Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: TLD ACE CORPORATION

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of TLD ACE CORPORATION in 805 BLOOMFIELD AVENUE, WINDSOR, CT 06095 (NAICS 336413). OSHA activity number 339593964.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch TLD ACE Corporation — free Get an email when a new federal OSHA severe-injury report for TLD ACE Corporation is published. One employer, no account, unsubscribe in one click.
Establishment
TLD ACE CORPORATION
Site address
805 BLOOMFIELD AVENUE
City
WINDSOR
State
CT
ZIP
06095
Mailing
805 BLOOMFIELD AVENUE, WINDSOR, CT 06095
Inspection type
Complaint (B)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
336413
Employees
200
Ownership type
A

21 citations on file for this inspection.

5(a)(1)

Serious Gravity 5 1 instance 3 exposed
Issued
Jun 27, 2014
Abate by
Aug 14, 2014
Penalty
Initial $4,951 · Current $3,218 Reduced
OSH ACT of 1970 Section (5)(a)(1): Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which was free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to fall hazards:    Roof:  On, or about, February 20, 2014, an extension ladder that was provided for access to and egress from the roof for snow removal operations was not extended approximately three feet above the roof surface.
Recent events (2)
  • — I (S) $3218.05
  • — Z (S) $4951

1910.36 G02

Serious Gravity 5 1 instance 1 exposed
Issued
Jun 27, 2014
Abate by
Feb 14, 2015
Penalty
Initial $4,951 · Current $3,218 Reduced
29 CFR 1910.36(g)(2): Exit access(es) were not at least 28 inches (71.1 cm) wide at all points:       Main Electrical Room:  On, or about, February 24, 2014, the large Square D transformer was installed in the path of egress from the far side of the electrical room.  The transformer was located less than 28 inches from the backside of the breakroom wall.
Recent events (2)
  • — I (S) $3218
  • — Z (S) $4951

1910.303 G01 I A

Serious Gravity 5 3 instances 1 exposed
Issued
Jun 27, 2014
Abate by
Feb 14, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(i)(A): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the depth of the working space in the direction of access to live parts (as measured from the live parts where they were exposed or from the enclosure front or opening whwere they were enclosed) was less than indicated in Table S-1 of Subpart S of Part 1910:    A.     Main Electrical Room:  On, or about, February 24, 2014, the following electrical enclosures were not provided with sufficient working space (depth):    1.      The Square D main service entrance enclosure was measured to be 29 inches from the break room wall.  The required distance was 42 inches.     2.      GE sub-panel that energized additional receptacles in the break room was measured to be 23 inches from the transformer.  The required distance was 36 inches.    B.     Building 808, Test Facility, Bay 4:  On, or about, February 27, 2014, a LCU test bank was located 30 inches from the face of the Cutler-Hammer Power Line Switchboard.  The required distance was 42 inches.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 G01 I B

Serious Gravity 5 1 instance 1 exposed
Issued
Jun 27, 2014
Abate by
Feb 14, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(i)(B): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the width of the working space in front of electrical equipment was less than the width of the equipment or 762 mm (30 inches), whichever was greater:      Main Electrical Room:  On, or about, February 24, 2014, the GE panel board/circuit breaker panel that energized general wiring in the area was not provided with sufficient working space (width) in that it was located between the wall and raceway enclosure/transformer.  The required width was 30 inches.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.106 E09 III

Serious Gravity 5 1 instance 12 exposed
Issued
Jun 27, 2014
Abate by
Aug 14, 2014
Penalty
Initial $3,960 · Current $2,574 Reduced
29 CFR 1910.106(e)(9)(iii): Combustible waste material and residues in a building or unit operating area were not kept to a minimum, stored in covered metal receptacles and disposed of daily:    Air Conditioning Assembly Department:  On, or about, February 24, 2014, paper towels that had been used with DX440 solvent, a Category 3 flammable liquid, were disposed of into open, plastic trash receptacles.
Recent events (2)
  • — I (S) $2574
  • — Z (S) $3960

1910.107 B05 IV

Serious Gravity 5 1 instance 10 exposed
Issued
Jun 27, 2014
Abate by
Feb 14, 2015
Penalty
Initial $4,951 · Current $3,218 Reduced
29 CFR 1910.107(b)(5)(iv): Space within the spray booth on the downstream and upstream sides of filters was not protected with approved automatic sprinklers:    Small Spray Booth:  On, or about, February 27, 2014, the small "touch-up" spray booth was not provided with sprinklers.  Rustoleum paint, a Category 1 flammable aerosol, was applied to components in the booth.
Recent events (2)
  • — I (S) $3218.15
  • — Z (S) $4951

1910.107 C09 I

Serious Gravity 10 1 instance 2 exposed
Issued
Jun 27, 2014
Abate by
Aug 14, 2014
Penalty
Initial $6,930 · Current $4,504 Reduced
29 CFR 1910.107(c)(9)(i): All metal parts of spray booths, exhaust ducts, and piping systems conveying flammable liquids or liquids with a flashpoint greater than 199.4 °F (93 °C) or aerated solids shall be properly electrically grounded in an effective and permanent manner.    Large Spray Booth:  On, or about, February 24, 2014, the DeVilbiss HVLP spraying gun used to apply flammable paint to unit enclosures was not grounded.  Continuity could not be found between the spray gun and building structures.
Recent events (2)
  • — I (S) $4504
  • — Z (S) $6930

1910.110 C05 VII A

Serious Gravity 5 2 instances 25 exposed
Issued
Jun 27, 2014
Abate by
Aug 14, 2014
Penalty
Initial $3,960 · Current $2,574 Reduced
29 CFR 1910.110(c)(5)(vii)(a): Containers were used in industrial occupancies with essentially noncombustible contents where portable equipment for space heating is essential but where a permanent heating installation was practical:     Large Paint Booth:  On, or about, February 27, 2014, two Thermoheat salamander heaters were used to heat units to be painted.  The salamanders were run using propane cylinders.   A permanent heating installation could have been installed, natural gas piping ran directly over the area where the salamanders were normally positioned during use.
Recent events (2)
  • — I (S) $2574
  • — Z (S) $3960

1910.132 A

Serious Gravity 10 1 instance 3 exposed
Issued
Jun 27, 2014
Abate by
Aug 14, 2014
Penalty
Initial $6,930 · Current $4,505 Reduced
29 CFR 1910.132(a): Protective equipment was not used when necessary whenever hazards capable of causing injury and impairment were encountered:      Roof:  On, or about, February 20, 2014, employees were performing snow removal operations on the roof of the building, including work near the edge of the roof and above an electrical substation.  Fall protection such as guardrails or personal fall arrest/restraint systems were not provided.
Recent events (2)
  • — I (S) $4504.5
  • — Z (S) $6930

1910.335 B02

Serious Gravity 10 1 instance 3 exposed
Issued
Jun 27, 2014
Abate by
Aug 14, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.335(b)(2): Barricades were not used in conjunction with safety signs where it was necessary to prevent or limit employee access to work areas in which employees were exposed to uninsulated energized conductors or circuit parts:  Roof:  On, or about, February 20, 2014, employees were performing snow removal operations on the roof of the building, including work near the edge of the roof above an electrical substation.  Barricades had not been provided to prevent employee access to areas of the roof where they could have fallen into the electrical substation.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.178 A04

Serious Gravity 5 1 instance 3 exposed
Issued
Jun 27, 2014
Abate by
Aug 14, 2014
Penalty
Initial $3,960 · Current $2,574 Reduced
29 CFR 1910.178(a)(4): When modifications were made to powered industrial trucks that could affect the capacity or operation of the truck, the capacity, operation, and maintenance instruction plates, tags or decals of the powered industrial truck were not changed accordingly:    Yard:  On, or about, February 27, 2014, the capacity plate provided on the Clark forktruck, serial number Y015-28-4331, was calculated for four foot long forks.  The truck was provided with six foot long forks.
Recent events (2)
  • — I (S) $2574
  • — Z (S) $3960

1910.213 B03

Serious Gravity 5 1 instance 1 exposed
Issued
Jun 27, 2014
Abate by
Aug 14, 2014
Penalty
Initial $3,960 · Current $2,574 Reduced
29 CFR 1910.213(b)(3): Provisions were not made to prevent woodworking machine(s) from automatically restarting upon restoration of power after power failure:     Materials Warehouse:  On, or about, February 24, 2014, the Skil table saw was not provided with a drop-out or other effective means to prevent the saw from restarting after a power outage.
Recent events (2)
  • — I (S) $2574
  • — Z (S) $3960

1910.303 B02

Serious Gravity 5 3 instances 8 exposed
Issued
Jun 27, 2014
Abate by
Aug 14, 2014
Penalty
Initial $4,951 · Current $3,218 Reduced
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:    A.  Materials Warehouse, Receiving Desk:  On, or about, February 24, 2014, three relocatable power taps were connected in series to energize computers, computer peripherals and a copy machine.    B.  Ground Power Unit Department:  On, or about, February 24, 2014, the Red Devil paint mixer provided for use with the AUE 300 Performance Enamel paint mixture was not designed to mix flammable materials with a low flash point.  The paint mixture components were Category 2 and Category 3 flammable liquids with flashpoints between 7 degrees, F and 99 degrees, F.    C.  Janitor's Closet:  On, or about, February 24, 2014, nonmetallic sheathed cable (e.g., romex) was run through the masonry block wall from a GE panelboard into an office area.  The cable was not protected against abrasions.
Recent events (2)
  • — I (S) $3218.15
  • — Z (S) $4951

1910.303 B07 I

Deleted Serious Gravity 5 1 instance 1 exposed
Issued
Jun 27, 2014
Penalty
Initial $3,960 · Current $0 Reduced
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment:  Air Conditioning Assembly Department:  On, or about, February 24, 2014, openings were left in the front of the Square D I-Line panel that was provided for lighting circuits.
Recent events (2)
  • — I (S) $0
  • — Z (S) $3960

1910.305 G01 IV A

Deleted Serious Gravity 5 1 instance 2 exposed
Issued
Jun 27, 2014
Abate by
Aug 14, 2014
Penalty
Initial $3,960 · Current $0 Reduced
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  Materials Warehouse:  On, or about, February 24, 2014, a DeWalt chop saw, Model DW713, was energized through an extension cord.
Recent events (2)
  • — I (S) $0
  • — Z (S) $3960

1910.305 G01 IV D

Serious Gravity 5 4 instances 10 exposed
Issued
Jun 27, 2014
Abate by
Aug 14, 2014
Penalty
Initial $0 · Current $2,574
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords and cables were used where attached to building surfaces:    Electrical Department:  On, or about, February 24, 2014, the following flexible cords were attached to building surfaces:    1.  A duplex pendant box used to energize a relocatable power tape which in turn energized a DeWalt battery charger.      2.  The flexible cord provided on the relocatable power tap used to energize a computer system used to access assembly procedures was attached to wall mounted armored cable with plastic ties.      3.  A drop cord with a single receptacle provided for use at a worktable was attached to electrical conduit.      4.  A drop cord with a knockout box provided for use at a worktable was attached to electrical conduit.
Recent events (2)
  • — I (S) $2574
  • — Z (S) $0

1910.332 B01

Serious 1 instance 4 exposed
Issued
Jun 27, 2014
Abate by
Oct 1, 2014
Penalty
Initial $4,951 · Current $3,218 Reduced
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments:     Building 808, Test Facility:  Employees who performed electrical testing on assembled ground support units had not been provided with Electrical Safety Related Work Practices training.
Recent events (2)
  • — I (S) $3218.15
  • — Z (S) $4951

1910.335 A01 I

Serious Gravity 5 1 instance 4 exposed
Issued
Jun 27, 2014
Abate by
Oct 1, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed:     Building 808, Test Facility:  Employees who performed electrical testing on assembled ground support units were not provided with appropriate personal protective equipment such as, but not limited to, fire resistive clothing, voltage rated gloves, face shields, balaclavas and hearing protection.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.107 B09

Other-than-serious 1 instance 10 exposed
Issued
Jun 27, 2014
Abate by
Aug 14, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.107(b)(9): A clear space of not less than 3 feet on all sides was not kept free from storage or combustible construction:  Small Spray Booth:  On, or about, February 27, 2014, items such as a large fan and flammable storage cabinet were stored on the sides of the small "touch-up" spray booth.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.178 P01

Other-than-serious 1 instance 1 exposed
Issued
Jun 27, 2014
Abate by
Aug 14, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.178(p)(1): Powered industrial truck(s) found to be in need of repair, defective, or in any way unsafe had not been  taken out of service until restored to safe operating condition:   Plant:  On, or about, February 20, 2014, the weather cover provided on the CAT Model GC70K sit down forktruck, serial number AT89B00071, was solid and did not allow the operator to see through the overhead guard.  The forktruck was used to lift a snow blower onto the roof for snow removal operations.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.1200 E01 II

Other-than-serious 1 instance 200 exposed
Issued
Jun 27, 2014
Abate by
Aug 14, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.1200(e)(1)(ii): The written hazard communication program did not include the methods the employer would use to inform employees of the hazards associated with chemicals contained in unlabeled pipes in their work areas:   Plant-wide:  On, or about, February 27, 2014, the company's written Hazard Communication Program did not include how employees would be informed of the hazards presented by chemicals in unlabeled pipes.  Abatement Note:  Labeling the pipes may abate the hazard.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View TLD ACE Corporation's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339593964.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.