2,004,209Inspections Most recent open 2026-07-13 Last loaded 2026-07-17
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Inspection: SUN TECH INDUSTRIES, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of SUN TECH INDUSTRIES, INC. in 41958 HWY 2, RAVENNA, NE 68869 (NAICS 326199). OSHA activity number 339546434.

Watch SUN Tech Industries, INC. — free Get an email when a new federal OSHA severe-injury report for SUN Tech Industries, INC. is published. One employer, no account, unsubscribe in one click.
Site address
41958 HWY 2
City
RAVENNA
State
NE
ZIP
68869
Mailing
41958 HWY 2, RAVENNA, NE 68869
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
326199
Employees
16
Ownership type
A

3 citations on file for this inspection.

1910.147 C04 II

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $1700.00 · Current $1500.00 Reduced
29 CFR 1910.147(c)(4)(ii): The specific procedures for the lockout/tagout of equipment at the facility is not clear and does not specifically outline the scope, purpose, authorization, rules, and techniques to be utilized for the control of hazardous energy, and the means to enforce compliance.     Job site located at 41958 Hwy 2, Ravenna, NE 68869-The employer's specific lockout/tagout procedures for the equipment and machines at the facility are not specific enough.  The procedures in place are to generic and do not name the specific piece of machinery, the type of hazardous energy to be isolated and how and where to go to actually isolate the energy.
Recent events (2)
  • — I (S) $1500
  • — Z (S) $1700

1910.147 C06 I

Deleted Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $1700.00 · Current $0.00 Reduced
29 CFR 1910.147(c)(6)(i): The employer shall conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirements of this standard are being followed.  Job site located at 41958 Hwy 2, Ravenna, NE 68869-The employer is failing to conduct annual inspection of the energy control procedure to ensure that the procedure and the requirements of this standard are being followed by employees at the facility.
Recent events (2)
  • — I (S) $0
  • — Z (S) $1700

1910.304 G05

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $1700.00 · Current $1500.00 Reduced
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective.    Job site located atr 41958 Hwy 2, Ravenna, NE 68869-The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective.  The employer had an industrial fan that was used in the facility for cooling purposes in the summer months that had the ground prong removed. The fan was plugged in and unplugged by employees at the facility.  The fan was located at the work area of Ms. Linsey Simmons the day of the inspection.  The employer stated that the fans are moved around and there were several employees who could have plugged-in or unplugged the industrial fan.
Recent events (2)
  • — I (S) $1500
  • — Z (S) $1700

View SUN TECH INDUSTRIES, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339546434.