SANTURCE, PR —
OSHA Inspection: U.S. IMMIGRATION AND CUSTOMS ENFORCEMENT-HSI SAN JUAN
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of U.S. IMMIGRATION AND CUSTOMS ENFORCEMENT-HSI SAN JUAN in 800 PONCE DE LEON AVENUE 12TH FLOOR, SANTURCE, PR 00907 (NAICS 928120). OSHA activity number 347484545.
Where did this inspection happen?
- Site address
- 800 PONCE DE LEON AVENUE 12TH FLOOR
- City
- SANTURCE
- State
- PR
- ZIP
- 00907
- Mailing
- P.O. BOX 13356, SAN JUAN, PR 00907
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 928120
- Employees
- 109
- Ownership type
- D
Citations
3 citations on file for this inspection.
1910.36 G02
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.36(g)(2): Exit access(es) were not at least 28 inches (71.1 cm) wide at all points. a. On or about May 21, 2024, at the basement warehouse area. There was a measurement of 20 inches wide along the exit access due to the storage of crates of large boxes on opposite sides which reduced the exit path, exposing employees working in the area. NOTE: Certification of abatement is not required for this citation item as abatement was documented by the compliance safety and health officer within 24 hours of the inspection.
Recent events (1)
- — Z (S) $0
1910.303 B02
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: On or about May 21, 2024, electrical equipment such as relocatable power tap (RPT) and extension cord were used in place of fixed firing to provide power to various appliances and computer equipment, exposing employees to electrical and fire hazards as follows: a. At the 11th floor, financial group department area. A seven-outlet relocatable ACE power tap/power strip surge protector (15-amp) was used to provide power to a Midea HS-160R compact refrigerator (8-amp) and a Ninja Coffee Bar appliance (13 amp). The Ninja appliance was series-connected to the power strip with an electrical cord. b. At the 11th floor, SA office area. Two (2) relocatable power taps (RPT); Efi Electronics and Tripp-Lite were series connected with an APC battery backup (XS 1500) to provide power to various computer and office equipment such as a Fellowes 99Ci paper shredder. NOTE: Certification of abatement is not required for this citation item as abatement was documented for both instances by the compliance safety and health officer within 24 hours of the inspection.
Recent events (1)
- — Z (S) $0
1910.303 G01
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: On or about May 21, 2024, electrical service panels were not readily accessible in the following areas: a. At the communications room - penthouse area, a portable IQ Air-air purifier unit was placed beneath one of the two electrical panels. b. At the 12th floor reception area, a work station table used for mailing forms and and supplies were placed in front of two electrical panels. NOTE: Certification of abatement is not required for this citation item as abatement was documented by the compliance safety and health officer within 24 hours of the inspection.
Recent events (1)
- — Z (O) $0
More inspections in this industry (NAICS 928120)
ATLANTA, GA—2026-05-19
DEPARTMENT OF HOMELAND SECURITY
WASHINGTON, DC—2025-06-02
ORGANIZATION OF AMERICAN STATES
ROMEOVILLE, IL—2025-02-27
NATIONAL WEATHER SERVICE OFFICE ROMEOVILLE-CHICAGO
NASHVILLE, TN—2024-04-16 00:00:00
DEPT OF HOMELAND SECURITY
BLACKSTONE, VA—2024-02-09 00:00:00
DIPLOMATIC SECURITY SERVICE OFFICE OF MOBILE SECURITY DEPLOYMENTS
More inspections in PR
PONCE, PR—2026-07-13
MACYS, PLAZA DEL CARIBE
SAN JUAN, PR—2026-07-10
PROYECTO ENLACE
PONCE, PR—2026-07-10
WILLIAM ECHEVARR�A ANDINO
CAROLINA, PR—2026-07-09
KFC ESCORIAL
CAROLINA, PR—2026-07-09
PIZZA HUT CAMPO RICO
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347484545.