Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,214Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: USDA-RURAL DEVELOPMENT

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of USDA-RURAL DEVELOPMENT in CALLE MUNOZ RIVERA #80, CAMUY, PR 00627 (NAICS 925120). OSHA activity number 339610883.

Watch Usda-Rural Development — free Get an email when a new federal OSHA severe-injury report for Usda-Rural Development is published. One employer, no account, unsubscribe in one click.
Site address
CALLE MUNOZ RIVERA #80
City
CAMUY
State
PR
ZIP
00627
Mailing
CALLE MUNOZ RIVERA #80, CAMUY, PR 00627
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
925120
Employees
5
Ownership type
D

9 citations on file for this inspection.

1910.303 B02

Serious Gravity 1 5 instances 5 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(b)(2): Installation and use. Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling:   a) On or about 03/05/14, at #80 Munoz Rivera Street, Camuy, PR, in the reception area, workstation #1, a relocatable power tap was not directly connected to a permanently installed branch circuit receptacle.   b) On or about 03/05/14, at #80 Munoz Rivera Street, Camuy, PR, in the reception area, workstation #2, an uninterruptible power supply was not connected to a permanently installed branch circuit receptacle.  c) On or about 03/05/14, at #80 Munoz Rivera Street, Camuy, PR, in the reception area, workstation #3, an uninterruptible power supply was not connected to a permanently installed branch circuit receptacle.  d) On or about 03/05/14, at #80 Munoz Rivera Street, Camuy, PR, in the office #1 area, a relocatable power tap was not directly connected to a permanently installed branch circuit receptacle.   e) On or about 03/05/14, at #80 Munoz Rivera Street, Camuy, PR, in the office #3 area, an uninterruptible power supply was not connected to a permanently installed branch circuit receptacle.   PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • — Z (S) $0

1910.303 F02

Serious Gravity 1 2 instances 5 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(f)(2): Services, feeders, and branch circuits. Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, shall be legibly marked to indicate its purpose, unless located and arranged so the purpose is evident:    a) On or about 03/05/14, at #80 Munoz Rivera Street, Camuy, PR,, in the office #3 area, the circuit breakers or fuses in the electrical panel were not identified or labeled to show the locations of the building whose circuits it protects.   b) On or about 03/05/14, at #80 Munoz Rivera Street, Camuy, PR,, in the south exit area, the circuit breakers or fuses in the electrical panel were not identified or labeled to show the locations of the building whose circuits it protects.    PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • — Z (S) $0

1910.305 B01 II

Serious Gravity 1 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(b)(1)(ii): Unused openings in cabinets, boxes, and fittings shall be effectively closed:  On or about 03/05/14, at #80 Munoz Rivera Street, Camuy, PR, in the office #3 area, openings in the electrical panel board were not closed.  PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • — Z (S) $0

1910.305 B02 I

Serious Gravity 1 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy:   On or about 03/05/14, at #80 Munoz Rivera Street, Camuy, PR, in the office #2 area, an electrical outlet box was not covered or closed.  PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • — Z (S) $0

1910.305 G01 IV A

Serious Gravity 1 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(g)(1)(iv)(A): Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, flexible cords and cables may not be used as a substitute for the fixed wiring of a structure:  a) On or about 03/05/14, at #80 Munoz Rivera Street, Camuy, PR, in the south exterior wall area, a flexible cord was used in lieu of permanent wiring.  b) On or about 03/05/14, at #80 Munoz Rivera Street, Camuy, PR, in the photocopy machine area, a flexible cord was used in lieu of permanent wiring.  PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • — Z (S) $0

1910.305 G01 IV B

Serious Gravity 1 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(g)(1)(iv)(B): Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, flexible cords and cables may not be used where run through holes in walls, ceilings, or floors:  a) On or about 03/05/14, at #80 Munoz Rivera Street, Camuy, PR, in the photocopy machine area, a flexible cord was run through a hole in a wall to service a relocatable power tap.  b) On or about 03/05/14, at #80 Munoz Rivera Street, Camuy, PR, in the south exterior wall area, a flexible cord was run through a hole in a wall to service an air conditioning unit.   PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • — Z (S) $0

1910.305 G02 III

Serious Gravity 1 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws:  On or about 03/05/14, at #80 Munoz Rivera Street, Camuy, PR, in the photocopy machine area, the outer insulation of the electrical cord was coming off due to the lack of strain relief.   PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • — Z (S) $0

1910.157 C01

Other-than-serious 2 instances 5 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.157(c)(1): The employer shall provide portable fire extinguishers and shall mount, locate and identify them so that they are readily accessible to employees without subjecting the employees to possible injury:  a) On or about 03/05/14, at #80 Munoz Rivera Street, Camuy, PR, in the LAN room area, a portable fire extinguisher was not mounted.  b) On or about 03/05/14, at #80 Munoz Rivera Street, Camuy, PR, in the break room area, a portable fire extinguisher was not mounted.  PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • — Z (O) $0

1910.157 E03

Other-than-serious 4 instances 5 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.157(e)(3): Portable fire extinguishers were not subjected to an annual maintenance check:  On or about 03/05/14, at #80 Munoz Rivera Street, Camuy, PR, throughout the facility, the portable fire extinguishers were not maintained annually.  PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • — Z (O) $0

View USDA-RURAL DEVELOPMENT's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339610883.