Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,198,201Inspections Most recent open 2026-08-31 Last loaded 2026-09-03

OSHA Inspection: ORION DRILLING COMPANY, LLC RIG #2

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of ORION DRILLING COMPANY, LLC RIG #2 in S. OF CR 405 ON FM 1680 MAKERS 1-H WELL, FLATONIA, TX 78941 (NAICS 213111). OSHA activity number 339610388.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Orion Drilling Company, LLC RIG #2 for free Get an email when a new federal OSHA severe-injury report for Orion Drilling Company, LLC RIG #2 is published. One employer, no account, unsubscribe in one click.
Site address
S. OF CR 405 ON FM 1680 MAKERS 1-H WELL
City
FLATONIA
State
TX
ZIP
78941
Mailing
674 FLATO RD, CORPUS CHRISTI, TX 78405
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
213111
Employees
13
Ownership type
Private (A)

4 citations on file for this inspection.

1910.303 B01 II

Other-than-serious 1 instance 4 exposed
Issued
Apr 1, 2014
Abate by
Apr 7, 2014
Penalty
Initial $3,300 · Current $2,000 Reduced
29 CFR 1910.303(b)(1)(ii): Electrical equipment was not free from recognized hazards, based on the mechanical strength and durability, including, for parts designed to enclose and protect other equipment, the adequacy of the protection thus provided:    On or about February 28, 2014 the cover of the Square D breaker panel providing power to the Rig manager's trailer had a broken door hinge.  The breaker panel was located on the side of Rig manager's trailer, found on the Makers 1-H well site.
Recent events (2)
  • · I (O) $2000
  • · Z (S) $3300

1910.303 B07

Serious Gravity 5 1 instance 4 exposed
Issued
Apr 1, 2014
Abate by
Apr 7, 2014
Penalty
Initial $5,500 · Current $4,400 Reduced
29 CFR 1910.303(b)(7):  Electrical equipment was not installed in a neat and workmanlike manner:    On or about February 28, 2014 a 75 KVA transformer had 7 screws missing including all the screws at the bottom of the front cover that kept the cover from falling down on live connections.  One half of the Weather guard was also missing.  The transformer was providing power for the Rig manager's trailer and other trailers, located on the edge of the drilling site, found on the Makers 1-H well.
Recent events (2)
  • · I (S) $4400
  • · Z (S) $5500

1910.305 E01

Serious Gravity 5 1 instance 4 exposed
Issued
Apr 1, 2014
Abate by
Apr 7, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.305(e)(1): Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures were not weatherproof in wet locations:  On or about February 28, 2014 the 75 KVA transformer providing power for the rig trailers had one side of the "weather shield" missing.  This condition created an electrical hazard to employee in the event rain water entered the transformer.  The transformer was located on the outside of the rig manager's trailer, found on the Makers 1-H well site.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.305 G02 III

Other-than-serious 1 instance 4 exposed
Issued
Apr 1, 2014
Abate by
Apr 7, 2014
Penalty
Initial $5,500 · Current $3,000 Reduced
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws:    On or about February 28, 2014, the power cord energizing the changing trailer did not have an effective strain relief device, the cord was located on the side of the transformer, found on the outside of the rig manager's trailer.
Recent events (2)
  • · I (O) $3000
  • · Z (S) $5500

View Orion Drilling Company, LLC RIG #2's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 339610388.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.