CHESAPEAKE, VA ·
OSHA Inspection: RAPID DEPLOYABLE SYSTEMS, INC.
Planned inspection · Health discipline
At a glance
On , OSHA opened a planned health inspection of RAPID DEPLOYABLE SYSTEMS, INC. in 2001 OLD GREEBRIER ROAD SUITE B, CHESAPEAKE, VA 23320 (NAICS 336611). OSHA activity number 339522732.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- RAPID DEPLOYABLE SYSTEMS, INC.
- Site address
- 2001 OLD GREEBRIER ROAD SUITE B
- City
- CHESAPEAKE
- State
- VA
- ZIP
- 23320
- Mailing
- 2001 OLD GREEBRIER ROAD SUITE B, CHESAPEAKE, VA 23320
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Health
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 336611
- Employees
- 10
- Ownership type
- Private (A)
Citations
4 citations on file for this inspection.
1910.304 A02
- Issued
- Jan 2, 2014
- Penalty
- Initial $1,360 · Current $952 Reduced
General-duty citation text
29 CFR 1910.304(a)(2): Polarity of connections. No grounded conductor may be attached to any terminal or lead so as to reverse designated polarity. a.) Rapid Deployable Systems, Inc., Shop: On or about 12/09/13, the electrical outlet on the work bench supplying power to a shop-vac and a chop saw was wired with a reverse hot and neutral connections, creating a electrical shock hazard.
Recent events (2)
- · I (S) $952
- · Z (S) $1360
1910.304 B03 II A
- Issued
- Jan 2, 2014
- Penalty
- Initial $1,360 · Current $952 Reduced
General-duty citation text
29 CFR 1910.304(b)(3)(ii)(A): All 125-volt, single-phase, 15-, 20-, and 30-ampere receptacle outlets that are not part of the permanent wiring of the building or structure and that are in use by personnel shall have ground-fault circuit-interrupter protection for personnel. Note 1 to paragraph (b)(3)(ii)(A) of this section: A cord connector on an extension cord set is considered to be a receptacle outlet if the cord set is used for temporary electric power. Note 2 to paragraph (b)(3)(ii)(A) of this section: Cord sets and devices incorporating the required ground-fault circuit-interrupter that are connected to the receptacle closest to the source of power are acceptable forms of protection. a.) Rapid Deployable Systems, Inc., Shop Area: On or about 12/09/13, the employer had three extension cords supplying power to an air compressor and a grinder that were not GFCI protected, creating a contact with electrical current hazard.
Recent events (2)
- · I (S) $952
- · Z (S) $1360
1910.304 G05
- Issued
- Jan 2, 2014
- Penalty
- Initial $1,360 · Current $952 Reduced
General-duty citation text
29 CFR 1910.304(g)(5): Grounding path. The path to ground from circuits, equipment, and enclosures shall be permanent, continuous, and effective. a.) Rapid Deployable Systems, Inc., Shop Area: On or about 12/09/13, the Dewalt 4.5 gallon air compressor that employees were using had a missing ground prong, creating a contact with live electrical hazard.
Recent events (2)
- · I (S) $952
- · Z (S) $1360
1910.303 B02
- Issued
- Jan 2, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Installation and use. Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling. a.) Rapid Deployable Systems, Inc., Shop Area: On or about 12/09/13, the metal duplex outlet supplying power to extension cords that were powering a portable air compressor and grinder was not installed and used in accordance with instructions included in the listing or labeling, in that it was not mounted.
Recent events (2)
- · I (O) $0
- · Z (O) $0
More inspections at Rapid Deployable Systems, INC.
View Rapid Deployable Systems, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 336611)
More inspections in VA
Source