BARDWELL, TX —
OSHA Inspection: PENCCO, INC.
Programmed Related inspection · Health discipline
At a glance
On , OSHA opened a programmed Related health inspection of PENCCO, INC. in 6555 E. HWY 34, BARDWELL, TX 75101 (NAICS 325998). OSHA activity number 339770786.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- PENCCO, INC.
- Site address
- 6555 E. HWY 34
- City
- BARDWELL
- State
- TX
- ZIP
- 75101
- Mailing
- 6555 E. HWY 34, BARDWELL, TX 75101
What kind of inspection was it?
- Inspection type
- Programmed Related (J)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 325998
- Employees
- 5
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.106 H06 III
- Issued
- Aug 5, 2014
- Abate by
- Sep 3, 2014
- Penalty
- Initial $4,900 · Current $0 Reduced
General-duty citation text
29 CFR 1910.106(h)(6)(iii): "Alarm systems." An approved means for prompt notification of fire to those within the plant and any public fire department available was not provided. It may be advisable to connect the plant system with the public system where public fire alarm system is available. On or about May 16, 2014 and at times prior thereto, a fire alarm system or alert system was not provided to warn employees of an unexpected/emergency fire where employees were exposed to fire, flash fire, and explosion hazards.
Recent events (3)
- — F (S) $0
- — C (S) $4900
- — Z (S) $4900
1910.106 H07 I A
- Issued
- Aug 5, 2014
- Abate by
- Sep 3, 2014
- Penalty
- Initial $4,900 · Current $0 Reduced
General-duty citation text
29 CFR 1910.106(h)(7)(i)(a): Precautions were not taken to prevent the ignition of flammable vapors. Sources of ignition include but are not limited to open flames; lightning; smoking; cutting and welding; hot surfaces; frictional heat; static, electrical, and mechanical sparks; spontaneous ignition, including heat-producing chemical reactions; and radiant heat. On or about May 16, 2014 and at times prior thereto, at the facility the employer did not put in place a system to prevent the ignition of flammable vapors such as but not limited to hydrogen gas created during the chemical process exposing employees to fire, flash fire, and explosion hazards.
Recent events (3)
- — F (S) $0
- — C (S) $4900
- — Z (S) $4900
1910.134 E01
- Issued
- Aug 5, 2014
- Abate by
- Sep 3, 2014
- Penalty
- Initial $2,100 · Current $2,100
General-duty citation text
29 CFR 1910.134(e)(1): The employer did not provide a medical evaluation to determine the employee's ability to use a respirator, before the employee was fit tested or required to use the respirator in the workplace: Note: The employer may discontinue an employee's medical evaluations when the employee is no longer required to use a respirator. On or about May 16, 2014 and at times prior thereto, employees engaged in loading and unloading hazardous chemicals, such as but not limited to, acids were required to wear half-mask respirators and the employer did not provide medical evaluations.
Recent events (2)
- — I (S) $2100
- — Z (S) $2100
1910.134 F01
- Issued
- Aug 5, 2014
- Abate by
- Sep 3, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.134(f)(1): The employer did not ensure that employee(s) required to use a tight-fitting facepiece respirator passed the appropriate qualitative fit test (QLFT) or quantitative fit test (QNFT): On or about May 16, 2014 and at times prior thereto, employees engaged in loading and unloading hazardous chemicals, such as but not limited to, acids were required to wear half-mask respirators and the employer did not provide fit testing.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections at Pencco, INC.
View Pencco, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 325998)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339770786.