Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ELECTRICAL INSTALLATIONS, INC.

Unprogrammed Other inspection · Safety discipline

On , OSHA opened an unprogrammed Other safety inspection of ELECTRICAL INSTALLATIONS, INC. in DAVIS COURT, WILTON, ME 04294 (NAICS 238210). OSHA activity number 341947935.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Electrical Installations, INC. — free Get an email when a new federal OSHA severe-injury report for Electrical Installations, INC. is published. One employer, no account, unsubscribe in one click.
Site address
DAVIS COURT
City
WILTON
State
ME
ZIP
04294
Mailing
397 WHITTIER HIGHWAY, MOULTONBOROUGH, NH 03254
Inspection type
Unprogrammed Other (I)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
3
Ownership type
A

2 citations on file for this inspection.

1926.403 I01

Other-than-serious 1 instance 10 exposed
Issued
Jan 13, 2017
Abate by
Jan 24, 2017
Penalty
Initial $3,180 · Current $0 Reduced
29 CFR 1926.403(i)(1): Sufficient access and working space was not provided and maintained about all electric equipment to permit ready and safe operation and maintenance of such equipment:    MCC Room - Access to the energized breaker panel was blocked by a portable lift, unmounted fire extinguisher, and pail.
Recent events (2)
  • — I (O) $0
  • — Z (S) $3180

1926.405 B01

Serious Gravity 1 4 instances 10 exposed
Issued
Jan 13, 2017
Abate by
Jan 24, 2017
Penalty
Initial $7,483 · Current $7,483
29 CFR 1926.405(b)(1): Unused openings in cabinets, boxes, and fittings were not effectively closed:    Old MCC Room - The breaker panel behind the door had four unused openings that were not effectively closed.    Electrical Installations, Inc. was previously cited for a violation of this occupational safety and health standard or its equivalent standard, which was contained in OSHA inspection number 974937, citation number 1, item number 2 and was affirmed as a final order on 6/26/2014, with respect to a workplace located at 18 Sinclair Road, Northeast Harbor, Maine.
Recent events (2)
  • — I (S) $7483
  • — Z (R) $7483

View Electrical Installations, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341947935.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.