SECAUCUS, NJ —
OSHA Inspection: GENERAL GLASS INTERNATIONAL
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of GENERAL GLASS INTERNATIONAL in 101 VENTURE WAY, SECAUCUS, NJ 07094 (NAICS 327211). OSHA activity number 339639411.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- GENERAL GLASS INTERNATIONAL
- Site address
- 101 VENTURE WAY
- City
- SECAUCUS
- State
- NJ
- ZIP
- 07094
- Mailing
- 101 VENTURE WAY, SECAUCUS, NJ 07094
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 327211
- Employees
- 122
- Ownership type
- A
Citations
10 citations on file for this inspection.
1910.37 B05
- Issued
- Aug 26, 2014
- Penalty
- Initial $3,960 · Current $2,376 Reduced
General-duty citation text
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit": a) Establishment - Decorative Glass Area The door leading from the Decorative Glass Area to the other large open facility and exit to the outdoors was not marked as an exit. Violation observed on or about 03/21/2014.
Recent events (2)
- — I (S) $2376
- — Z (S) $3960
1910.184 C01
- Issued
- Aug 26, 2014
- Penalty
- Initial $4,950 · Current $2,970 Reduced
General-duty citation text
29 CFR 1910.184(c)(1): Sling(s) that were damaged or defective were used: a) Establishment - Cutting Table Area: Synthetic web sling with tears in the area of the sling's eye had not been removed from service. Violation observed on or about 03/05/2014.
Recent events (2)
- — I (S) $2970
- — Z (S) $4950
1910.212 A01
- Issued
- Aug 26, 2014
- Penalty
- Initial $6,930 · Current $4,158 Reduced
General-duty citation text
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks: a) Establishment - In the Forvet A & B Machine Area: Employees were exposed to flying glass chips or slugs as the polycarbonate shield was not hinged-down between the operator and the point of operation of the machine. Violation observed on or about 03/05/2014.
Recent events (2)
- — I (O) $4158
- — Z (S) $6930
1910.215 A01
- Issued
- Aug 26, 2014
- Penalty
- Initial $4,950 · Current $2,970 Reduced
General-duty citation text
29 CFR 1910.215(a)(1): Abrasive wheel(s) used on grinding machinery were not used with safety guard(s): a) Establishment - Maintenance Area: The Baldor Grinder was being used without tongue guards. Violation observed on or about 03/21/2014.
Recent events (2)
- — I (S) $2970
- — Z (S) $4950
1910.242 B
- Issued
- Aug 26, 2014
- Penalty
- Initial $3,960 · Current $2,376 Reduced
General-duty citation text
29 CFR 1910.242(b): Compressed air used for cleaning purposes was not reduced to less than 30 p.s.i.: a) Establishment - In the Forvet Machine Area Employees used compressed air which was measured at 72 p.s.i. for cleaning purposes in their work area. Violation observed on or about 03/05/2014.
Recent events (2)
- — I (S) $2376
- — Z (S) $3960
1910.303 B02
- Issued
- Aug 26, 2014
- Penalty
- Initial $4,950 · Current $2,970 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a) Establishment - Carpentry Shop Worker was utilizing a receptacle outlet box energized with 110V service that was hung from the ceiling and laid on some wood. Violation observed on or about 03/05/2014. b) Establishment - Maintenance and Door Department Worker was utilizing a receptacle outlet box energized with 110V service that was attached by a tie to the leg of a table and hanging near the floor.. Violation observed on or about 03/05/2014. c) Establishment - Forvet Machine Area Workers were using a relocatable power tap on the floor of the shop which is not an intended use for this device. Violation observed on or about 03/05/2014.
Recent events (2)
- — I (S) $2970
- — Z (S) $4950
1910.303 F02
- Issued
- Aug 26, 2014
- Penalty
- Initial $3,960 · Current $2,376 Reduced
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: (a) Establishment - Storage Area by the Lunchroom The distribution panel boards named LPT 1 and LPT2 at 208/120V 3PH 4W, did not have their overcurrent devices legibly marked and plant maintenance personnel were unclear as to some of the breaker purposes. Violation observed on or about 03/05/2014.
Recent events (2)
- — I (S) $2376
- — Z (S) $3960
1910.305 B01
- Issued
- Aug 26, 2014
- Penalty
- Initial $3,960 · Current $2,376 Reduced
General-duty citation text
29 CFR 1910.305(b)(1): Conductors entering boxes, cabinets, or fittings were not protected from abrasions: a) Establishment - Maintenance Area by the Baldor Grinder: The conductor entering the receptacle outlet box was not protected from being damaged as it entered the top of the box. Violation observed on or about 03/05/2014.
Recent events (2)
- — I (S) $2376
- — Z (S) $3960
1910.305 G01 IV A
- Issued
- Aug 26, 2014
- Penalty
- Initial $2,970 · Current $1,782 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: a) Establishment - Enco Milling Machine Area: Extension cord was used to supply power to components of the Enco Milling Machine instead of plugging the components directly to a permanent electrical outlet. Violation observed on or about 03/05/2014.
Recent events (2)
- — I (S) $1782
- — Z (S) $2970
1910.334 A02 II
- Issued
- Aug 26, 2014
- Penalty
- Initial $4,950 · Current $2,970 Reduced
General-duty citation text
29 CFR 1910.334(a)(2)(ii): There was a defect or evidence of damage that could have exposed an employee to injury and the defective or damaged item was not removed from service: a) Establishment - Glass Cutting Area The power cord to the Oreck vacuum had cuts to its insulation and the vacuum was still being used by employees to clean the carpet of the cutting table. Violation observed on or about 03/05/2014.
Recent events (2)
- — I (S) $2970
- — Z (S) $4950
More inspections at General Glass International
View General Glass International's full OSHA safety record →
More inspections in this industry (NAICS 327211)
More inspections in NJ
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339639411.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.