Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: OREGON AIR NATIONAL GUARD, 173RD FW

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of OREGON AIR NATIONAL GUARD, 173RD FW in 211 ARNOLD AVENUE, SUITE 12, KLAMATH FALLS, OR 97603 (NAICS 928110). OSHA activity number 339699514.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Oregon AIR National Guard, 173RD FW — free Get an email when a new federal OSHA severe-injury report for Oregon AIR National Guard, 173RD FW is published. One employer, no account, unsubscribe in one click.
Site address
211 ARNOLD AVENUE, SUITE 12
City
KLAMATH FALLS
State
OR
ZIP
97603
Mailing
211 ARNOLD AVENUE, SUITE 12, KLAMATH FALLS, OR 97603
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
928110
Employees
240
Ownership type
D

2 citations on file for this inspection.

1910.37 B06

Serious Gravity 1 1 instance 60 exposed
Issued
May 1, 2014
Abate by
Jun 16, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(6): Each exit sign was not illuminated to a surface value of at least five foot-candles (54 lux) by a reliable light source and be distinctive in color:  Hanger 219:  On or about April 15, 2014 and times prior thereto, there were four exit doors that had no illumination.  This exposed employees to smoke inhalation hazards from delays in getting to the exit door.
Recent events (1)
  • — Z (S) $0

1910.303 G01 I B

Other-than-serious 1 instance 5 exposed
Issued
May 1, 2014
Abate by
May 15, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(i)(B): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the width of the working space in front of electrical equipment was less than the width of the equipment or 762 mm (30 inches), whichever was greater :  Building 249 hydraulic shop:  On or about April 15, 2014 and times prior thereto, the electrical panels were blocked by some work tables.  This exposed employees to tripping hazards getting access to the panel for examination.