EL PASO, TX —
OSHA Inspection: INTERNATIONAL BOUNDARY & WATER COMMISSION
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of INTERNATIONAL BOUNDARY & WATER COMMISSION in 2616 W. PAISANO, EL PASO, TX 79922 (NAICS 928120). OSHA activity number 339670366.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- INTERNATIONAL BOUNDARY & WATER COMMISSION
- Site address
- 2616 W. PAISANO
- City
- EL PASO
- State
- TX
- ZIP
- 79922
- Mailing
- 2616 W. PAISANO, EL PASO, TX 79922
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 928120
- Employees
- 9
- Ownership type
- D
Citations
10 citations on file for this inspection.
1910.107 C06
- Issued
- Jul 18, 2014
- Abate by
- Jul 30, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.107(c)(6): Electrical wiring and equipment not subject to deposits of combustible residues but located in a spraying area as herein defined were not explosion-proof type approved for Class I, group D locations and did not otherwise conform to the provisions of subpart S of this part, for Class I, Division 1, Hazardous Locations: STORAGE/WELDING SHOP; On or about April 9, 2014 the employer did not ensure that electrical equipment and wiring were of explosion-proof type approved for Class I, group D locations. Employees engaged in spray painting operations were exposed to fire and explosion hazards.
Recent events (1)
- — Z (S) $0
1910.215 A04
- Issued
- Jul 18, 2014
- Abate by
- Jul 30, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.215(a)(4): On offhand grinding machines, work rests were not used to support the work and/or were not kept adjusted closely to the wheel with a maximum opening of one-eighth inch to prevent the work from being jammed between the wheel and the rest, which may cause wheel breakage. WELDING SHOP; On or about April 9, 2014 the employer did not ensure that the gap between a grinder's rest and abrasive wheel was 1/8 inch or less. This condition exposed employees to struck-by hazards.
Recent events (1)
- — Z (S) $0
1910.242 A
- Issued
- Jul 18, 2014
- Abate by
- Jul 30, 2014
- Penalty
- Initial $0 · Current $0
8870
General-duty citation text
29 CFR 1910.242(a): The employer did not ensure that employees were furnished with tools and equipment that were in a safe condition: WELDING SHOP; On or about April 9, 2014 the employer did not ensure that an angle grinder's electrical cord in need of repair and/or replacement was taken out of service until it was in safe operable condition. This condition exposed employees to hazards associated with electrical shock, arc, and sparks.
Recent events (1)
- — Z (S) $0
1910.243 C01
- Issued
- Jul 18, 2014
- Abate by
- Jul 30, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.243(c)(1): Abrasive wheel(s) were used on portable grinder(s) which were not provided with safety guard(s) meeting the requirements specified in 29 CFR 1910.243(c)(1) through (c)(4)(a): WELDING SHOP; On or about April 9, 2014 the employer did not ensure that employees using an angle grinder were provided with and/or required to use a guard when engaged in grinding operations. This condition exposed employees to hazards associated with struck-by hazards.
Recent events (1)
- — Z (S) $0
1910.252 A01 I
- Issued
- Jul 18, 2014
- Abate by
- Jul 30, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.252(a)(1)(i): When the object to be welded or cut could not be readily moved, all movable fire hazards in the vicinity were not taken to a safe place: WELDING SHOP; On or about April 9, 2014 the employer did not ensure that flammable paints and/or solvents in the welding area were removed to a safe location during welding operations. This condition exposed employees to fire hazards.
Recent events (1)
- — Z (S) $0
1910.254 D08
- Issued
- Jul 18, 2014
- Abate by
- Jul 30, 2014
- Penalty
- Initial $0 · Current $0
8870
General-duty citation text
29 CFR 1910.254(d)(8): Welding cables with splices within 10 feet (3 m) of the holder were used: WELDING SHOP; On or about April 9, 2014 the employer did not ensure that the welding lead on a welding machine (electric) was not used. The damaged area on the cable was wrapped with black electrical tap approximately two feet from the stinger. This condition exposed employees to hazards associated with electrical shock, arc, and sparks.
Recent events (1)
- — Z (S) $0
1910.304 B03 II A
- Issued
- Jul 18, 2014
- Abate by
- Jul 30, 2014
- Penalty
- Initial $0 · Current $0
8870
General-duty citation text
29 CFR 1910.304(b)(3)(ii)(A): All 125-volt, single-phase, 15, 20 and 30-ampere receptacle outlets that are not part of the permanent wiring of the building or structure and that are in use by personnel did not have ground-fault circuit-interrupter protection for personnel. MAINTENANCE/WELDING SHOP; On or about April 9, 2014the employer did not ensure that receptacle(s) were equipped with a GFCI system where construction type work was performed. This condition exposed employees to hazards associated with electrical shock, arc, and sparks.
Recent events (1)
- — Z (S) $0
1910.305 B01 II
- Issued
- Jul 18, 2014
- Abate by
- Jul 30, 2014
- Penalty
- Initial $0 · Current $0
8870
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: WELDING SHOP; On or about April 9, 2014 the employer did not ensure that an unused opening on a knife safety switch panel was closed. The knock-out tab had been removed. This condition exposed employees to hazards associated with electrical shock, arc, and sparks.
Recent events (1)
- — Z (S) $0
1910.305 C03 II
- Issued
- Jul 18, 2014
- Abate by
- Jul 30, 2014
- Penalty
- Initial $0 · Current $0
8870
General-duty citation text
29 CFR 1910.305(c)(3)(ii): Single-throw knife switches, molded-case switches, switches with butt contacts, and circuit breakers used as switches shall be connected so that the terminals supplying the load are deenergized when the switch is in the open position. However, blades and terminals supplying the load of a switch may be energized when the switch is in the open position where the switch is connected to circuits or equipment inherently capable of providing a backfeed source of power. For such installations, a permanent sign was not installed on the switch enclosure or immediately adjacent to open switches that read, "WARNING -- LOAD SIDE TERMINALS MAY BE ENERGIZED BY BACKFEED." WELDING SHOP; On or about April 9, 2014 the employer did not ensure that an energized knife safety switch panel was labeled with a warning sign as required by the standard and/or ensuring that the energized load side terminals were equipped with flash guards. This condition exposed employees to hazards associated with electrical shock, arc, and sparks.
Recent events (1)
- — Z (S) $0
1910.305 J07
- Issued
- Jul 18, 2014
- Abate by
- Jul 30, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(j)(7): Provisions were not made for sufficient diffusion and ventilation of gases from storage batteries to prevent the accumulation of explosive mixtures: MAINTENANCE/WELDING SHOP; On or about April 9, 2014 the employer did not ensure that batteries were not charged directly below a natural gas heater. This condition exposed employees to explosion hazards.
Recent events (1)
- — Z (S) $0
More inspections at International Boundary & Water Commission
View International Boundary & Water Commission's full OSHA safety record →
More inspections in this industry (NAICS 928120)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339670366.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.