OSHA Inspection: ELECTRICAL INSTALLATIONS, INC.

Unprogrammed Other inspection · Safety discipline

On , OSHA opened an unprogrammed Other safety inspection of ELECTRICAL INSTALLATIONS, INC. in 18 SINCLAIR ROAD NORTHEAST HARBOR WASTE WATER TREATMENT PLANT, NORTHEAST HARBOR, ME 04662 (NAICS 238210). OSHA activity number 339749376.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Electrical Installations, INC. — free Get an email when a new federal OSHA severe-injury report for Electrical Installations, INC. is published. One employer, no account, unsubscribe in one click.
Site address
18 SINCLAIR ROAD NORTHEAST HARBOR WASTE WATER TREATMENT PLANT
City
NORTHEAST HARBOR
State
ME
ZIP
04662
Mailing
397 WHITTIER HIGHWAY, MOULTONBOROUGH, NH 03254
Inspection type
Unprogrammed Other (I)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
5
Ownership type
A

3 citations on file for this inspection.

1926.403 B02

Other-than-serious 2 instances 1 exposed
Issued
Jun 3, 2014
Abate by
Jun 9, 2014
Penalty
Initial $0 · Current $0
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification:   In the following instances, equipment were not installed in accordance to its listing, labeling or certification:   a) New Blower Room - Blue nonmetallic outlet box for the GFCI receptacle was not mounted or fastened.    b) New Blower Room - The nonmetallic sheathed cable used to energize the GFCI receptacle in the blue nonmetallic box was not supported and secured.
Recent events (1)
  • — Z (O) $0

1926.405 B01

Other-than-serious 6 instances 3 exposed
Issued
Jun 3, 2014
Abate by
Jun 9, 2014
Penalty
Initial $0 · Current $0
29 CFR 1926.405(b)(1): Unused openings in cabinets, boxes, and fittings were not effectively closed:  Outside New Blower Room - The weatherproof box had unused openings that were not effectively closed.
Recent events (1)
  • — Z (O) $0

1926.416 A03

Other-than-serious 3 instances 1 exposed
Issued
Jun 3, 2014
Abate by
Jun 9, 2014
Penalty
Initial $0 · Current $0
29 CFR 1926.416(a)(3): Employer did not post or maintain proper warning signs at locations where the performance of the work could bring a person, tool, or machine into physical or electrical contact with an energized electrical power circuit:   Motor Control Center Room -  Arc flash/blast warning stickers were not displayed on the newly installed Allen Bradley Centerline 2100 motor control center where three units were energized.