FERNDALE, WA —
OSHA Inspection: CUSTOMS AND BORDER PROTECTION, BELLINGHAM PATROL STATION
Planned inspection · Health discipline
At a glance
On , OSHA opened a planned health inspection of CUSTOMS AND BORDER PROTECTION, BELLINGHAM PATROL STATION in 1431 SUNSET AVE, FERNDALE, WA 98248 (NAICS 928110). OSHA activity number 339774978.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Site address
- 1431 SUNSET AVE
- City
- FERNDALE
- State
- WA
- ZIP
- 98248
- Mailing
- 1431 SUNSET AVE, FERNDALE, WA 98248
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 928110
- Employees
- 69
- Ownership type
- D
Citations
6 citations on file for this inspection.
1910.1025 H01
- Issued
- Jun 10, 2014
- Abate by
- Jul 28, 2014
- Penalty
- Initial $0 · Current $0
1591
General-duty citation text
29 CFR 1910.1025(h)(1): All surfaces were not maintained as free as practicable of accumulations of lead: a) Weapons Cleaning Bench, where an effective housekeeping schedule was not in place to ensure all surfaces were maintained as free as practicable of accumulations of lead.
Recent events (1)
- — Z (S) $0
1910.303 B02
- Issued
- Jun 10, 2014
- Abate by
- Jul 28, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled equipment was not installed and used in accordance with any instructions included in the listing or labeling: a) Facility, where electrical equipment not used as listed or labeled included: 1. Room 113, where the APC relocatable power tap was used to supply power to the Sylvania microwave oven. 2. Room 115, where the APC relocatable power tap was daisy chained with a black relocatable power tap and used to supply power to computer equipment. 3. Room 116, where a relocatable power tap was used to supply power to the Keurig coffee maker. 4. Room 124, where the APC relocatable power tap was used to supply power to the Hamilton Beach coffee maker. The U.S. Customs & Border Protection Patrol was previously cited for a violation of this standard which was contained in OSHA inspection no. 242715.015, citation no. 2, item no. 1, issued on March 9, 2012 with respect to a workplace at Bellingham, WA. The U.S. Customs & Border Protection Patrol was previously cited for a violation of this standard which was contained in OSHA inspection no. 110160.015, citation no. 1, item no. 1, issued on January 11, 2012 with respect to a workplace at Blaine, WA.
Recent events (1)
- — Z (R) $0
1910.303 G01 II
- Issued
- Jun 10, 2014
- Abate by
- Jul 28, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(ii): Working space for equipment likely to require examination, adjustment, servicing, or maintenance while energized was used for storage: a) Sensor Shop, where items including gun lockers, fire extinguishers and storage totes were stored in front of electrical panel VML. The U.S. Customs & Border Protection Patrol was previously cited for a violation of this standard which was contained in OSHA inspection no. 242715.015, citation no. 2, item no. 2, issued on March 9, 2012 with respect to a workplace at Bellingham, WA. The U.S. Customs & Border Protection Patrol was previously cited for a violation of this standard which was contained in OSHA inspection no. 110160.015, citation no. 2, item no. 2, issued on January 11, 2012 with respect to a workplace at Blaine, WA. The U.S. Customs & Border Protection Patrol was previously cited for a violation of this standard which was contained in OSHA inspection no. 309097897, citation no. 2, item no. 2, issued on July 19, 2010 with respect to a workplace at Sumas, WA.
Recent events (1)
- — Z (R) $0
1910.157 E01
- Issued
- Jun 10, 2014
- Abate by
- Jul 28, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(e)(1): The employer was not responsible for the inspection, maintenance and testing of all portable fire extinguishers in the workplace: a) Government Vehicles, where employees would be expected to fight incipient stage fires, the Kidde fire extinguisher was equipped with an inspection tag dated April 2013.
Recent events (1)
- — Z (O) $0
1910.157 E02
- Issued
- Jun 10, 2014
- Abate by
- Jul 28, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(e)(2): Portable fire extinguishers were not visually inspected at least monthly: a) Government Vehicles, where employees would be expected to fight incipient stage fires, fire extinguishers such as, Kidde extinguishers, located in the government owned vehicles were not inspected on a monthly basis.
Recent events (1)
- — Z (O) $0
1910.1200 G08
- Issued
- Jun 10, 2014
- Abate by
- Jul 28, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.1200(g)(8): The employer did not maintain in the workplace copies of the required safety data sheets for each hazardous chemical, and did not ensure that they were readily accessible during each work shift to employees when they were in their work area(s): a) Facility, where safety data sheets were not maintained for ammunition including, but not limited to, Federal 50 Centerfire Pistol Cartridges.
Recent events (1)
- — Z (O) $0
More inspections at Customs and Border Protection, Bellingham Patrol Station
View Customs and Border Protection, Bellingham Patrol Station's full OSHA safety record →
More inspections in this industry (NAICS 928110)
More inspections in WA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339774978.