Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,197,549Inspections Most recent open 2026-08-27 Last loaded 2026-08-31

OSHA Inspection: PALLET WORLD, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of PALLET WORLD, INC. in 8292 FREMONT PIKE, PERRYSBURG, OH 43551 (NAICS 321920). OSHA activity number 339656050.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Pallet World, INC. for free Get an email when a new federal OSHA severe-injury report for Pallet World, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
PALLET WORLD, INC.
Site address
8292 FREMONT PIKE
City
PERRYSBURG
State
OH
ZIP
43551
Mailing
8292 FREMONT PIKE, PERRYSBURG, OH 43551
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
321920
Employees
54
Ownership type
Private (A)

5 citations on file for this inspection.

1910.305 B01 II

Serious Gravity 1 1 instance 10 exposed
Issued
May 15, 2014
Abate by
Jun 3, 2014
Penalty
Initial $2,100 · Current $2,100
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:  a. Pallet World, Inc. - Perrysburg, Ohio: On or about April 1, 2014, the employer did not ensure that unused openings in the electrical box, used to power the pallet conveyor and located near the pallet saws, were closed to protect employees from electrical shock hazards.
Recent events (2)
  • · I (S) $2100
  • · Z (S) $2100

1910.332 B01

Serious Gravity 10 1 instance 1 exposed
Issued
May 15, 2014
Abate by
Oct 4, 2014
Penalty
Initial $4,900 · Current $3,900 Reduced
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments:    a.  Pallet World, Inc. - Perrysburg, Ohio: On or about March 24, 2014, the employer did not ensure employees who are exposed to electrical hazards while performing work on or near energized parts were trained in electrical safety-related work practices.  A maintenance employee was exposed to electrical-related injuries in that safe work practices were not employed when performing electrical work/tests.
Recent events (2)
  • · I (S) $3900
  • · Z (S) $4900

1910.333 A

Deleted Serious Gravity 10 1 instance 1 exposed
Issued
May 15, 2014
Abate by
Jun 10, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.333(a): Safety-related work practices were not employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts, when work was performed near or on equipment or circuits which were or could be energized:  a. Pallet World, Inc. - Perrysburg, Ohio:  On or about March 24, 2014, the employer did not develop and implement electrical safety related work practices which cover employees exposed to live electrical conductors while performing electrical work.  Maintenance personnel responsible for troubleshooting and/or performing electrical tests were exposed to electrical in that safe work practices were not employed to prevent electrical shock and/or other injuries.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.333 A01

Deleted Serious Gravity 10 1 instance 1 exposed
Issued
May 15, 2014
Abate by
Jun 10, 2014
Penalty
Initial $4,900 · Current $0 Reduced
29 CFR 1910.333(a)(1): Live parts to which an employee may be exposed were not deenergized before the employee worked on or was near to them:  a.  Pallet World, Inc. - Perrysburg, Ohio: On or about March 25, 2014, an employee was exposed to electrical hazards in that the main electrical power distribution panel was not deenergized and locked out before employees accessed the downstream bus bar to perform tasks such as, but not limited to, verifying absence of energy and replacing fuses.  A maintenance worker was exposed to 480 volts while working near live parts at the bus bar to replace fuses located in the electrical panel for band saws.
Recent events (2)
  • · I (S) $0
  • · Z (S) $4900

1910.335 A01 I

Other-than-serious 1 instance 1 exposed
Issued
May 15, 2014
Abate by
Jul 10, 2014
Penalty
Initial $4,900 · Current $0 Reduced
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed:    a. Pallet World, Inc. - Perrysburg, Ohio: On or about March 24, 2014, the employer did not assure that employees who perform electrical tests to troubleshoot and verify absence of energy are provided with and use personal protective equipment to protect against electrical hazards.  A maintenance employee, using a multi-meter to troubleshoot circuits at the main 480 volt panel, was exposed to electrical shock and arc flash hazards in that flame resistant clothing, insulated gloves with leather gloves, hard hat, and arc rated face shield were not worn during the troubleshooting activities.
Recent events (2)
  • · I (O) $0
  • · Z (S) $4900

View Pallet World, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 339656050.