On , OSHA opened a planned safety inspection of BENADA ALUMINUM PRODUCTS, LLC in 2540 JEWETT LANE, SANFORD, FL 32771 (NAICS 331316). OSHA activity number 339760845.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Benada Aluminum Products, LLC — free Get an email when a new federal OSHA severe-injury report for Benada Aluminum Products, LLC is published. One employer, no account, unsubscribe in one click.
Site address
2540 JEWETT LANE
City
SANFORD
State
FL
ZIP
32771
Mailing
2540 JEWETT LANE, SANFORD, FL 32771
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
331316
Employees
200
Ownership type
A

11 citations on file for this inspection.

1910.147 C06 I

Serious Gravity 5 1 instance 10 exposed
Issued
Jul 22, 2014
Abate by
Aug 22, 2014
Penalty
Initial $3,825 · Current $2,295 Reduced
29 CFR 1910.147(c)(6)(i): The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirement of this standard were being followed:  a) For the Benada Aluminum Products facility as observed on or about 05/22/2014, periodic inspections of lockout tagout procedures were not conducted at least annually. Maintenance employees were not evaluated on specific lockout tagout procedures.
Recent events (2)
  • — I (S) $2295
  • — Z (S) $3825

1910.147 C07 I A

Serious Gravity 5 2 instances 10 exposed
Issued
Jul 22, 2014
Abate by
Aug 15, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.147(c)(7)(i)(A): Authorized employee(s) did not receive training in the recognition of applicable hazardous energy sources, the type and magnitude of the energy available in the workplace, and the methods and means necessary for energy isolation and control:  For the Benada Aluminum Products facility as observed on or about 05/22/2014:   a) Authorized maintenance employees were not trained on the energy control procedures.   b) Employees were not familiar with safe energy isolation practices, in that, employees were not aware of the requirement to place their own lock on energy isolating devices prior to working on equipment.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.335 A01 V

Serious Gravity 5 1 instance 2 exposed
Issued
Jul 22, 2014
Abate by
Aug 8, 2014
Penalty
Initial $3,825 · Current $2,295 Reduced
29 CFR 1910.335(a)(1)(v): Employees exposed to the danger of injury to the eyes or face from electric arcs or flashes or from flying objects resulting from electrical explosion did not wear protective equipment for the eyes or face:  a) For the Benada Aluminum Products facility as observed on or about 05/22/2014, employees performed voltage testing on live equipment/circuits ranging from 120VAC to 480VAC without face protection.
Recent events (2)
  • — I (S) $2295
  • — Z (S) $3825

1910.335 A01 I

Serious Gravity 5 1 instance 2 exposed
Issued
Jul 22, 2014
Abate by
Aug 8, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed:  a) For the Benada Aluminum Products facility as observed on or about 05/08/2014, electrical personal protective equipment to protect the hands, body and face from electric shock and electric arc flash hazards was not available and worn by maintenance employees while working on live circuits at voltages between 120VAC and 480VAC.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.332 B01

Serious Gravity 5 1 instance 2 exposed
Issued
Jul 22, 2014
Abate by
Aug 15, 2014
Penalty
Initial $3,825 · Current $2,295 Reduced
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments:  a) For the Benada Aluminum Products facility as observed between 05/22/2014 and 06/16/2014, maintenance employees who performed live voltage testing on circuits up to 480 VAC had not been trained on the hazards of electrical arc flash.
Recent events (2)
  • — I (S) $2295
  • — Z (S) $3825

1910.242 B

Repeat Gravity 5 2 instances 2 exposed
Issued
Jul 22, 2014
Abate by
Aug 1, 2014
Penalty
Initial $9,000 · Current $5,400 Reduced
29 CFR 1910.242(b): Compressed air used for cleaning. Compressed air shall not be used for cleaning purposes except where reduced to less than 30 p.s.i. and then only with effective chip guarding and personal protective equipment.  For the Benada Aluminum Products facility as observed on or about 05/02/2014, employees used compressed air for cleaning at pressures greater than 30 p.s.i.  a) In the forklift shop compressed air was used at a dead front pressure of 90 p.s.i.  b) At the billet saw, compressed air was used for cleaning at a dead front pressure of 60 p.s.i.   Benada Aluminum Products, LLC was previously cited for a violation of this occupational safety and health standard or its equivalent standard (29 CFR 1910.242(b)), which was contained in OSHA inspection number 316472679, citation number 1, item number 09, and was affirmed as a final order on 08/17/2012 with respect to a workplace located at 2540 Jewett Lane, Sanford, FL 32771.
Recent events (2)
  • — I (R) $5400
  • — Z (R) $9000

1910.253 B04 III

Repeat Gravity 5 1 instance 5 exposed
Issued
Jul 22, 2014
Penalty
Initial $7,200 · Current $4,320 Reduced
29 CFR 1910.253(b)(4)(iii): Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one-half hour.  a) For the Benada Aluminum Products facility as observed on or about 05/08/2014, oxygen compressed gas cylinders were stored right next to acetylene fuel compressed gas cylinders at the maintenance shop. This resulted in a fire hazard for employees.  Benada Aluminum Products, LLC was previously cited for a violation of this occupational safety and health standard or its equivalent standard (29 CFR 1910.253(b)(4)(iii)), which was contained in OSHA inspection number 316472679, citation number 1, item number 11, and was affirmed as a final order on 08/17/2012 with respect to a workplace located at 2540 Jewett Lane, Sanford, FL 32771.
Recent events (2)
  • — I (R) $4320
  • — Z (R) $7200

1910.253 E03 II C 2

Repeat Gravity 5 1 instance 5 exposed
Issued
Jul 22, 2014
Penalty
Initial $7,200 · Current $4,320 Reduced
29 CFR 1910.253(e)(3)(ii)(C)(2): Back flow protection was not provided by an approved device that would prevent oxygen from flowing into the fuel gas system or fuel from flowing into the oxygen system:  a) For the Benada Aluminum Products facility as observed on or about 05/08/2014, an oxygen-acetylene torch used on press # 2 was missing a backflow prevention device to keep oxygen from flowing into the fuel gas system exposing employees to fire hazards.  Benada Aluminum Products, LLC was previously cited for a violation of this occupational safety and health standard or its equivalent standard (29 CFR 1910.253(3)(3)(ii)(C)(2)), which was contained in OSHA inspection number 316472679, citation number 1, item number 10b, and was affirmed as a final order on 08/17/2012 with respect to a workplace located at 2540 Jewett Lane, Sanford, FL 32771.
Recent events (2)
  • — I (R) $4320
  • — Z (R) $7200

1910.253 E03 II C 3

Repeat Gravity 5 1 instance 5 exposed
Issued
Jul 22, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.253(e)(3)(ii)(C)(3): Flashback protection was not provided by an approved device that would prevent flame from passing into the fuel gas system:  a) For the Benada Aluminum Products facility as observed on or about 05/08/2014, an oxygen-acetylene torch at press #2 was missing a flashback arrestor exposing employees to fire hazards.  Benada Aluminum Products, LLC was previously cited for a violation of this occupational safety and health standard or its equivalent standard (29 CFR 1910.253(3)(3)(ii)(C)(3)), which was contained in OSHA inspection number 316472679, citation number 1, item number 10c, and was affirmed as a final order on 08/17/2012 with respect to a workplace located at 2540 Jewett Lane, Sanford, FL 32771.
Recent events (2)
  • — I (R) $0
  • — Z (R) $0

1910.147 C04 II D

Other-than-serious 1 instance 10 exposed
Issued
Jul 22, 2014
Abate by
Aug 8, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.147(c)(4)(ii)(D): The energy control procedures did not clearly and specifically outline the requirements for testing a machine or equipment to determine and verify the effectiveness of lockout devices, tagout devices, and other energy control:  a) For the Benada Aluminum Products facility as observed on or about 05/08/2014, energy control procedures did not specify to verify by testing that a machine or equipment such as, but not limited to, extruding equipment was effectively de-energized and locked out.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.303 B02

Other-than-serious 1 instance 2 exposed
Issued
Jul 22, 2014
Abate by
Jul 30, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  a) For the Benada Aluminum Products facility as observed on or about 5/22/2014, a portable power tap was used in an industrial environment, not rated for how it was being used, with equipment such as an industrial Dayton fan.