon.
Recent events (1)
- — Z (S) $0
1910.219 E03 I
- Issued
- Jan 6, 2014
- Abate by
- Mar 15, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.219(e)(3)(i): Vertical or inclined belt(s) were not enclosed by guard(s) conforming to the requirements specified at 29 CFR 1910.219(m) and (o). (a) On or about December 11, 2013 the inspection revealed that employees were potentially exposed to serious injury from the exposed belt of the Adler sewing machine, serial number 035300016, property number 3530-00-892-4652 that was located in the textile room at Camp Withycombe in Portland, Oregon.
Recent events (1)
- — Z (S) $0
1910.303 C03 I
- Issued
- Jan 6, 2014
- Abate by
- Feb 20, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(c)(3)(i): All splices and joints and the free ends of the conductors were not covered with an insulation equivalent to that of the conductors or with an insulating device identified for the purpose. (a) On or about December 11, 2013 the inspection revealed spliced wires that were not covered with an insulation equivalent to that of the conductors or with an insulating device identified for the purpose. The spliced wires were located inside a junction box with a hinged opening, on the east wall adjacent to the entrance to room 26 in the main power division building at Campy Withycombe in Clackamas.
Recent events (1)
- — Z (S) $0
1910.303 H02 V E
- Issued
- Jan 6, 2014
- Abate by
- Feb 20, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(h)(2)(v)(E): Doors and covers of enclosures used solely as pull boxes, splice boxes, or junction boxes were not locked, bolted, or screwed on to prevent unauthorized personnel access. (a) On or about December 11, 2013 the inspection revealed a junction box with a hinged cover that was not locked, bolted, or screwed on to prevent unauthorized personnel access. The junction box was located on the east wall adjacent to the entrance to room 26 in the main power division building at Camp Withycombe in Clackamas, Oregon.
Recent events (1)
- — Z (S) $0
1910.305 A02 IX
- Issued
- Jan 6, 2014
- Abate by
- Feb 20, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(a)(2)(ix): All lamps for general illumination were not protected from accidental contact or breakage by a suitable fixture or lampholder with a guard. (a) On or about December 11, 2013 the inspection revealed a fluorescent light that was not protected from accidental contact. The light was located in the magna non-destructive testing room at Camp Withycombe in Clackamas, Oregon. (b) On or about December 11, 2013 the inspection revealed an incandescent light that was not protected from accidental contact. Located in the magna non-destructive testing room at Camp Withycombe in Clackamas, Oregon.
Recent events (1)
- — Z (S) $0
1910.305 B02 I
- Issued
- Jan 6, 2014
- Abate by
- Feb 20, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose: (a) On or about December 10, 2013 the inspection revealed an outlet that was not provided with a cover. The outlet was located on the east wall of the conference room #129 in building 6481 at Camp Withycombe in Clackamas, Oregon. (b) On or about December 10, 2013 the inspection revealed a junction box that was not provided with a cover. The junction box was located in room 135 in building 6481 at Camp Withycombe in Clackamas, Oregon.
Recent events (1)
- — Z (S) $0
1910.305 B01 I
- Issued
- Jan 6, 2014
- Abate by
- Feb 20, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasion, and openings through which conductors enter were not effectively closed. (a) On or about December 11, 2013 the inspection revealed a conductor entering a cutout that was not protected from abrasion, also the opening through which the conductor entered was not effectively closed. The hazard was located on the right side of the junction box located on the wall adjacent to the entrance to room 26 in the main power division building at Camp Withycombe in Clackamas, Oregon.
Recent events (1)
- — Z (O) $0
1910.305 B01 II
- Issued
- Jan 6, 2014
- Abate by
- Feb 20, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: (a) On or about December 11, 2013 the inspection revealed an unused opening that was not effectively closed. The opening was located under the Siemens switch box providing power to a bench press in room 191B at Camp Withycombe in Clackamas, Oregon.
Recent events (1)
- — Z (O) $0
More inspections at Oregon Army National Guard, Csms
View Oregon Army National Guard, Csms's full OSHA safety record →
More inspections in this industry (NAICS 928110)
More inspections in OR
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339514804.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.