Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,191,473Inspections Most recent open 2026-07-28 Last loaded 2026-07-31

OSHA Inspection: GOLD COUNTRY CASINO & HOTEL

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of GOLD COUNTRY CASINO & HOTEL in 4020 OLIVE HIGHWAY, OROVILLE, CA 95966 (NAICS 713290). OSHA activity number 339609539.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Gold Country Casino & Hotel — free Get an email when a new federal OSHA severe-injury report for Gold Country Casino & Hotel is published. One employer, no account, unsubscribe in one click.
Site address
4020 OLIVE HIGHWAY
City
OROVILLE
State
CA
ZIP
95966
Mailing
5 TYME WAY, OROVILLE, CA 95966
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
713290
Employees
512
Ownership type
A

10 citations on file for this inspection.

1910.151 C

Serious Gravity 5 1 instance 1 exposed
Issued
Apr 24, 2014
Abate by
Jun 11, 2014
Penalty
Initial $4,000 · Current $2,600 Reduced
29 CFR 1910.151(c): Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use:     Central Plant: On March 3, 2014, and at times prior thereto, emergency drenching is not made immediately available when employees transfer corrosive Formula 3340 Bromide Salt, pH 13, into the water treatment operation.
Recent events (2)
  • — I (S) $2600
  • — Z (S) $4000

1910.213 B03

Serious Gravity 5 1 instance 1 exposed
Issued
Apr 24, 2014
Abate by
May 20, 2014
Penalty
Initial $4,000 · Current $2,600 Reduced
29 CFR 1910.213(b)(3): Provisions were not made to prevent woodworking machine(s) from automatically restarting upon restoration of power after power failure:    Temporary Carpenter Shop: On March 3, 2014, and at times prior thereto, the Ridgid Table Saw, model Ts24120, was not provided with anti-restart control.
Recent events (2)
  • — I (S) $2600
  • — Z (S) $4000

1910.303 B02

Serious Gravity 1 1 instance 1 exposed
Issued
Apr 24, 2014
Penalty
Initial $3,000 · Current $1,950 Reduced
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:     Temporary Carpenter's Shop: On March 3, 2014, and at times prior thereto, a four-plug non-class rated outlet box was installed on the ground next to the Ridgid Table Saw.
Recent events (2)
  • — I (S) $1950
  • — Z (S) $3000

1910.305 G01 IV A

Serious Gravity 1 1 instance 21 exposed
Issued
Apr 24, 2014
Penalty
Initial $3,000 · Current $1,950 Reduced
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:    Maintenance Workshop: On March 3, 2014, and at times prior thereto, employees used a microwave which was permanently energized by an orange extension cord.
Recent events (2)
  • — I (S) $1950
  • — Z (S) $3000

1910.307 C

Serious Gravity 5 2 instances 1 exposed
Issued
Apr 24, 2014
Abate by
May 20, 2014
Penalty
Initial $5,000 · Current $3,250 Reduced
29 CFR 1910.307(c): Equipment, wiring methods, and installations of equipment in hazardous (classified) locations were not intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location:     Temporary Carpenter Shop: On March 3, 2014, and at times prior thereto, Class II wood dust had accumulated inside ofelectrical equipment that was not intrinsically safe or approved for Class II Division E/F/G locations:     A. Employees used a Ridgid Wet/Dry shop vacuum cleaner for cleaning up combustible wood dust on and around the Ridgid table saw.     B. A four-plug outlet which energized the Ridgid Table Saw was installed on the floor next to the table saw and saw dust had accumulated inside the outlet box where the live wiring was housed.
Recent events (2)
  • — I (S) $3250
  • — Z (S) $5000

1910.333 A01

Serious Gravity 5 1 instance 1 exposed
Issued
Apr 24, 2014
Abate by
May 20, 2014
Penalty
Initial $4,000 · Current $2,600 Reduced
29 CFR 1910.333(a)(1): Live parts to which an employee was exposed were not de-energized before the employee worked on or near them:    Establishment: On March 4, 2014, and at times prior thereto, employees performed trouble-shooting and live electrical work up to 277 volts on electrical equipment like ballasts and breakers.
Recent events (2)
  • — I (S) $2600
  • — Z (S) $4000

1910.335 A01 I

Serious Gravity 5 1 instance 1 exposed
Issued
Apr 24, 2014
Abate by
May 20, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed:  Establishment: On March 3, 2014, and at times prior thereto, adequate electrical personal protective equipment such as, but not limited to, fire resistant clothing, volt rated gloves, and hard hats, were not provided to employees who worked performed trouble-shooting and live electrical work up to 277 volts.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.22 D01

Other-than-serious 1 instance 21 exposed
Issued
Apr 24, 2014
Abate by
May 20, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.22(d)(1): On every building or other structure, or part thereof, used for mercantile, business, industrial or storage purposes, the loads approved by the building official were not marked on plates of approved design and securely affixed in a conspicuous place in each space to which they relate:  Maintenance Shop: On March 3, 2014, and at times prior thereto, the storage mezzanine above the restroom and maintenance offices was not rated for load capacity.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.37 B02

Other-than-serious 1 instance 3 exposed
Issued
Apr 24, 2014
Abate by
Apr 30, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit":  Main Electrical Closet: On March 3, 2014, and at times prior thereto, there was no EXIT signage provided for the single west facing door which led directly outside.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.147 C01

Other-than-serious 2 instances 21 exposed
Issued
Apr 24, 2014
Abate by
May 20, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.147(c)(1): The employer did not establish a program consisting of an energy control procedure, employee training and periodic inspections to ensure that before any employee performed any servicing or maintenance on a machine or equipment where the unexpected energizing, startup or release of stored energy could occur and cause injury, the machine or equipment shall be isolated from the energy source and rendered inoperative:  Establishment: On March 3, 2014, and at times prior thereto, the employer did not establishment the required elements of an energy control procedure where employees were performing routine maintenance and service on several different types of equipment, including multi-energy source equipment:  A. Machine Specific Procedures were not in place for multi-energy source equipment like pumps.  B. Training was not provided after an employee had recieved initial training upon hire.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Gold Country Casino & Hotel's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339609539.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.