MILTON, PA —
OSHA Inspection: ACF INDUSTRIES, LLC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of ACF INDUSTRIES, LLC in 417 N ARCH STREET, MILTON, PA 17847 (NAICS 336510). OSHA activity number 339552937.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ACF INDUSTRIES, LLC
- Site address
- 417 N ARCH STREET
- City
- MILTON
- State
- PA
- ZIP
- 17847
- Mailing
- 417 N ARCH STREET, MILTON, PA 17847
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 336510
- Employees
- 325
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.110 B08 XI
- Issued
- Mar 31, 2014
- Abate by
- May 15, 2014
- Penalty
- Initial $4,250 · Current $0 Reduced
General-duty citation text
29 CFR 1910.110(b)(8)(xi): Buried piping outside buildings was not protected against corrosion and physical damage: a) Outside Boiler and Paint Shops: Two underground propane lines (1 inch and 3 inch), used to supply propane for cutting torches and heating, leaked creating an explosion and fire hazard, on or about January 13, 2014. Abatement Certification Required.
Recent events (2)
- — I (S) $0
- — Z (S) $4250
1910.110 B09 VII B
- Issued
- Mar 31, 2014
- Abate by
- May 15, 2014
- Penalty
- Initial $0 · Current $3,187
General-duty citation text
29 CFR 1910.110(b)(9)(vii)(b): The propane hoses extended from one room to another, passed through walls, partitions, ceilings, or floors and was concealed from view or used in a concealed location: a) Building 104 Boiler shop: Propane hoses, used to supply fuel to portable heaters and cutting torches, were routed through wall partitions, concealed from view and subject to physical damage, as observed on or about February 11, 2014. Abatement Certification Required.
Recent events (2)
- — I (S) $3187
- — Z (S) $0
1910.110 B09 I
- Issued
- Mar 31, 2014
- Abate by
- May 15, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.110(b)(9)(i): Hose was not fabricated of materials that were resistant to the action of LP-Gas in the liquid and vapor phases: a) Building 104 Boiler Shop: Goodyear 1/4 inch Gemini Grade R Acetylene Only standard duty hose was used to supply propane to cutting torches and portable heaters, as observed on or about February 11, 2014. Abatement Certification Required.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections at ACF Industries, LLC
View ACF Industries, LLC's full OSHA safety record →
More inspections in this industry (NAICS 336510)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339552937.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.