Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: BELTEX CORPORATION

Follow-up inspection · Safety discipline

On , OSHA opened a follow-up safety inspection of BELTEX CORPORATION in 3801 N. GROVE STREET, FORT WORTH, TX 76106 (NAICS 311611). OSHA activity number 339782633.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Beltex Corporation — free Get an email when a new federal OSHA severe-injury report for Beltex Corporation is published. One employer, no account, unsubscribe in one click.
Establishment
BELTEX CORPORATION
Site address
3801 N. GROVE STREET
City
FORT WORTH
State
TX
ZIP
76106
Mailing
3801 N. GROVE STREET, FORT WORTH, TX 76106
Inspection type
Follow-up (F)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
311611
Employees
130
Ownership type
A

5 citations on file for this inspection.

1910.305 B01 II

Serious Gravity 5 4 instances 15 exposed
Issued
Oct 28, 2014
Abate by
Nov 26, 2014
Penalty
Initial $4,500 · Current $2,700 Reduced
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:    On or about May 28, 2014 and at times prior thereto, the employer did not ensure that unused openings were effectively closed or covered exposing employees to electrical shock and fire hazards:    a) In the compressor room the 480 volt square D east and west panel boxes had opened holes in the front panel and on the bottom of the panels;    b) In the box storage room a 6 amp, 240 volt 3 phase panel box had opened holes in the bottom;    c) In the boiler room the electrical circuit breaker panel had two opened holes; and    d) In the small deboning entry room the circuit breaker panel box had an opened hole and the panel box had an opened hole in the bottom.
Recent events (2)
  • — I (S) $2700
  • — Z (S) $4500

1910.305 B02 I

Serious Gravity 5 3 instances 7 exposed
Issued
Oct 28, 2014
Abate by
Nov 26, 2014
Penalty
Initial $4,500 · Current $2,700 Reduced
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose:    On or about May 28, 2014 and at times prior thereto, the employer did not ensure that employees were not exposed to electrical and fire hazards where approved covers were not provided:    a) In the compressor room, the 480 volt raceway cover was not attached and opened exposing the internal wiring, and two Mercoid controls did not have covers;    b) Outside of the small kill room, the Leeson water pump was plugged into a two receptacle outlet box that did not have a cover; and    c) In the small kill deboning room against the back wall behind the conveyer, a 120 volt two receptacle outlet box did not have a cover.
Recent events (2)
  • — I (S) $2700
  • — Z (S) $4500

1910.212 A03 II

Repeat Gravity 5 1 instance 2 exposed
Issued
Oct 28, 2014
Abate by
Nov 26, 2014
Penalty
Initial $9,000 · Current $5,400 Reduced
29 CFR 1910.212(a)(3)(ii): Point(s) of operation of machinery were not guarded to prevent employee(s) from having any part of their body in the danger zone(s) during operating cycle(s):    On or about May 28, 2014 and at times prior thereto, in the large deboning room 7041B, the employer did not ensure that the model 55 meat band saw that was being operated was adjusted to the height of the material being cut.  The blade guard was locked in the upright highest point with approximately 14 inches of rotating blade exposing the employees to amputation hazards.    The Beltex Corporation (Frontier Meats) was previously cited for a violation of this occupational safety and health standard or its equivalent standard 1910.212(a)(3)(ii), which was contained in OSHA inspection number 661358, citation number 1, item number 2 and was affirmed as a final order on 04/04/13, with a final abatement date of 04/09/13, with respect to a workplace located at 3801 N. Grove Fort worth, Texas 76106.
Recent events (2)
  • — I (R) $5400
  • — Z (R) $9000

1910.219 F03

Repeat Gravity 5 2 instances 10 exposed
Issued
Oct 28, 2014
Abate by
Nov 26, 2014
Penalty
Initial $9,000 · Current $5,400 Reduced
29 CFR 1910.219(f)(3): Sprocket wheels and chains which were seven -7 feet or less above floors or platforms were not enclosed.    On or about May 28, 2014 and at times prior thereto, the employer did not ensure that all sprockets and chains in the plant were guarded to protect the employees from caught in and amputation hazards:    a) Outside the small kill room employees operated a conveyer belt in the Boar hide collection area and the sprocket and chain was not fully guarded; and    b) In the small kill processing area employees operated a conveyer belt and the sprockets and chain underneath the conveyor were not guarded.    The Beltex Corporation (Frontier Meats) was previously cited for a violation of this occupational safety and health standard or its equivalent standard 1910.219(f)(3), which was contained in OSHA inspection number 661358, citation number 1, item number 4 and was affirmed as a final order on 04/04/13, with a final abatement date of 04/09/13, with respect to a workplace located at 3801 N. Grove Fort worth, Texas 76106.
Recent events (2)
  • — I (R) $5400
  • — Z (R) $9000

1910.305 G01 IV B

Repeat Gravity 5 3 instances 70 exposed
Issued
Oct 28, 2014
Abate by
Nov 26, 2014
Penalty
Initial $9,000 · Current $5,400 Reduced
29 CFR 1910.305(g)(1)(iv)(B): Flexible cords and cables were run through holes in walls, ceilings, or floors:     On or about May 29, 2014 and at times prior thereto, in the small kill room and the large kill room, employees used flexible cords running through the ceiling and walls to power items such as but not limited to hand tools, fans, and light fixtures exposing them to electrical shock and fire hazards.      The Beltex Corporation (Frontier Meats) was previously cited for a violation of this occupational safety and health standard or its equivalent standard 1910.305(g)(1)(iv)(B), which was contained in OSHA inspection number 661358, citation number 1, item number 5b and was affirmed as a final order on 04/04/13, with a final abatement date of 04/09/13, with respect to a workplace located at 3801 N. Grove Fort worth, Texas 76106.