CAMUY, PR —
OSHA Inspection: USDA-RURAL DEVELOPMENT
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of USDA-RURAL DEVELOPMENT in CALLE MUNOZ RIVERA #80, CAMUY, PR 00627 (NAICS 925120). OSHA activity number 339610883.
Where did this inspection happen?
- Establishment
- USDA-RURAL DEVELOPMENT
- Site address
- CALLE MUNOZ RIVERA #80
- City
- CAMUY
- State
- PR
- ZIP
- 00627
- Mailing
- CALLE MUNOZ RIVERA #80, CAMUY, PR 00627
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 925120
- Employees
- 5
- Ownership type
- D
Citations
9 citations on file for this inspection.
1910.303 B02
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(b)(2): Installation and use. Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling: a) On or about 03/05/14, at #80 Munoz Rivera Street, Camuy, PR, in the reception area, workstation #1, a relocatable power tap was not directly connected to a permanently installed branch circuit receptacle. b) On or about 03/05/14, at #80 Munoz Rivera Street, Camuy, PR, in the reception area, workstation #2, an uninterruptible power supply was not connected to a permanently installed branch circuit receptacle. c) On or about 03/05/14, at #80 Munoz Rivera Street, Camuy, PR, in the reception area, workstation #3, an uninterruptible power supply was not connected to a permanently installed branch circuit receptacle. d) On or about 03/05/14, at #80 Munoz Rivera Street, Camuy, PR, in the office #1 area, a relocatable power tap was not directly connected to a permanently installed branch circuit receptacle. e) On or about 03/05/14, at #80 Munoz Rivera Street, Camuy, PR, in the office #3 area, an uninterruptible power supply was not connected to a permanently installed branch circuit receptacle. PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
- — Z (S) $0
1910.303 F02
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(f)(2): Services, feeders, and branch circuits. Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, shall be legibly marked to indicate its purpose, unless located and arranged so the purpose is evident: a) On or about 03/05/14, at #80 Munoz Rivera Street, Camuy, PR,, in the office #3 area, the circuit breakers or fuses in the electrical panel were not identified or labeled to show the locations of the building whose circuits it protects. b) On or about 03/05/14, at #80 Munoz Rivera Street, Camuy, PR,, in the south exit area, the circuit breakers or fuses in the electrical panel were not identified or labeled to show the locations of the building whose circuits it protects. PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
- — Z (S) $0
1910.305 B01 II
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in cabinets, boxes, and fittings shall be effectively closed: On or about 03/05/14, at #80 Munoz Rivera Street, Camuy, PR, in the office #3 area, openings in the electrical panel board were not closed. PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
- — Z (S) $0
1910.305 B02 I
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: On or about 03/05/14, at #80 Munoz Rivera Street, Camuy, PR, in the office #2 area, an electrical outlet box was not covered or closed. PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
- — Z (S) $0
1910.305 G01 IV A
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, flexible cords and cables may not be used as a substitute for the fixed wiring of a structure: a) On or about 03/05/14, at #80 Munoz Rivera Street, Camuy, PR, in the south exterior wall area, a flexible cord was used in lieu of permanent wiring. b) On or about 03/05/14, at #80 Munoz Rivera Street, Camuy, PR, in the photocopy machine area, a flexible cord was used in lieu of permanent wiring. PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
- — Z (S) $0
1910.305 G01 IV B
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(B): Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, flexible cords and cables may not be used where run through holes in walls, ceilings, or floors: a) On or about 03/05/14, at #80 Munoz Rivera Street, Camuy, PR, in the photocopy machine area, a flexible cord was run through a hole in a wall to service a relocatable power tap. b) On or about 03/05/14, at #80 Munoz Rivera Street, Camuy, PR, in the south exterior wall area, a flexible cord was run through a hole in a wall to service an air conditioning unit. PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
- — Z (S) $0
1910.305 G02 III
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws: On or about 03/05/14, at #80 Munoz Rivera Street, Camuy, PR, in the photocopy machine area, the outer insulation of the electrical cord was coming off due to the lack of strain relief. PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
- — Z (S) $0
1910.157 C01
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.157(c)(1): The employer shall provide portable fire extinguishers and shall mount, locate and identify them so that they are readily accessible to employees without subjecting the employees to possible injury: a) On or about 03/05/14, at #80 Munoz Rivera Street, Camuy, PR, in the LAN room area, a portable fire extinguisher was not mounted. b) On or about 03/05/14, at #80 Munoz Rivera Street, Camuy, PR, in the break room area, a portable fire extinguisher was not mounted. PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
- — Z (O) $0
1910.157 E03
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.157(e)(3): Portable fire extinguishers were not subjected to an annual maintenance check: On or about 03/05/14, at #80 Munoz Rivera Street, Camuy, PR, throughout the facility, the portable fire extinguishers were not maintained annually. PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
- — Z (O) $0
More inspections at USDA-RURAL DEVELOPMENT
LE MARS, IA—2025-02-04
USDA RURAL DEVELOPMENT
YAKIMA, WA—2024-10-07 00:00:00
USDA RURAL DEVELOPMENT
MOROVIS, PR—2022-12-15 00:00:00
USDA-RURAL DEVELOPMENT
NORWICH, CT—2022-03-16 00:00:00
USDA RURAL DEVELOPMENT
MOUNT VERNON, WA—2021-12-07 00:00:00
USDA RURAL DEVELOPMENT
View USDA-RURAL DEVELOPMENT's full OSHA safety record →
More inspections in this industry (NAICS 925120)
NEW YORK, NY—2026-07-09
U.S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT 8HDXX0061
HONOKAA, HI—2026-05-04
COUNTY OF HAWAII - DPR, AQUATICS SECTION
MANY FARMS, AZ—2026-04-06
DEPT OF HEALTH AND HUMAN SERVICES - INDIAN HEALTH SERVICE
COLUMBIA, MD—2026-03-25
HOWARD COUNTY GOVERNMENT
COLUMBIA, MD—2026-02-18
HOWARD COUNTY GOVERNMENT
More inspections in PR
SAN JUAN, PR—2026-07-16
U.S. DEPARTMENT OF AGRICULTURE-FOREST SERVICE
PONCE, PR—2026-07-15
CENTROS SOR ISOLINA FERRE INC
PONCE, PR—2026-07-15
FC CONSTRUCTION LLC
PONCE, PR—2026-07-15
HECTOR M. RIVERA
SAN JUAN, PR—2026-07-15
MUNICIPIO DE SAN JUAN
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339610883.