FLATONIA, TX ·
OSHA Inspection: ORION DRILLING COMPANY, LLC RIG #2
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of ORION DRILLING COMPANY, LLC RIG #2 in S. OF CR 405 ON FM 1680 MAKERS 1-H WELL, FLATONIA, TX 78941 (NAICS 213111). OSHA activity number 339610388.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ORION DRILLING COMPANY, LLC RIG #2
- Site address
- S. OF CR 405 ON FM 1680 MAKERS 1-H WELL
- City
- FLATONIA
- State
- TX
- ZIP
- 78941
- Mailing
- 674 FLATO RD, CORPUS CHRISTI, TX 78405
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 213111
- Employees
- 13
- Ownership type
- Private (A)
Citations
4 citations on file for this inspection.
1910.303 B01 II
- Issued
- Apr 1, 2014
- Abate by
- Apr 7, 2014
- Penalty
- Initial $3,300 · Current $2,000 Reduced
General-duty citation text
29 CFR 1910.303(b)(1)(ii): Electrical equipment was not free from recognized hazards, based on the mechanical strength and durability, including, for parts designed to enclose and protect other equipment, the adequacy of the protection thus provided: On or about February 28, 2014 the cover of the Square D breaker panel providing power to the Rig manager's trailer had a broken door hinge. The breaker panel was located on the side of Rig manager's trailer, found on the Makers 1-H well site.
Recent events (2)
- · I (O) $2000
- · Z (S) $3300
1910.303 B07
- Issued
- Apr 1, 2014
- Abate by
- Apr 7, 2014
- Penalty
- Initial $5,500 · Current $4,400 Reduced
General-duty citation text
29 CFR 1910.303(b)(7): Electrical equipment was not installed in a neat and workmanlike manner: On or about February 28, 2014 a 75 KVA transformer had 7 screws missing including all the screws at the bottom of the front cover that kept the cover from falling down on live connections. One half of the Weather guard was also missing. The transformer was providing power for the Rig manager's trailer and other trailers, located on the edge of the drilling site, found on the Makers 1-H well.
Recent events (2)
- · I (S) $4400
- · Z (S) $5500
1910.305 E01
- Issued
- Apr 1, 2014
- Abate by
- Apr 7, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(e)(1): Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures were not weatherproof in wet locations: On or about February 28, 2014 the 75 KVA transformer providing power for the rig trailers had one side of the "weather shield" missing. This condition created an electrical hazard to employee in the event rain water entered the transformer. The transformer was located on the outside of the rig manager's trailer, found on the Makers 1-H well site.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1910.305 G02 III
- Issued
- Apr 1, 2014
- Abate by
- Apr 7, 2014
- Penalty
- Initial $5,500 · Current $3,000 Reduced
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws: On or about February 28, 2014, the power cord energizing the changing trailer did not have an effective strain relief device, the cord was located on the side of the transformer, found on the outside of the rig manager's trailer.
Recent events (2)
- · I (O) $3000
- · Z (S) $5500
More inspections at Orion Drilling Company, LLC RIG #2
View Orion Drilling Company, LLC RIG #2's full OSHA safety record →
More inspections in this industry (NAICS 213111)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 339610388.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.