BOSTON, MA ·
OSHA Inspection: CROWN ENERGY SERVICES, INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of CROWN ENERGY SERVICES, INC. in 111 HUNTINGTON AVENUE, BOSTON, MA 02199 (NAICS 238220). OSHA activity number 339633257.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- CROWN ENERGY SERVICES, INC.
- Site address
- 111 HUNTINGTON AVENUE
- City
- BOSTON
- State
- MA
- ZIP
- 02199
- Mailing
- 868 FOLSOM STREET, SAN FRANCISCO, CA 94107
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Union (A)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238220
- Employees
- 28
- Ownership type
- Private (A)
Citations
7 citations on file for this inspection.
1910.132 D01
- Issued
- Jul 10, 2014
- Abate by
- Aug 28, 2014
- Penalty
- Initial $7,000 · Current $7,000
General-duty citation text
29 CFR 1910.132(d)(1): The employer did not assess the workplace to determine if hazards are present, or are likely to be present, which necessitate the use of personal protective equipment (PPE): Prudential Center buildings: The employer did not conduct an arc flash hazard analysis as required by NFPA 70E to determine appropriate PPE for employees working on or near energized equipment and within the arc flash boundary.
Recent events (3)
- · F (S) $7000
- · C (S) $7000
- · Z (S) $7000
1910.335 A01 I
- Issued
- Jul 10, 2014
- Abate by
- Aug 28, 2014
- Penalty
- Initial $7,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed: Prudential Center buildings: The employer did not provide appropriate work uniforms to the electricians in that the uniform content of the shirts was 60 percent cotton and meltable fibers of 40 percent polyester. Additionally, some electricians were provided with short sleeved uniforms. The uniform pants provided were 100 percent cotton which does not provide protection from arc flash hazards.
Recent events (3)
- · F (S) $0
- · C (S) $7000
- · Z (S) $7000
1910.137 B02 VIII
- Issued
- Jul 10, 2014
- Abate by
- Aug 7, 2014
- Penalty
- Initial $2,550 · Current $400 Reduced
General-duty citation text
29 CFR 1910.137(b)(2)(viii): Electrical protective equipment was not subjected to periodic electrical tests in accordance with Tables I-5 and I-6: Prudential Center buildings: Salisbury rubber insulating gloves, Class 0, Type 1 rated to 1000V AC had not been tested since the manufacture date of March 2005.
Recent events (3)
- · F (O) $400
- · C (S) $2550
- · Z (S) $2550
1910.332 B01
- Issued
- Jul 10, 2014
- Abate by
- Aug 28, 2014
- Penalty
- Initial $7,000 · Current $7,000
General-duty citation text
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments: Prudential Center buildings: (a) Employees who perform electrical work and testing on energized electrical equipment and systems were not effectively trained in implementing electrical safety-related work practices for tasks such as changing lighting ballasts, removal and installation of overcurrent devices, and troubleshooting and repair of electrical equipment of up to 480 Volts. (b) Employees had not been effectively trained in the selection and use of electrical personal protective equipment such as uniform clothing selection, arc flash suits, head protection, and electrical rated gloves.
Recent events (3)
- · F (S) $7000
- · C (S) $7000
- · Z (S) $7000
1910.335 A01 IV
- Issued
- Jul 10, 2014
- Abate by
- Aug 28, 2014
- Penalty
- Initial $2,550 · Current $0 Reduced
General-duty citation text
29 CFR 1910.335(a)(1)(iv): Employees exposed to the danger of head injury from electric shock or burns due to contact with exposed energized parts did not wear nonconductive head protection: Prudential Center buildings: Employees working on or near energized electrical equipment of up to 480 volts did not wear hard hats.
Recent events (3)
- · F (S) $0
- · C (S) $2550
- · Z (S) $2550
1910.333 A01
- Issued
- Jul 10, 2014
- Abate by
- Aug 28, 2014
- Penalty
- Initial $7,000 · Current $7,000
General-duty citation text
29 CFR 1910.333(a)(1): Live parts to which an employee was exposed were not deenergized before the employee worked on or near them: (a) 111 Huntington Ave, Boston - 26th Floor: An employee was shocked and burned when contact was made with live parts while testing and changing a lighting ballast where the circuit had not been de-energized. (b) Prudential Center buildings: Employees were exposed to live electrical parts while performing tasks including but not limited to changing ballasts for 277V lighting fixtures and installing and replacing overcurrent devices in equipment of up to 480 volts where the circuits had not been deenergized.
Recent events (3)
- · F (S) $7000
- · C (S) $7000
- · Z (S) $7000
1910.333 B02 I
- Issued
- Jul 10, 2014
- Abate by
- Aug 28, 2014
- Penalty
- Initial $2,550 · Current $400 Reduced
General-duty citation text
29 CFR 1910.333(b)(2)(i): The employer did not maintain a written copy of the procedures outlined in paragraph (b)(2) of 29 CFR 1910.333 available for inspection by employees and by the Assistant Secretary of Labor and his or her authorized representatives: Prudential Center buildings: The company did not have written procedures for locking out and/or tagging de-energized electrical equipment.
Recent events (3)
- · F (O) $400
- · C (S) $2550
- · Z (S) $2550
More inspections at Crown Energy Services, INC.
View Crown Energy Services, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 238220)
More inspections in MA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 339633257.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.