OSHA Inspection: BURRIS LOGISTICS, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of BURRIS LOGISTICS, INC. in 10900 CENTRAL PORT DR, ORLANDO, FL 32824 (NAICS 493120). OSHA activity number 339643348.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Burris Logistics, INC. — free Get an email when a new federal OSHA severe-injury report for Burris Logistics, INC. is published. One employer, no account, unsubscribe in one click.
Site address
10900 CENTRAL PORT DR
City
ORLANDO
State
FL
ZIP
32824
Mailing
10900 CENTRAL PORT DR, ORLANDO, FL 32824
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
493120
Employees
230
Ownership type
A

6 citations on file for this inspection.

1910.24 E

Deleted Serious Gravity 5 1 instance 3 exposed
Issued
Jun 30, 2014
Abate by
Nov 14, 2014
Penalty
Initial $6,000 · Current $0 Reduced
29 CFR 1910.24(e): The fixed stairs were not installed at angles to the horizontal between 30 and 50 degrees as outlined, but not limited to the combinations given in Table D-1.    a. At the maintenance shop, employees were exposed to a fall hazard, in that, a fixed stairway used daily to access the roof during refrigeration equipment inspections and testing was installed at a 76 degree angle.
Recent events (2)
  • — I (S) $0
  • — Z (S) $6000

1910.305 G02 III

Serious Gravity 5 1 instance 20 exposed
Issued
Jun 30, 2014
Penalty
Initial $3,400 · Current $2,800 Reduced
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws:    a. Delivery truck hook up area, employees were exposed to an electrical hazard, in that, the 220 volt charging station number 329 had the outer insulation pulled from the plug thus allowing pull to be transmitted to the terminal screws of the plug.
Recent events (2)
  • — I (S) $2800
  • — Z (S) $3400

1910.305 J02 IV

Serious Gravity 5 1 instance 20 exposed
Issued
Jun 30, 2014
Abate by
Oct 20, 2014
Penalty
Initial $5,000 · Current $4,400 Reduced
29 CFR 1910.305(j)(2)(iv): A receptacle installed in a wet or damp location was not suitable for the location:     a. Delivery truck hookup area, at the 30, 50 and 60 amp charge stations, employees were exposed to an electrical hazard, in that, 30 trailer hook up stations which were installed outdoors did not have waterproof receptacles.
Recent events (2)
  • — I (S) $4400
  • — Z (S) $5000

1910.304 G05

Other-than-serious 2 instances 9 exposed
Issued
Jun 30, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:  a. At the battery charging area, employees were exposed to an electrical hazard, in that, the flexible cord providing power to the fan was missing the ground prong.  b. At the shipping dock area,  employees were exposed to an electrical hazard, in that, two flexible cords providing power to the zone 1 shrink wrap machine were missing the ground prong.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.305 G01 IV A

Other-than-serious 3 instances 20 exposed
Issued
Jun 30, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:   a. At the battery charging area, employees were exposed to an electrical hazard, in that, a computer multi outlet extension strip was used to provide power to portable equipment such as a fan.   b. Receiving dock area, at the access point for the wireless network, employees were exposed to an electrical hazard, in that, a red extension cord was used in place of fixed wiring to provide power to the wireless router.  c. Maintenance shop area, employees were exposed to an electrical hazard, in that, a red extension cord was used in place of the fixed wiring to provide power to the water cooler.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.305 G01 IV D

Other-than-serious 1 instance 20 exposed
Issued
Jun 30, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords were attached to building surfaces:   a. Receiving dock area, at the access point for wireless network, employees were exposed to an electrical hazard, in that, a red extension cord was attached to the building to provide power to the wireless router.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Burris Logistics, INC.'s full OSHA safety record →