OSHA Inspection: MASSACHUSETTS INSTITUTE OF TECHNOLOGY

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of MASSACHUSETTS INSTITUTE OF TECHNOLOGY in 105 MASSACHUSETTS AVENUE, CAMBRIDGE, MA 02139 (NAICS 611310). OSHA activity number 339592719.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Massachusetts Institute of Technology — free Get an email when a new federal OSHA severe-injury report for Massachusetts Institute of Technology is published. One employer, no account, unsubscribe in one click.
Site address
105 MASSACHUSETTS AVENUE
City
CAMBRIDGE
State
MA
ZIP
02139
Mailing
77 MASSACHUSETTS AVENUE EHS OFFICE N52-496, CAMBRIDGE, MA 02139
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
611310
Employees
19000
Ownership type
A

4 citations on file for this inspection.

1910.132 D01

Other-than-serious 1 instance 35 exposed
Issued
Jun 13, 2014
Abate by
Jul 31, 2014
Penalty
Initial $3,000 · Current $1,000 Reduced
29 CFR 1910.132(d)(1): The employer did not assess the workplace to determine if hazards are present, or are likely to be present, which necessitate the use of personal protective equipment (PPE):    Location: Building 13, mechanical room exhaust fans      On or about 2/18/14, the employer did not perform a hazard assessment related to hazardous fumes generated in the mechanical rooms from the exhaust fans drain ports left open that exhaust the building's lab hoods.  The hazard assessment would determine if implementing measures such as, but not limited to, mechanical ventilation/ engineering controls, respiratory protection, administrative controls, or other personal protective equipment is required.
Recent events (2)
  • — I (O) $1000
  • — Z (S) $3000

1910.212 A01

Serious Gravity 5 4 instances 2 exposed
Issued
Jun 13, 2014
Abate by
Jul 31, 2014
Penalty
Initial $5,000 · Current $2,500 Reduced
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks:    Location: Building 13    Instance #1: Mechanical room #13-5047 - On or about 2/18/14, the employer did not ensure that the guarding device was replaced on exhaust fan motor #701797 to protect employees from in-going nip-points of the rotating shaft, pulleys, and belt.      Instance #2 through #4: Mechanical room #13-5023 - On or about 3/28/14, the employer did not adequately secure the guarding device on exhaust fan motors #717330, 701802, and 701598 to protect employees from in-going nip-points of the rotating shaft, pulleys, and belt.
Recent events (2)
  • — I (S) $2500
  • — Z (S) $5000

1910.303 B07 I

Serious Gravity 5 4 instances 4 exposed
Issued
Jun 13, 2014
Abate by
Jul 31, 2014
Penalty
Initial $5,000 · Current $2,000 Reduced
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment.    Location: Building 13, mechanical rooms    On or about 2/18/14, faceplates and/or cover plates were missing, exposing employees to electrical shock and fire hazards in the following but not limited to areas;      Instance 1: Mechanical room #13-5071 - 120-volt light switch faceplate missing,  Instance 2: Mechanical room #13-5071 - a cover plate was missing on the conduit box for exhaust hood #701783,  Instance 3: Mechanical room #13-4047 - a cover plate was missing on the conduit box for exhaust hood #701798,  Instance 4: Mechanical room #13-5023 - a cover plate was missing on the conduit box for exhaust hood #701811.
Recent events (2)
  • — I (S) $2000
  • — Z (S) $5000

1910.305 B01 II

Serious Gravity 5 1 instance 2 exposed
Issued
Jun 13, 2014
Abate by
Jul 31, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:  Location:  Building 13, mechanical room #5023    On or about 2/18/14, the 480-volt electrical cabinet had openings that were not effectively closed as required exposing employees who perform maintenance in the mechanical room to electrical shock hazards and fire hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0