Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,194,531Inspections Most recent open 2026-08-11 Last loaded 2026-08-14

OSHA Inspection: EISEN GROUP

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of EISEN GROUP in 3300 PANEL WAY, SAINT CHARLES, MO 63301 (NAICS 332312). OSHA activity number 339727703.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Eisen Group for free Get an email when a new federal OSHA severe-injury report for Eisen Group is published. One employer, no account, unsubscribe in one click.
Establishment
EISEN GROUP
Site address
3300 PANEL WAY
City
SAINT CHARLES
State
MO
ZIP
63301
Mailing
3300 PANEL WAY, SAINT CHARLES, MO 63301
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332312
Employees
37
Ownership type
A

3 citations on file for this inspection.

1910.252 A02 XIII C

Serious Gravity 1 2 instances 5 exposed
Issued
Sep 5, 2014
Penalty
Initial $1,785 · Current $1,250 Reduced
29 CFR 1910.252(a)(2)(xiii)(C): The employer did not insist that cutters or welders and their supervisors were suitably trained in the safe operation of their equipment and the safe use of the process:    Welding area:  Welders and their supervisor were not trained specifically in the safe use of cutting and welding equipment and the processes.
Recent events (2)
  • · I (S) $1249.5
  • · Z (S) $1785

1910.305 B01 II

Serious Gravity 5 1 instance 2 exposed
Issued
Sep 5, 2014
Penalty
Initial $2,975 · Current $2,083 Reduced
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:     Welding area: Four unused holes in a 480 volt energized electrical box used to supply power to a motor and a sensor were not closed to prevent employee exposure to electrical hazards.
Recent events (2)
  • · I (S) $2082.5
  • · Z (S) $2975

1910.1000 A02

Serious Gravity 1 1 instance 4 exposed
Issued
Sep 5, 2014
Penalty
Initial $1,785 · Current $1,250 Reduced

Hazardous substances 0731

29 CFR 1910.1000(a)(2): Employee(s) were exposed to an airborne concentration of copper fumes listed in Table Z-1 in excess of the 8 hour Time Weighted Average (TWA) concentration of  0.1 milligram per cubic meter (mg/m3):      Welding area: Employees who were performing welding operations were overexposed to copper fumes due to inadequate ventilation.  OSHA sampling was conducted on May 01, 2014.  Following 8-hour TWA results were obtained from the sampling 0.13 mg/m3, 0.23 mg/m3, 0.33 mg/m3, and 1.10 mg/m3. The values obtained were 2 to 10 1/2 times the permissible exposure limit (PEL) of 0.1 mg/m3.
Recent events (2)
  • · I (S) $1249.5
  • · Z (S) $1785

View Eisen Group's full OSHA safety record →