Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ACF INDUSTRIES, LLC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of ACF INDUSTRIES, LLC in 417 N ARCH STREET, MILTON, PA 17847 (NAICS 336510). OSHA activity number 339552937.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch ACF Industries, LLC — free Get an email when a new federal OSHA severe-injury report for ACF Industries, LLC is published. One employer, no account, unsubscribe in one click.
Establishment
ACF INDUSTRIES, LLC
Site address
417 N ARCH STREET
City
MILTON
State
PA
ZIP
17847
Mailing
417 N ARCH STREET, MILTON, PA 17847
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
336510
Employees
325
Ownership type
A

3 citations on file for this inspection.

1910.110 B08 XI

Deleted Serious Gravity 5 2 instances 1 exposed
Issued
Mar 31, 2014
Abate by
May 15, 2014
Penalty
Initial $4,250 · Current $0 Reduced
29 CFR 1910.110(b)(8)(xi):  Buried piping outside buildings was not protected against corrosion and physical damage:  a) Outside Boiler and Paint Shops: Two underground propane lines (1 inch and 3 inch), used to supply propane for cutting torches and heating, leaked creating an explosion and fire hazard, on or about January 13, 2014.  Abatement Certification Required.
Recent events (2)
  • — I (S) $0
  • — Z (S) $4250

1910.110 B09 VII B

Serious Gravity 5 3 instances 1 exposed
Issued
Mar 31, 2014
Abate by
May 15, 2014
Penalty
Initial $0 · Current $3,187
29 CFR 1910.110(b)(9)(vii)(b): The propane hoses extended from one room to another, passed through walls, partitions, ceilings, or floors and was concealed from view or used in a concealed location:    a) Building 104 Boiler shop: Propane hoses, used to supply fuel to portable heaters and cutting torches, were routed through wall partitions, concealed from view and subject to physical damage, as observed on or about February 11, 2014.    Abatement Certification Required.
Recent events (2)
  • — I (S) $3187
  • — Z (S) $0

1910.110 B09 I

Serious Gravity 5 1 instance 1 exposed
Issued
Mar 31, 2014
Abate by
May 15, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.110(b)(9)(i): Hose was not fabricated of materials that were resistant to the action of LP-Gas in the liquid and vapor phases:  a) Building 104 Boiler Shop: Goodyear 1/4 inch Gemini Grade R Acetylene Only standard duty hose was used to supply propane to cutting torches and portable heaters, as observed on or about February 11, 2014.  Abatement Certification Required.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View ACF Industries, LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339552937.