OSHA Inspection: M & W ALUMINUM PRODUCTS INC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of M & W ALUMINUM PRODUCTS INC in 321 WAVEL STREET, SYRACUSE, NY 13206 (NAICS 336370). OSHA activity number 339611923.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch M & W Aluminum Products INC for free Get an email when a new federal OSHA severe-injury report for M & W Aluminum Products INC is published. One employer, no account, unsubscribe in one click.
Site address
321 WAVEL STREET
City
SYRACUSE
State
NY
ZIP
13206
Mailing
321 WAVEL STREET, SYRACUSE, NY 13206
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
336370
Employees
14
Ownership type
Private (A)

5 citations on file for this inspection.

1910.212 A01

Serious Gravity 10 7 instances 7 exposed
Issued
Jul 7, 2014
Abate by
Aug 21, 2014
Penalty
Initial $2,800 · Current $1,960 Reduced
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks:    a) Right-side Polishing Area, on or about 3/5/2014: A Dayton Industrial Motor with unguarded rotating chuck was used by employees to polish and buff metal rods.    b) Left-side Polishing Area, on or about 3/5/2014: Le Blonde Lathe with unguarded rotating chuck was used by employees to polish and buff metal rods.    c) Back-side Cutting Area, on or about 4/3/2014: Two Jet Milling Machines were not provided with a guard over the rotating chuck.      d) Back-side Cutting Area, on or about 3/5/2014: Jet Band Saw with unused portion of the blade unguarded was used by employees for cutting metal.     e) Front-side CNC Area, on or about 3/5/2014: Jet Drill Press with unguarded rotating chuck was used by employees to drill and tap parts.       f) Front-side CNC Area, on or about 3/5/2014: Jet Lathe with unguarded rotating chuck was used by employees for tooling.     g) Front-side CNC Area, on or about 4/3/2014: Shop Fox Drill Press with unguarded rotating chuck was used by employees for chamfer parts.
Recent events (2)
  • · I (S) $1960
  • · Z (S) $2800

1910.305 B01 II

Other-than-serious 2 instances 3 exposed
Issued
Jul 7, 2014
Abate by
Jul 31, 2014
Penalty
Initial $1,600 · Current $0 Reduced
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:    a) Main Panel Area, on or about 3/5/2014: Metal Square D disconnect box used as main disconnect to a distribution panel had an unused opening not effectively closed on the lower right corner at the right side of the box.    b) Main Panel Area, on or about 3/5/2014: Metal Distribution panel used as branch circuit distribution panel had an unused opening not effectively closed on the upper right corner at the right side of the box.
Recent events (2)
  • · I (O) $0
  • · Z (S) $1600

1910.305 G01 III

Deleted Serious Gravity 5 2 instances 4 exposed
Issued
Jul 7, 2014
Abate by
Aug 21, 2014
Penalty
Initial $1,600 · Current $0 Reduced
29 CFR 1910.305(g)(1)(iii): Flexible cords and cables were used for purposes prohibited by subparagraphs (A) through (E) of this paragraph:   a) Front-side CNC Area, on or about 3/5/2014: A flexible extension cord was used as permanent wiring to power a Power Strip.  b) Back-side CNC Area, on or about 3/5/2014: A flexible extension cord was used as permanent wiring to power a Hydraulic Press.
Recent events (2)
  • · I (S) $0
  • · Z (S) $1600

1910.157 E03

Other-than-serious 2 instances 1 exposed
Issued
Jul 7, 2014
Abate by
Jul 31, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.157(e)(3): The annual maintenance record (Fire Extinguisher) was not retained for one year after the last entry or the life of the shell, whichever is less:  a) Back side of the Building, on or about 3/5/2014: Fire extinguisher maintenance record was not available upon request.   b) Front side of the Building, on or about 3/5/2014: Fire extinguisher maintenance record was not available upon request.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

1910.303 B02

Other-than-serious 1 instance 3 exposed
Issued
Jul 7, 2014
Abate by
Aug 21, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  a) Front-side CNC Area, on or about 4/3/2014: An office rated power strip was used to provide power to drill press and an impulse sealer, exposing employees to minor burns.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

View M & W Aluminum Products INC's full OSHA safety record →