Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,198,201Inspections Most recent open 2026-08-31 Last loaded 2026-09-03

OSHA Inspection: CROWN ENERGY SERVICES, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of CROWN ENERGY SERVICES, INC. in 111 HUNTINGTON AVENUE, BOSTON, MA 02199 (NAICS 238220). OSHA activity number 339633257.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Crown Energy Services, INC. for free Get an email when a new federal OSHA severe-injury report for Crown Energy Services, INC. is published. One employer, no account, unsubscribe in one click.
Site address
111 HUNTINGTON AVENUE
City
BOSTON
State
MA
ZIP
02199
Mailing
868 FOLSOM STREET, SAN FRANCISCO, CA 94107
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Union (A)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238220
Employees
28
Ownership type
Private (A)

7 citations on file for this inspection.

1910.132 D01

Serious Gravity 10 1 instance 3 exposed
Issued
Jul 10, 2014
Abate by
Aug 28, 2014
Penalty
Initial $7,000 · Current $7,000
29 CFR 1910.132(d)(1): The employer did not assess the workplace to determine if hazards are present, or are likely to be present, which necessitate the use of personal protective equipment (PPE):    Prudential Center buildings:  The employer did not conduct an arc flash hazard analysis as required by NFPA 70E to determine appropriate PPE for employees working on or near energized equipment and within the arc flash boundary.
Recent events (3)
  • · F (S) $7000
  • · C (S) $7000
  • · Z (S) $7000

1910.335 A01 I

Serious Gravity 10 1 instance 3 exposed
Issued
Jul 10, 2014
Abate by
Aug 28, 2014
Penalty
Initial $7,000 · Current $0 Reduced
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed:    Prudential Center buildings:  The employer did not provide appropriate work uniforms to the electricians in that the uniform content of the shirts was 60 percent cotton and meltable fibers of 40 percent polyester.  Additionally, some electricians were provided with short sleeved uniforms.  The uniform pants provided were 100 percent cotton which does not provide protection from arc flash hazards.
Recent events (3)
  • · F (S) $0
  • · C (S) $7000
  • · Z (S) $7000

1910.137 B02 VIII

Other-than-serious 2 instances 2 exposed
Issued
Jul 10, 2014
Abate by
Aug 7, 2014
Penalty
Initial $2,550 · Current $400 Reduced
29 CFR 1910.137(b)(2)(viii): Electrical protective equipment was not subjected to periodic electrical tests in accordance with Tables I-5 and I-6:    Prudential Center buildings:  Salisbury rubber insulating gloves, Class 0, Type 1 rated to 1000V AC had not been tested since the manufacture date of March 2005.
Recent events (3)
  • · F (O) $400
  • · C (S) $2550
  • · Z (S) $2550

1910.332 B01

Serious Gravity 10 2 instances 3 exposed
Issued
Jul 10, 2014
Abate by
Aug 28, 2014
Penalty
Initial $7,000 · Current $7,000
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments:    Prudential Center buildings:     (a)  Employees who perform electrical work and testing on energized electrical equipment and systems were not effectively trained in implementing electrical safety-related work practices for tasks such as changing lighting ballasts, removal and installation of overcurrent devices, and troubleshooting and repair of electrical equipment of up to 480 Volts.    (b)  Employees had not been effectively trained in the selection and use of electrical personal protective equipment such as uniform clothing selection, arc flash suits, head protection, and electrical rated gloves.
Recent events (3)
  • · F (S) $7000
  • · C (S) $7000
  • · Z (S) $7000

1910.335 A01 IV

Serious Gravity 1 1 instance 3 exposed
Issued
Jul 10, 2014
Abate by
Aug 28, 2014
Penalty
Initial $2,550 · Current $0 Reduced
29 CFR 1910.335(a)(1)(iv): Employees exposed to the danger of head injury from electric shock or burns due to contact with exposed energized parts did not wear nonconductive head protection:    Prudential Center buildings: Employees working on or near energized electrical equipment of up to 480 volts did not wear hard hats.
Recent events (3)
  • · F (S) $0
  • · C (S) $2550
  • · Z (S) $2550

1910.333 A01

Serious Gravity 10 2 instances 3 exposed
Issued
Jul 10, 2014
Abate by
Aug 28, 2014
Penalty
Initial $7,000 · Current $7,000
29 CFR 1910.333(a)(1): Live parts to which an employee was exposed were not deenergized before the employee worked on or near them:   (a) 111 Huntington Ave, Boston - 26th Floor:  An employee was shocked and burned when contact was made with live parts while testing and changing a lighting ballast where the circuit had not been de-energized.  (b) Prudential Center buildings:  Employees were exposed to live electrical parts while performing tasks including but not limited to changing ballasts for 277V lighting fixtures and installing and replacing overcurrent devices in equipment of up to 480 volts where the circuits had not been deenergized.
Recent events (3)
  • · F (S) $7000
  • · C (S) $7000
  • · Z (S) $7000

1910.333 B02 I

Other-than-serious 1 instance 3 exposed
Issued
Jul 10, 2014
Abate by
Aug 28, 2014
Penalty
Initial $2,550 · Current $400 Reduced
29 CFR 1910.333(b)(2)(i): The employer did not maintain a written copy of the procedures outlined in paragraph (b)(2) of 29 CFR 1910.333 available for inspection by employees and by the Assistant Secretary of Labor and his or her authorized representatives:    Prudential Center buildings:  The company did not have written procedures for locking out and/or tagging de-energized electrical equipment.
Recent events (3)
  • · F (O) $400
  • · C (S) $2550
  • · Z (S) $2550

View Crown Energy Services, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 339633257.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.